Chapter 3 Termination board wiring

The link repeater is limited to 60 devices on either side of the link (120 devices total).

The link repeater requires an earth ground. The installer should be aware of this before making power connections.

Recommended shield connections are shown in Figure 19. Figure 20 on page 39 shows a daisy-chain repeater connection. Follow these guidelines when using a repeater:

Reference the installation information that comes with the link repeater (Comm5 repeater installation, 3270 3285).

Connect the shield-drain wires entering the repeater to a terminal marked with a capacitor symbol. The entering shield-drain wire must be connected to earth ground at the Tracker controller.

Connect the shield-drain wires leaving the repeater to the repeater terminal marked with an earth ground symbol.

Figure 19. Connecting communication link shield wiring to repeater

24 Vac

Transformer

Earth ground

Entering shield. Continuous run, typically starting at the Tracker controller.

Leaving shield. Must be connected to the earth ground terminal on the repeater and terminated (insulated from ground) at the last UCM.

Link Repeater

124 VAC

3

Comm

4

5

6

Comm

7

8

9

Legend

=

Transformer

=

Earth ground

=

Twisted pair, shielded wire

=

Shield ground

per Trane specifications

 

 

 

 

 

38

BMTK-SVN01D-EN

Image 46
Contents Building Automation System Page BMTK-SVN01D-EN February Page BMTK-SVN01D-EN BMTK-SVN01D-EN Contents Appendix a Appendix BOverview Tracker controllerOverview Overview Controller components Tracker controller componentsTermination module Termination moduleMain module Main moduleDisplay module Display moduleModel numbers Model number definitionTracker Controller specifications Tracker controller specificationsSpecification Description Tracker controller models 12 and 24 UCM capacities UCM maximum capacities for Tracker models 12Tracker model UCM type Maximum UCMs Tracker controller model Wshp UCM capacities UCM maximum capacities for Tracker model Wshp105 Inspect for shipping damage Before installationVerify the shipment Store unused components until needed Avoid Equipment DamageAfter installation Tracker controller post-installation checklistFCC compliance Termination module mounting Verify location conformance to controller specificationsSelect a location for the controller Termination module mounting Minimum clearances Optimal touch screen viewing angles Termination module conduit access and mounting holes Mount the termination moduleSecuring the termination module to a wall Securing the termination module to a conduit boxInstalling electrical conduit Electrical conduit installationTermination module mounting Termination board wiring Termination board wiring Power wiring specifications Wire 24 Vac powerVac power Description Wire specifications Terminals Input and output wire specifications Wire optional inputs and outputsInput and output Description Wire specifications Terminals Wire the alarm relay Wire the priority shutdown deviceWire the utility pulse meter Wire the thermistorWire the UCMs Wire specificationsTrane-approved wire suppliers Supplier Cable type Number Details Catalog PairsSpecifications for Echelon Level 4 compliant cables Specification ValueUCM wiring configurations Figure NoteWire the UCMs Resistor color band table Termination resistor placement for Comm5 linksTolerance Color sequence Daisy-chain termination resistor placement Tracker Wire supported UCMs Requirements for repeaters on Comm5 communication linksConnecting communication link shield wiring to repeater Comm5 daisy-chain repeater connection Termination board wiring Main module mounting Main module mounting Display module mounting Display module mounting Display module engagement Display module mounting Cable and adapter specifications for direct connection PC workstation wiringVerify PC workstation specifications Direct connection to PC workstationPC workstation wiring Tracker direct connection to a PC workstation Modem connection to PC workstation Tracker modem connection to a PC workstation Connecting over an existing LAN Ethernet connection to PC workstationConnecting through a hub Tracker Controller PC WorkstationConnecting with one cable Service pin buttons and jumper TroubleshootingTroubleshooting components LEDsTroubleshooting LED name Alarm LEDTracker main logic board LEDs Color Description NumberMain logic board service pin buttons and jumper Service pin buttons/jumper FunctionSymptom/action troubleshooting Symptom/action troubleshootingSymptom Action Present of the proper severity to actuate the alarm output Symptom/action troubleshooting Troubleshooting Cleaning the touch screen MaintenanceCalibrating the touch screen Maintenance Optional supplies checklist Installation checklistsRequired supplies checklist Required suppliesComm5 UCM identification and location Comm5 UCM identification and locationSpace Comfort Controllers 24 maximum Space Comfort Controllers VariTrac central control panels 10 maximum Modules 4 maximumPre-installation wiring notes Termination module post-installation checklist Termination module post-installation checklistCircuit Mandatory Test Actual value Wiring Thermistor sensor electrical characteristics Temperature ºF Temperature ºC Sensor resistance Ohms xAppendix a Installation checklists Declaration of Conformity Electromagnetic Emission When and where issuedProduct Number BMTK000AA0A110 Mark of Compliance European ContactIndex NumericsIndex Index Index Page Trane