Trane BMTK-SVN01D-EN, Building Automation System Main logic board service pin buttons and jumper

Page 66

®

Chapter 7 Troubleshooting

Table 13. Main logic board service pin buttons and jumper

Service pin buttons/jumper

Function

 

 

S1

This service pin is the reset button. Pressing S1 reboots the controller. It starts the

 

same operation as does rebooting the controller from either the controller or the PC

 

software. All RAM data is permanently lost.

 

Note: Before pressing this button, attempt to restart the controller by cycling power; this method

 

retains the RAM image.

 

 

S2

Momentarily pressing this service pin button causes the controller to broadcast

 

Neuron ID and Program ID. This action also turns on LED9.

 

 

J1

This jumper is for factory use only. It must always remain in place. If removed, the

 

backup capacitor will not charge and data may be lost if power is lost.

 

 

58

BMTK-SVN01D-EN

Image 66
Contents Building Automation System Page BMTK-SVN01D-EN February Page BMTK-SVN01D-EN BMTK-SVN01D-EN Contents Appendix a Appendix BOverview Tracker controllerOverview Overview Controller components Tracker controller componentsTermination module Termination moduleMain module Main moduleDisplay module Display moduleModel numbers Model number definitionTracker controller specifications Tracker Controller specificationsSpecification Description UCM maximum capacities for Tracker models 12 Tracker controller models 12 and 24 UCM capacitiesTracker model UCM type Maximum UCMs UCM maximum capacities for Tracker model Wshp Tracker controller model Wshp UCM capacities105 Inspect for shipping damage Before installationVerify the shipment Store unused components until needed Avoid Equipment DamageAfter installation Tracker controller post-installation checklistFCC compliance Verify location conformance to controller specifications Termination module mountingSelect a location for the controller Termination module mounting Minimum clearances Optimal touch screen viewing angles Termination module conduit access and mounting holes Mount the termination moduleSecuring the termination module to a wall Securing the termination module to a conduit boxInstalling electrical conduit Electrical conduit installationTermination module mounting Termination board wiring Termination board wiring Wire 24 Vac power Power wiring specificationsVac power Description Wire specifications Terminals Wire optional inputs and outputs Input and output wire specificationsInput and output Description Wire specifications Terminals Wire the alarm relay Wire the priority shutdown deviceWire the utility pulse meter Wire the thermistorWire the UCMs Wire specificationsTrane-approved wire suppliers Supplier Cable type Number Details Catalog PairsSpecifications for Echelon Level 4 compliant cables Specification ValueUCM wiring configurations Figure NoteWire the UCMs Termination resistor placement for Comm5 links Resistor color band tableTolerance Color sequence Daisy-chain termination resistor placement Tracker Wire supported UCMs Requirements for repeaters on Comm5 communication linksConnecting communication link shield wiring to repeater Comm5 daisy-chain repeater connection Termination board wiring Main module mounting Main module mounting Display module mounting Display module mounting Display module engagement Display module mounting Cable and adapter specifications for direct connection PC workstation wiringVerify PC workstation specifications Direct connection to PC workstationPC workstation wiring Tracker direct connection to a PC workstation Modem connection to PC workstation Tracker modem connection to a PC workstation Connecting over an existing LAN Ethernet connection to PC workstationConnecting through a hub Tracker Controller PC WorkstationConnecting with one cable Service pin buttons and jumper TroubleshootingTroubleshooting components LEDsTroubleshooting LED name Alarm LEDTracker main logic board LEDs Color Description NumberMain logic board service pin buttons and jumper Service pin buttons/jumper FunctionSymptom/action troubleshooting Symptom/action troubleshootingSymptom Action Present of the proper severity to actuate the alarm output Symptom/action troubleshooting Troubleshooting Maintenance Cleaning the touch screenCalibrating the touch screen Maintenance Optional supplies checklist Installation checklistsRequired supplies checklist Required suppliesComm5 UCM identification and location Comm5 UCM identification and locationSpace Comfort Controllers 24 maximum Space Comfort Controllers VariTrac central control panels 10 maximum Modules 4 maximumPre-installation wiring notes Termination module post-installation checklist Termination module post-installation checklistCircuit Mandatory Test Actual value Wiring Thermistor sensor electrical characteristics Temperature ºF Temperature ºC Sensor resistance Ohms xAppendix a Installation checklists Declaration of Conformity Electromagnetic Emission When and where issuedProduct Number BMTK000AA0A110 Mark of Compliance European ContactIndex NumericsIndex Index Index Page Trane