Initial Installation

QUALIFIED INSTALLERS ONLY

The height for the vent must be between 10ft (3.05m) and 35ft (10.67m).

Install sealed Vertical Vent Cap to prevent leakage of room air up through chimney.

The intake is 2" (51mm) and the exhaust is 3" (76mm).

Measure the height of the chimney beforehand and purchase the appropriate kit. Never attempt to over-stretch a flexible liner to accommodate the height of the chimney. Any chimney over 15' (4.6m), install the Sonnet 15’ 2” & 3” Flex Vent (part #50-1512) and the Sonnet 2” & 3” Flex Couplers (part #50-1513). Every joint in the venting must be secured with three (3) #8 x 3/8” HWH sheet metal screws and an appropriate sealant (either silicone or milpac).

The flue damper can be fully blocked open or removed for installation of

the Sonnet; the smoke shelves, shields and baffles may be removed if

attached by mechanical fasteners.

The chimney must be clean, in good working order and constructed of non-combustible materials.

Make sure that all chimney cleanouts are tight fitting and will not permit air to leak into the chimney.

Refractory, glass doors, screen rails, screen mesh and log grates can be removed from the fireplace before installing the Sonnet.

Figure 41: Installation of Sonnet DV .

REMOTE HANDSET WALL BRACKET INSTALLATION:

Kit Contents:

Quantity

Description

 

 

1

Wall Bracket (Top & Bottom)

 

 

1

Spacer

 

 

1

Countersink Head Screw

 

 

2

Pan Head Screw

 

 

2

Spacer

 

 

Note: The spacer maybe found between the top and bottom halves of the wall bracket.

IMPORTANT:

The remote handset wall bracket must be installed in the same room as the Sonnet.

Installation Options:

1.Mounted to wall with bottom of bracket only; refer to Figure 42.

2.Mounted to wall with top and bottom of bracket; refer to Figure 43 (most common).

3.Mounted to wall and bottom of light switch cover

with top and bottom of mount; refer to Figure 44.

42: Wall Bracket

Figure 43: Wall Bracket Installation

Figure 44: Wall Bracket

Installation Option 1.

Option 2.

Installation Option 3.

23

Image 23
Contents Consumer InstallerFor Your Safety General Safety PrecautionsTable of Contents Vented GAS Fireplace Heater Sonnet BV/DV NG/LPG Codes And ApprovalsDimensions SpecificationsTrimmable Lighting and Turning OFF Instructions Operating InstructionsAdjustment of Flame Height Setting the TimeSetting C/24 hour or F/12 hour Clock Automatic Pilot ModeSetting the Timer Changing the Mode of OperationMAN Mode Manual Flame Height Adjustment Setting the TemperatureComponent Sound & Reason Adjusting the venturi air settingPilot Flame Maintenance And ServiceReceiver Remote HandsetChanging Remote Handset Code Out of the firebox Kit Parts ListConversion Kit Installation Each end that fit in to the brass nut but Mantle width and height Initial InstallationCan be started Vent Kit Installation Kit Contents Quantity DescriptionUnit Sheet metal screws evenly spaced KIT Components Installation InstructionsProper flame appearance. The amount of air Wall Bracket Top & Bottom Tools Required Fan wiring diagramInstalling Power Cord Fan Kit InstallationGas Line Connection Grounding Power CordOpening Inlet Pressure Tap on To Test Valve PressuresKit Contents Secondary InstallationInstallation Screw Hook Bracket To the Trim AssemblyMinimum size of Large Removal InstallationEnsure the Sonnet is turned off and allow the unit to cool Hook PlacementsEmpty firebox showing the ledges for the back logs Third Stage Log Set Installation Never operate the fireplace with the glass door removed Log Set and Ember InstallationProblem Possible Cause Solution Trouble ShootingValve’s Safety Possible Cause SolutionNumber Parts List ComponentsBV only Part DescriptionReference Part Description Part Number ComponentsDiagramParts Reference Option Description Part Number Parts List OptionsParts Diagram Options To the Dealer WarrantyWarranty Installation Data Sheet