Trane Building Automation System, BMTK-SVN01D-EN manual Termination module mounting

Page 23

®

Chapter 2

Termination module mounting

After unpacking and inspecting the shipment, mount the termination module. The mounting process for the termination module consists of selecting a location and mounting the module. This chapter provides information and procedures that enable you to mount the termination module.

Select a location for the controller

When selecting a location for the Tracker controller:

Select a location that is in a clean, non-corrosive, indoor environment. The controller is only intended for indoor installation.

Consider both security and control wire lengths when making the selection.

Select a location that limits controller access to operating and service personnel.

Select a location that conforms to the operating environment described in Table 1 on page 9. The recommended operating environ- ment will extend the life of the electronic components. Verify that the location does not subject the controller to extreme operating condi- tions (including excessive vibration).

CAUTION

Avoid Equipment Damage!

Install the Tracker controller out of direct sunlight. Failure to do so may cause overheating, which could result in equipment damage.

IMPORTANT

Do not install the Tracker controller near high-power radio signals, elec- trical switching gear, power buses, large motors, or other sources of electrical noise. The electrical interference may lead to control malfunc- tions.

Verify location conformance to controller specifications

Verify that the selected location conforms to the applicable controller specifications listed in Table 1 on page 9.

BMTK-SVN01D-EN

15

Image 23
Contents Building Automation System Page BMTK-SVN01D-EN February Page BMTK-SVN01D-EN BMTK-SVN01D-EN Contents Appendix B Appendix aTracker controller OverviewOverview Overview Tracker controller components Controller componentsTermination module Termination moduleMain module Main moduleDisplay module Display moduleModel number definition Model numbersSpecification Description Tracker controller specificationsTracker Controller specifications Tracker model UCM type Maximum UCMs UCM maximum capacities for Tracker models 12Tracker controller models 12 and 24 UCM capacities 105 UCM maximum capacities for Tracker model WshpTracker controller model Wshp UCM capacities Store unused components until needed Avoid Equipment Damage Before installationVerify the shipment Inspect for shipping damageTracker controller post-installation checklist After installationFCC compliance Select a location for the controller Verify location conformance to controller specificationsTermination module mounting Termination module mounting Minimum clearances Optimal touch screen viewing angles Mount the termination module Termination module conduit access and mounting holesSecuring the termination module to a conduit box Securing the termination module to a wallElectrical conduit installation Installing electrical conduitTermination module mounting Termination board wiring Termination board wiring Vac power Description Wire specifications Terminals Wire 24 Vac powerPower wiring specifications Input and output Description Wire specifications Terminals Wire optional inputs and outputsInput and output wire specifications Wire the priority shutdown device Wire the alarm relayWire the thermistor Wire the utility pulse meterWire specifications Wire the UCMsSupplier Cable type Number Details Catalog Pairs Trane-approved wire suppliersSpecification Value Specifications for Echelon Level 4 compliant cablesFigure Note UCM wiring configurationsWire the UCMs Tolerance Color sequence Termination resistor placement for Comm5 linksResistor color band table Daisy-chain termination resistor placement Tracker Requirements for repeaters on Comm5 communication links Wire supported UCMsConnecting communication link shield wiring to repeater Comm5 daisy-chain repeater connection Termination board wiring Main module mounting Main module mounting Display module mounting Display module mounting Display module engagement Display module mounting Direct connection to PC workstation PC workstation wiringVerify PC workstation specifications Cable and adapter specifications for direct connectionPC workstation wiring Tracker direct connection to a PC workstation Modem connection to PC workstation Tracker modem connection to a PC workstation Ethernet connection to PC workstation Connecting over an existing LANTracker Controller PC Workstation Connecting through a hubConnecting with one cable LEDs TroubleshootingTroubleshooting components Service pin buttons and jumperTroubleshooting Color Description Number Alarm LEDTracker main logic board LEDs LED nameService pin buttons/jumper Function Main logic board service pin buttons and jumperSymptom Action Symptom/action troubleshootingSymptom/action troubleshooting Present of the proper severity to actuate the alarm output Symptom/action troubleshooting Troubleshooting Calibrating the touch screen MaintenanceCleaning the touch screen Maintenance Required supplies Installation checklistsRequired supplies checklist Optional supplies checklistSpace Comfort Controllers 24 maximum Comm5 UCM identification and locationComm5 UCM identification and location Space Comfort Controllers Modules 4 maximum VariTrac central control panels 10 maximumPre-installation wiring notes Circuit Mandatory Test Actual value Wiring Termination module post-installation checklistTermination module post-installation checklist Temperature ºF Temperature ºC Sensor resistance Ohms x Thermistor sensor electrical characteristicsAppendix a Installation checklists Declaration of Conformity Mark of Compliance European Contact When and where issuedProduct Number BMTK000AA0A110 Electromagnetic EmissionNumerics IndexIndex Index Index Page Trane