Trane BMTK-SVN01D-EN manual Present of the proper severity to actuate the alarm output

Page 68

®

Chapter 7 Troubleshooting

Table 14. Symptom/action troubleshooting (Continued)

Symptom

Action

 

 

Tracker alarm output is not

Confirm proper wiring of the alarm relay output. Consult the post-installation

working as expected.

checklist (Table 18 on page 70) for details.

 

Initiate the BOP self test from the display module.

 

Note: The binary output is for alarm notification only. There must be an unacknowledged alarm

 

present of the proper severity to actuate the alarm output.

 

 

Tracker controller will not

Look for wiring problems (shorts or opens, for example) that develop when wire

communicate with its

is damaged during installation.

UCMs.

Look for shorts between the two conductors resulting from nicks in the insulating

 

 

jacket. (This can be caused by improper technique when stripping away the outer

 

jacket and shield.)

 

Look for a strong source of EMI/RFI interference nearby.

 

Look for ac power disturbances from nearby transformers and electrical equip-

 

ment. This is especially true when running communication links in close proxim-

 

ity to florescent lighting ballasts.

 

Verify the UCM has not failed.

 

Verify proper termination resistance.

 

 

Tracker processor is locked

Cycle power to the Tracker main module by removing it from the termination

up.

module.

 

If the processor is still locked up after cycling power to the controller, perform a

 

reboot from the display module or the PC software (if the controller is able to

 

communicate).

 

If the controller will not respond to the above listed methods, push the reset but-

 

ton (S1) on the main module (see Figure 30 on page 56).

 

Note: Heartbeat LED (HRT LED5) will be solid green.

 

 

Alarm LED on the display is

At the Tracker controller user interface home screen, push the alarm button on

flashing red.

the display module to acknowledge the alarm, then take the proper corrective

 

action.

 

Note: The alarm LED flashes when the controller receives an alarm of the appropriate severity.

 

Pressing the Alarm button acknowledges the alarm and turns off the flashing LED (until the control-

 

ler receives another alarm of the appropriate severity).

 

 

Tracker controller is annun-

At the Tracker controller user interface home screen, push the alarm button on

ciating an alarm.

the display module to acknowledge the alarm, then take the proper corrective

 

action.

 

Note: The alarm relay energizes when the controller receives an alarm of the appropriate severity.

 

Pressing the alarm button acknowledges the alarm and turns off the alarm relay output (until the

 

controller receives another alarm of the appropriate severity).

 

 

Display module is not illu-

Press anywhere on the touch screen surface to turn the back light on. The control-

minated.

ler automatically turns off the back light during extended periods of inactivity to

 

conserve energy and bulb life.

 

Confirm that the controller has 24 Vac power. When the display module has

 

power, the alarm LED will be either solid green or flashing red.

 

 

Display module does not

Confirm that the controller has 24 Vac power. When the display module has

respond to the touch.

power, the alarm LED will be either solid green or flashing red.

 

If the display module is not responding correctly when the display module is

 

powered up and the back light is on, initiate the touch-screen calibration proce-

 

dure from the display module.

 

 

60

BMTK-SVN01D-EN

Image 68
Contents Building Automation System Page BMTK-SVN01D-EN February Page BMTK-SVN01D-EN BMTK-SVN01D-EN Contents Appendix a Appendix BOverview Tracker controllerOverview Overview Controller components Tracker controller componentsTermination module Termination moduleMain module Main moduleDisplay module Display moduleModel numbers Model number definitionSpecification Description Tracker controller specificationsTracker Controller specifications Tracker model UCM type Maximum UCMs UCM maximum capacities for Tracker models 12Tracker controller models 12 and 24 UCM capacities 105 UCM maximum capacities for Tracker model WshpTracker controller model Wshp UCM capacities Before installation Verify the shipmentInspect for shipping damage Store unused components until needed Avoid Equipment DamageAfter installation Tracker controller post-installation checklistFCC compliance Select a location for the controller Verify location conformance to controller specificationsTermination module mounting Termination module mounting Minimum clearances Optimal touch screen viewing angles Termination module conduit access and mounting holes Mount the termination moduleSecuring the termination module to a wall Securing the termination module to a conduit boxInstalling electrical conduit Electrical conduit installationTermination module mounting Termination board wiring Termination board wiring Vac power Description Wire specifications Terminals Wire 24 Vac powerPower wiring specifications Input and output Description Wire specifications Terminals Wire optional inputs and outputsInput and output wire specifications Wire the alarm relay Wire the priority shutdown deviceWire the utility pulse meter Wire the thermistorWire the UCMs Wire specificationsTrane-approved wire suppliers Supplier Cable type Number Details Catalog PairsSpecifications for Echelon Level 4 compliant cables Specification ValueUCM wiring configurations Figure NoteWire the UCMs Tolerance Color sequence Termination resistor placement for Comm5 linksResistor color band table Daisy-chain termination resistor placement Tracker Wire supported UCMs Requirements for repeaters on Comm5 communication linksConnecting communication link shield wiring to repeater Comm5 daisy-chain repeater connection Termination board wiring Main module mounting Main module mounting Display module mounting Display module mounting Display module engagement Display module mounting PC workstation wiring Verify PC workstation specificationsCable and adapter specifications for direct connection Direct connection to PC workstationPC workstation wiring Tracker direct connection to a PC workstation Modem connection to PC workstation Tracker modem connection to a PC workstation Connecting over an existing LAN Ethernet connection to PC workstationConnecting through a hub Tracker Controller PC WorkstationConnecting with one cable Troubleshooting Troubleshooting componentsService pin buttons and jumper LEDsTroubleshooting Alarm LED Tracker main logic board LEDsLED name Color Description NumberMain logic board service pin buttons and jumper Service pin buttons/jumper FunctionSymptom Action Symptom/action troubleshootingSymptom/action troubleshooting Present of the proper severity to actuate the alarm output Symptom/action troubleshooting Troubleshooting Calibrating the touch screen MaintenanceCleaning the touch screen Maintenance Installation checklists Required supplies checklistOptional supplies checklist Required suppliesSpace Comfort Controllers 24 maximum Comm5 UCM identification and locationComm5 UCM identification and location Space Comfort Controllers VariTrac central control panels 10 maximum Modules 4 maximumPre-installation wiring notes Circuit Mandatory Test Actual value Wiring Termination module post-installation checklistTermination module post-installation checklist Thermistor sensor electrical characteristics Temperature ºF Temperature ºC Sensor resistance Ohms xAppendix a Installation checklists Declaration of Conformity When and where issued Product Number BMTK000AA0A110Electromagnetic Emission Mark of Compliance European ContactIndex NumericsIndex Index Index Page Trane