Chapter 6 PC workstation wiring

IMPORTANT

Do not use a standard phone cable for a direct connection. The RJ-12 cable is a 6-wire straight-through cable. Failure to comply will cause the Tracker controller to malfunction.

IMPORTANT

The maximum allowable length of the RJ-12 cable is 50 ft (15 m). Failure to comply may cause the Tracker controller to malfunction.

1.Locate the RJ-12 cable and the appropriate adapter.

2.Connect the RJ-12 cable to the RJ-12 port on the bottom side of the controller (Figure 24).

3.Connect the other end of the RJ-12 cable to a 9-pin or 25-pin adapter, as appropriate (Figure 25 on page 49).

4.Connect the adaptor to the appropriate serial port on the PC worksta- tion.

Figure 24. Tracker communication ports

LAN RJ-45 port

RJ-12 port

RJ-11 port

(Ethernet connection)

(PC direct connection)

(modem connection to

 

 

standard telephone line)

48

BMTK-SVN01D-EN

Image 56
Contents Building Automation System Page BMTK-SVN01D-EN February Page BMTK-SVN01D-EN BMTK-SVN01D-EN Contents Appendix a Appendix BOverview Tracker controllerOverview Overview Controller components Tracker controller componentsTermination module Termination moduleMain module Main moduleDisplay module Display moduleModel numbers Model number definitionSpecification Description Tracker controller specificationsTracker Controller specifications Tracker model UCM type Maximum UCMs UCM maximum capacities for Tracker models 12Tracker controller models 12 and 24 UCM capacities 105 UCM maximum capacities for Tracker model WshpTracker controller model Wshp UCM capacities Before installation Verify the shipmentInspect for shipping damage Store unused components until needed Avoid Equipment DamageAfter installation Tracker controller post-installation checklistFCC compliance Select a location for the controller Verify location conformance to controller specificationsTermination module mounting Termination module mounting Minimum clearances Optimal touch screen viewing angles Termination module conduit access and mounting holes Mount the termination moduleSecuring the termination module to a wall Securing the termination module to a conduit boxInstalling electrical conduit Electrical conduit installationTermination module mounting Termination board wiring Termination board wiring Vac power Description Wire specifications Terminals Wire 24 Vac powerPower wiring specifications Input and output Description Wire specifications Terminals Wire optional inputs and outputsInput and output wire specifications Wire the alarm relay Wire the priority shutdown deviceWire the utility pulse meter Wire the thermistorWire the UCMs Wire specificationsTrane-approved wire suppliers Supplier Cable type Number Details Catalog PairsSpecifications for Echelon Level 4 compliant cables Specification ValueUCM wiring configurations Figure NoteWire the UCMs Tolerance Color sequence Termination resistor placement for Comm5 linksResistor color band table Daisy-chain termination resistor placement Tracker Wire supported UCMs Requirements for repeaters on Comm5 communication linksConnecting communication link shield wiring to repeater Comm5 daisy-chain repeater connection Termination board wiring Main module mounting Main module mounting Display module mounting Display module mounting Display module engagement Display module mounting PC workstation wiring Verify PC workstation specificationsCable and adapter specifications for direct connection Direct connection to PC workstationPC workstation wiring Tracker direct connection to a PC workstation Modem connection to PC workstation Tracker modem connection to a PC workstation Connecting over an existing LAN Ethernet connection to PC workstationConnecting through a hub Tracker Controller PC WorkstationConnecting with one cable Troubleshooting Troubleshooting componentsService pin buttons and jumper LEDsTroubleshooting Alarm LED Tracker main logic board LEDsLED name Color Description NumberMain logic board service pin buttons and jumper Service pin buttons/jumper FunctionSymptom Action Symptom/action troubleshootingSymptom/action troubleshooting Present of the proper severity to actuate the alarm output Symptom/action troubleshooting Troubleshooting Calibrating the touch screen MaintenanceCleaning the touch screen Maintenance Installation checklists Required supplies checklistOptional supplies checklist Required suppliesSpace Comfort Controllers 24 maximum Comm5 UCM identification and locationComm5 UCM identification and location Space Comfort Controllers VariTrac central control panels 10 maximum Modules 4 maximumPre-installation wiring notes Circuit Mandatory Test Actual value Wiring Termination module post-installation checklistTermination module post-installation checklist Thermistor sensor electrical characteristics Temperature ºF Temperature ºC Sensor resistance Ohms xAppendix a Installation checklists Declaration of Conformity When and where issued Product Number BMTK000AA0A110Electromagnetic Emission Mark of Compliance European ContactIndex NumericsIndex Index Index Page Trane