Trane BMTK-SVN01D-EN, Building Automation System Termination module post-installation checklist

Page 78

®

Appendix A Installation checklists

Termination module post-installation checklist

Use Table 18 to verify that the circuits connected to the termination board on the termination module are wired correctly. Record test results in the “Actual value” column.

Table 18. Termination module post-installation checklist

Circuit

Mandatory

Test

Actual value

wiring

 

 

 

 

 

 

 

24 Vac

 

Measure the voltage between TB1-1 and TB1-2. It must be 24 Vac

 

TB1-1,

 

nominal (19 Vac to 30 Vac).

 

TB1-2,

9

Measure the voltage between TB1-1 and TB1-3. It must be approxi-

 

TB1-3

mately the same voltage as measured between TB1-1 and TB1-2

 

 

 

The ground wire must be connected to terminal TB-3. It must be

 

 

 

tied to building or earth ground at nearest location. Measure the

 

 

 

voltage between TB1-2 and TB1-3. It must be approximately 0 V.

 

 

 

 

 

Alarm relay

 

Measure the voltage between TB1-4 and TB1-5. It must not exceed

 

TB1-4,

 

24 Vac. Jumper these two terminals. The user-supplied load should

 

TB1-5

 

now be energized and active.

 

 

 

 

 

Priority

 

There must be no voltage applied to these terminals. These termi-

 

shutdown

 

nals must be connected to dry contacts only. Measure the resis-

 

TB1-6,

 

tance between TB1-6 and TB1-7. It must be approximately 0 with

 

TB1-7

 

the user-supplied contacts in the closed position, and infinity ohms

 

 

 

with the contacts in the open position.

 

 

 

 

 

Meter input

 

There must be no voltage applied to these terminals. The terminals

 

TB1-8,

 

must be connected to dry contacts only. Measure the resistance

 

TB1-9

 

between TB1-8 and TB1-9. It must be approximately 0 with

 

 

 

demand meter contacts in the closed position, and infinity ohms

 

 

 

with the contacts in the open position.

 

 

 

 

 

Thermistor

 

There must be no voltage applied to these terminals. The cable

 

TB1-10,

 

shield must be connected to terminal TB1-12. Measure the resis-

 

TB1-11,

 

tance between TB1-10 and TB1-11.

 

TB1-12

 

Note the approximate temperature at the location of the outdoor

 

 

 

air temperature sensor.

 

 

 

 

 

 

 

Compare the resistance and temperature values to the listed val-

 

 

 

ues in Table 19 on page 71.

 

 

 

 

 

Comm

 

There must be no voltage applied to these terminals. Measure the

 

TB1-13,

9

resistance between TB1-13 and TB1-14. The resistance must be

 

TB1-14,

approximately 50 with daisy-chained wiring. This test confirms

 

TB1-15

 

the correct usage of the termination resistors as well as the conti-

 

 

 

nuity of the wire.

 

 

 

 

 

70

BMTK-SVN01D-EN

Image 78
Contents Building Automation System Page BMTK-SVN01D-EN February Page BMTK-SVN01D-EN BMTK-SVN01D-EN Contents Appendix a Appendix BOverview Tracker controllerOverview Overview Controller components Tracker controller componentsTermination module Termination moduleMain module Main moduleDisplay module Display moduleModel numbers Model number definitionTracker controller specifications Tracker Controller specificationsSpecification Description UCM maximum capacities for Tracker models 12 Tracker controller models 12 and 24 UCM capacitiesTracker model UCM type Maximum UCMs UCM maximum capacities for Tracker model Wshp Tracker controller model Wshp UCM capacities105 Inspect for shipping damage Before installationVerify the shipment Store unused components until needed Avoid Equipment DamageAfter installation Tracker controller post-installation checklistFCC compliance Verify location conformance to controller specifications Termination module mountingSelect a location for the controller Termination module mounting Minimum clearances Optimal touch screen viewing angles Termination module conduit access and mounting holes Mount the termination moduleSecuring the termination module to a wall Securing the termination module to a conduit boxInstalling electrical conduit Electrical conduit installationTermination module mounting Termination board wiring Termination board wiring Wire 24 Vac power Power wiring specificationsVac power Description Wire specifications Terminals Wire optional inputs and outputs Input and output wire specificationsInput and output Description Wire specifications Terminals Wire the alarm relay Wire the priority shutdown deviceWire the utility pulse meter Wire the thermistorWire the UCMs Wire specificationsTrane-approved wire suppliers Supplier Cable type Number Details Catalog PairsSpecifications for Echelon Level 4 compliant cables Specification ValueUCM wiring configurations Figure NoteWire the UCMs Termination resistor placement for Comm5 links Resistor color band tableTolerance Color sequence Daisy-chain termination resistor placement Tracker Wire supported UCMs Requirements for repeaters on Comm5 communication linksConnecting communication link shield wiring to repeater Comm5 daisy-chain repeater connection Termination board wiring Main module mounting Main module mounting Display module mounting Display module mounting Display module engagement Display module mounting Cable and adapter specifications for direct connection PC workstation wiringVerify PC workstation specifications Direct connection to PC workstationPC workstation wiring Tracker direct connection to a PC workstation Modem connection to PC workstation Tracker modem connection to a PC workstation Connecting over an existing LAN Ethernet connection to PC workstationConnecting through a hub Tracker Controller PC WorkstationConnecting with one cable Service pin buttons and jumper TroubleshootingTroubleshooting components LEDsTroubleshooting LED name Alarm LEDTracker main logic board LEDs Color Description NumberMain logic board service pin buttons and jumper Service pin buttons/jumper FunctionSymptom/action troubleshooting Symptom/action troubleshootingSymptom Action Present of the proper severity to actuate the alarm output Symptom/action troubleshooting Troubleshooting Maintenance Cleaning the touch screenCalibrating the touch screen Maintenance Optional supplies checklist Installation checklistsRequired supplies checklist Required suppliesComm5 UCM identification and location Comm5 UCM identification and locationSpace Comfort Controllers 24 maximum Space Comfort Controllers VariTrac central control panels 10 maximum Modules 4 maximumPre-installation wiring notes Termination module post-installation checklist Termination module post-installation checklistCircuit Mandatory Test Actual value Wiring Thermistor sensor electrical characteristics Temperature ºF Temperature ºC Sensor resistance Ohms xAppendix a Installation checklists Declaration of Conformity Electromagnetic Emission When and where issuedProduct Number BMTK000AA0A110 Mark of Compliance European ContactIndex NumericsIndex Index Index Page Trane