Mitsubishi Electronics PUHY-HP-THMU-A installation manual Transporting the unit

Page 5

2In case of collective installation and continuous installation [Fig. 6.0.2]

C

300*

[11-13/16]

BB

A

C

[1-3/16]

450*

23/32]-

30

 

 

 

 

 

[17

C

 

100*

-15/16]

 

 

 

[3

B B

A

C

100

450*

23/32]

 

 

 

[3-15/16]

 

-

 

 

 

[17

B

C A A A C

450* 450 450 100* [17-23/32] [17-23/32] [17-23/32] [3-15/16]

B

C

15*

[19/32]

A A A

450 450 [17-23/32] [17-23/32]

(Unit: mm [in])

 

C

300*

[11-13/16]

 

 

 

 

B

A

 

900

-7/16]

B

 

 

 

 

 

 

[35

 

 

 

 

C

300*

13/16]

 

 

 

 

 

 

 

[11-

 

 

 

 

 

 

C

 

 

300* [11-13/16]

 

 

 

 

A

 

 

900

-7/16]

B

 

 

 

 

 

 

[35

 

 

1000*

B

 

 

 

 

 

 

 

 

 

 

 

 

 

[39-3/8]

 

 

 

 

 

 

 

A Front

 

 

 

B Must be open

CWall height (H)

When multiple units are installed adjacent to each other, secure enough space to allow for air circulation and walkway between groups of units as shown in the figures.

At least two sides must be left open.

As with the single installation, add the height that exceeds the height limit <h> to the figures that are marked with an asterisk (*).

GB

7. Transporting the unit

[Fig. 7.0.1]

(Unit: m [ft])

40

8 [26]

8 [26]

Use suspension ropes that will withstand the weight of the unit.

When moving the unit, use a 4-point suspension, and avoid giving impacts to the unit (Do not use 2-point suspension).

Place protective pads on the unit where it comes in contact with the ropes to protect the unit from being scratched.

Set the angle of roping at 40˚ or less.

Use 2 ropes that are each longer than 8 m [26ft].

Place protective padding at the corners of the product to protect the product from scratches or dents that might be caused by the rope.

Caution:

Be very careful when carrying/moving the product.

-When installing the outdoor unit, suspend the unit at the specified location of the unit base. Stabilize as necessary so that it does not move to the side and support it at 4 points. If the unit is installed or suspended with 3-point support, the unit may become unstable and fall.

5

Image 5
Contents Outdoor Unit Safety precautions ContentsBefore installation relocation electri- cal work Before installationAbout the product Before starting the test runSpace required for unit installation and operation SpecificationsCombination of outdoor unit Parts included listTransporting the unit Be very careful when carrying/moving the productRefrigerant piping installation Installation of unitInstallation Outlet Inlet Inlet InletRefrigerant piping system Outdoor model P144 ~ P192 Precautions for outdoor unit combinationsCalculation of additional refrigerant charge Additional refrigerant chargeCap N·m /kg·cm Shaft N·m /kg·cm Size of hexagonal Appropriate tightening torqueWrench mm Ø9.52 3/8 22/220 Ø12.7 1/2 20/200Airtight test Airtight test, evacuation, and refrigerant chargingOnly use refrigerant R410A EvacuationThermal insulation of refrigerant piping Temperature ResistanceOutdoor Water-proof hemp cloth + Zinc plate + Oily paint Refrigerant ChargingWiring transmission cables Examples of transmission cable wiring Wiring examplesGround Unnecessary address setting Necessary main/sub settingSequence with the IC Main Automatically identified. *1Thickness of wire for main power supply, on/off capacities Wiring of main power supply and equipment capacitySchematic Drawing of Wiring Example Rating plate information Test run/Typical unit operationPrécautions de sécurité Avant installation et travaux électriquesContenu Avant linstallation déménagement travaux électriques Avant linstallationPropos du produit Avant de commencer lessaiCombinaison dunités extérieures Espace requis pour installer et utiliser lunitéSpécifications Liste des pièces inclusesFaites très attention en portant/déménageant le produit En cas dinstallation collective FigTransport de lunité Installation de la tuyauterie du frigorigène Installation de lunitéInstallation Mise en gardeModèle extérieur P72 P96 Système de tuyauterie du frigorigèneNutilisez jamais la tuyauterie du frigorigène existante Précautions pour les combinaisons dunités extérieures Modèle extérieur P144 P192Calcul de la charge supplémentaire de frigorigène Charge supplémentaire de frigorigèneCouple de serrage approprié Utilisez uniquement le frigorigène R410A Test dherméticité, évacuation et chargement de frigorigèneTest dherméticité Chargement du frigorigène Isolation thermique de la tuyauterieDu frigorigène Raccordement des câbles de transmission Exemples de câblage 1 Télécommande M-NETÉlévateur du niveau des signaux de transmission Schéma du câblage exemple Fig ~208-230V L1, L2, L3 Terre ~208-230V L, NEssai de fonctionnement/Fonctionnement type dune unité Informations de la plaque signalétiquePage Page WT05234X02