Mitsubishi Electronics PUHY-HP-THMU-A Wiring of main power supply and equipment capacity

Page 16

GB

Remote controller cable length: r1, r2 = 10 m [32 ft] (0.3 to 1.25 mm2 [AWG 22 to 16])

If the length exceeds 10 m [32 ft], use 1.25 mm2 [AWG 16] shielded cable and calculate the length of that portion (L4 and L7) as within the total extended length and the longest remote length.

11.4. Wiring of main power supply and equipment capacity

Schematic Drawing of Wiring (Example)

[Fig. 11.4.1]

3~208–230V

 

 

B

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L1, L2, L3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

~208–230V

 

 

B

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L, N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

 

E

 

 

 

E

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ground

Ground

Ground

Ground

 

 

 

 

 

 

A Switch (Breakers for wiring and current leakage)

 

 

 

 

 

 

 

 

 

B Breakers for current leakage

 

C Outdoor unit

 

D Pull box

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E Indoor unit

 

 

 

 

 

 

Thickness of wire for main power supply, on/off capacities

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

 

Unit combination

 

Minimum wire thickness (mm2 [AWG])

 

Swtich (A)

Breaker for wiring

Breaker for current leakage

Maximum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main cable

 

Branch

 

Ground

 

Capacity

Fuse

(NFB)(A)

 

 

current (A)

 

PUHY-HP72THMU-A

13.3 [6]

 

 

-

 

 

 

13.3 [6]

 

60

60

60

60A 100mA 0.1sec. or less

44.1

 

PUHY-HP96THMU-A

21.2 [4]

 

 

-

 

 

 

21.2 [4]

 

75

75

75

75A

100mA 0.1sec. or less

59.7

 

PUHY-HP144TSHMU-A

PUHY-HP72THMU-A

13.3 [6]

 

 

-

 

 

 

13.3 [6]

 

60

60

60

60A

100mA 0.1sec. or less

44.1

Outdoor unit

 

 

 

 

 

 

PUHY-HP72THMU-A

13.3 [6]

 

 

-

 

 

 

13.3 [6]

 

60

60

60

60A

100mA 0.1sec. or less

44.1

 

PUHY-HP192TSHMU-A

PUHY-HP96THMU-A

21.2 [4]

 

 

-

 

 

 

21.2 [4]

 

75

75

75

75A

100mA 0.1sec. or less

59.7

 

 

 

 

 

 

 

PUHY-HP96THMU-A

21.2 [4]

 

 

-

 

 

 

21.2 [4]

 

75

75

75

75A

100mA 0.1sec. or less

59.7

 

 

 

 

Indoor unit

0.41 [22]

 

0.41 [22]

 

0.41 [22]

 

15

15

15

20A

30mmA 0.1sec. or less

-

1.Use dedicated power supplies for the outdoor unit and indoor unit. Ensure OC and OS are wired individually.

2.Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.

3.The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one rank thicker in diameter. Make sure the power-supply voltage does not drop more than 10%.

4.Specific wiring requirements should adhere to the wiring regulations of the region.

5.Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For example, use wiring such as YZW.

6.A switch with at least 3 mm [1/8 in] contact separation in each pole shall be provided by the Air conditioner installation.

Warning:

Be sure to use specified wires for connections and ensure no external force is imparted to terminal connections. If connections are not fixed firmly, heating or fire may result.

Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.

Caution:

Some installation sites may require attachment of a ground leakage breaker for the inverter. If a ground leakage breaker is not installed, there is a danger of electric shock.

Do not use anything other than a breaker and fuse with the correct capacity. Using a fuse or wire of too large capacity may cause malfunction or fire.

16

Image 16
Contents Outdoor Unit Contents Safety precautionsBefore installation Before installation relocation electri- cal workAbout the product Before starting the test runSpecifications Space required for unit installation and operationCombination of outdoor unit Parts included listBe very careful when carrying/moving the product Transporting the unitInstallation of unit Refrigerant piping installationInstallation Outlet Inlet Inlet InletRefrigerant piping system Precautions for outdoor unit combinations Outdoor model P144 ~ P192Additional refrigerant charge Calculation of additional refrigerant chargeAppropriate tightening torque Cap N·m /kg·cm Shaft N·m /kg·cm Size of hexagonalWrench mm Ø9.52 3/8 22/220 Ø12.7 1/2 20/200Airtight test, evacuation, and refrigerant charging Airtight testOnly use refrigerant R410A EvacuationTemperature Resistance Thermal insulation of refrigerant pipingOutdoor Water-proof hemp cloth + Zinc plate + Oily paint Refrigerant ChargingWiring transmission cables Wiring examples Examples of transmission cable wiringUnnecessary address setting Necessary main/sub setting GroundSequence with the IC Main Automatically identified. *1Schematic Drawing of Wiring Example Wiring of main power supply and equipment capacityThickness of wire for main power supply, on/off capacities Test run/Typical unit operation Rating plate informationContenu Avant installation et travaux électriquesPrécautions de sécurité Avant linstallation Avant linstallation déménagement travaux électriquesPropos du produit Avant de commencer lessaiEspace requis pour installer et utiliser lunité Combinaison dunités extérieuresSpécifications Liste des pièces inclusesTransport de lunité En cas dinstallation collective FigFaites très attention en portant/déménageant le produit Installation de lunité Installation de la tuyauterie du frigorigèneInstallation Mise en gardeNutilisez jamais la tuyauterie du frigorigène existante Système de tuyauterie du frigorigèneModèle extérieur P72 P96 Modèle extérieur P144 P192 Précautions pour les combinaisons dunités extérieuresCharge supplémentaire de frigorigène Calcul de la charge supplémentaire de frigorigèneCouple de serrage approprié Test dherméticité Test dherméticité, évacuation et chargement de frigorigèneUtilisez uniquement le frigorigène R410A Du frigorigène Isolation thermique de la tuyauterieChargement du frigorigène Raccordement des câbles de transmission 1 Télécommande M-NET Exemples de câblageÉlévateur du niveau des signaux de transmission ~208-230V L1, L2, L3 Terre ~208-230V L, N Schéma du câblage exemple FigInformations de la plaque signalétique Essai de fonctionnement/Fonctionnement type dune unitéPage Page WT05234X02