Trane Building Automation System, BMTK-SVN01D-EN Symptom/action troubleshooting, Symptom Action

Page 67

®

Symptom/action troubleshooting

Symptom/action troubleshooting

Table 14 provides a list of symptoms that indicate a problem in the Tracker system. For each symptom, the table provides one or more actions that you can perform in an attempt to resolve the problem.

Table 14. Symptom/action troubleshooting

Symptom

Action

 

 

Tracker controller does not

Verify that the telephone cable is connected to the PC modem port (Figure 24 on

communicate by modem.

page 48).

 

Verify that the phone line is an analog line (not digital).

 

Perform the modem self-test procedure from the display module.

 

Note: The modem is an integral component of the main module and is not field replaceable.

 

Replacement of the modem requires replacement of the main module.

 

 

Tracker controller does not

Verify that the cable is connected to the PC direct connect port (Figure 24 on

communicate by EIA-232

page 48).

port.

Verify that the proper cable is used. (Refer to Table 10 on page 47.)

 

 

Verify that the PC workstation is using the Tracker controller software; other com-

 

munications software will not work.

 

Look for activity on the PC RX LED (Figure 30 on page 56).

 

 

Tracker controller did not

When the controller is initially powered up, it automatically discovers all communi-

discover UCMs when ini-

cating UCMs of the proper type and installs them into its database. The discovery

tially started.

process takes several minutes, depending on how many UCMs are installed on the

 

communication link.

 

After the controller has built its database after the initial power up, the controller no

 

longer automatically discovers UCMs. If you want to initiate the discovery process,

 

you must do so manually. Initiate the discovery process when a new UCM is added

 

to the system or an existing UCM is replaced.

 

Verify proper wiring of the Comm5 communication link. (UCMs can be discov-

 

ered only if Comm5 communication has been established.)

 

Wait at least 5 minutes for the controller to discover the UCMs.

 

Note: You can press the service pin button on a UCM at any time to check if it is communicating

 

with the controller. Pressing the service pin button causes the UCM status LED to flash on and off

 

(known as “winking”), if the controller is communicating with that UCM.

 

 

Touch screen beeps when

Touch screen is out of calibration.

touched but does not

Perform the procedures for calibrating the touch screen in Tracker Building Auto-

progress to the next screen.

mation System Controller Operations guide (BMT-SVU01A-EN).

 

 

 

Touch-screen back light and

Perform the adjust brightness and contrast procedure from the display module.

contrast is out of adjust-

 

ment.

 

 

 

Tracker I/O status is wrong.

Verify electrical connection using the post-installation checklist (Table 18 on

 

page 70).

 

Verify I/O status as indicated on home display on the display module.

 

Display Tracker I/O status self test from display module.

 

 

BMTK-SVN01D-EN

59

Image 67
Contents Building Automation System Page BMTK-SVN01D-EN February Page BMTK-SVN01D-EN BMTK-SVN01D-EN Contents Appendix B Appendix aTracker controller OverviewOverview Overview Tracker controller components Controller componentsTermination module Termination moduleMain module Main moduleDisplay module Display moduleModel number definition Model numbersTracker Controller specifications Tracker controller specificationsSpecification Description Tracker controller models 12 and 24 UCM capacities UCM maximum capacities for Tracker models 12Tracker model UCM type Maximum UCMs Tracker controller model Wshp UCM capacities UCM maximum capacities for Tracker model Wshp105 Store unused components until needed Avoid Equipment Damage Before installationVerify the shipment Inspect for shipping damageTracker controller post-installation checklist After installationFCC compliance Termination module mounting Verify location conformance to controller specificationsSelect a location for the controller Termination module mounting Minimum clearances Optimal touch screen viewing angles Mount the termination module Termination module conduit access and mounting holesSecuring the termination module to a conduit box Securing the termination module to a wallElectrical conduit installation Installing electrical conduitTermination module mounting Termination board wiring Termination board wiring Power wiring specifications Wire 24 Vac powerVac power Description Wire specifications Terminals Input and output wire specifications Wire optional inputs and outputsInput and output Description Wire specifications Terminals Wire the priority shutdown device Wire the alarm relayWire the thermistor Wire the utility pulse meterWire specifications Wire the UCMsSupplier Cable type Number Details Catalog Pairs Trane-approved wire suppliersSpecification Value Specifications for Echelon Level 4 compliant cablesFigure Note UCM wiring configurationsWire the UCMs Resistor color band table Termination resistor placement for Comm5 linksTolerance Color sequence Daisy-chain termination resistor placement Tracker Requirements for repeaters on Comm5 communication links Wire supported UCMsConnecting communication link shield wiring to repeater Comm5 daisy-chain repeater connection Termination board wiring Main module mounting Main module mounting Display module mounting Display module mounting Display module engagement Display module mounting Direct connection to PC workstation PC workstation wiringVerify PC workstation specifications Cable and adapter specifications for direct connectionPC workstation wiring Tracker direct connection to a PC workstation Modem connection to PC workstation Tracker modem connection to a PC workstation Ethernet connection to PC workstation Connecting over an existing LANTracker Controller PC Workstation Connecting through a hubConnecting with one cable LEDs TroubleshootingTroubleshooting components Service pin buttons and jumperTroubleshooting Color Description Number Alarm LEDTracker main logic board LEDs LED nameService pin buttons/jumper Function Main logic board service pin buttons and jumperSymptom/action troubleshooting Symptom/action troubleshootingSymptom Action Present of the proper severity to actuate the alarm output Symptom/action troubleshooting Troubleshooting Cleaning the touch screen MaintenanceCalibrating the touch screen Maintenance Required supplies Installation checklistsRequired supplies checklist Optional supplies checklistComm5 UCM identification and location Comm5 UCM identification and locationSpace Comfort Controllers 24 maximum Space Comfort Controllers Modules 4 maximum VariTrac central control panels 10 maximumPre-installation wiring notes Termination module post-installation checklist Termination module post-installation checklistCircuit Mandatory Test Actual value Wiring Temperature ºF Temperature ºC Sensor resistance Ohms x Thermistor sensor electrical characteristicsAppendix a Installation checklists Declaration of Conformity Mark of Compliance European Contact When and where issuedProduct Number BMTK000AA0A110 Electromagnetic EmissionNumerics IndexIndex Index Index Page Trane