Mitsubishi Electronics PUHY-HP-THMU-A installation manual Wiring transmission cables

Page 13

11.Wiring (For details, refer to the installation manual of each indoor/outdoor unit and controller.)

11.1. Caution

[Fig. 11.2.2]

 

1Follow ordinance of your governmental organization for technical standard re- lated to electrical equipment, wiring regulations and guidance of each electric power company.

2Wiring for control (hereinafter referred to as transmission line) shall be (5 cm or more [2 in or more]) apart from power source wiring so that it is not influenced by electric noise from power source wiring. (Do not insert transmission line and power source wire in the same conduit.)

3Be sure to provide designated grounding work to the outdoor unit.

4Give some allowance to wiring for the electrical part box on the indoor and outdoor units, because these boxes are sometimes removed at the time of service work.

5Never connect the main power source to terminal block of transmission line. If

connected, electrical parts will burn out.

A

2

3

1

6Use 2-core shield cable for the transmission line. If transmission lines of different systems are wired with the same multiplecore cable, the resultant poor trans- mitting and receiving will cause erroneous operations.

7Only the transmission line specified should be connected to the terminal block for outdoor unit transmission.

Erroneous connection does not allow the system to operate.

8When connecting a System Controller to outdoor units or performing a group operation of indoor units that are connected to different outdoor units, a transmission line for centralized control is required. When using a transmission line for centralized control, connect the transmission line (non-polar 2 core wire) to all TB7 terminals between all outdoor units.

9Grouping is set by operating the remote controller.

11.2. Control box and connecting position of wiring

1Outdoor unit

1.Remove the front panel of the control box by removing the 4 screws and push- ing it up a little before pulling it out.

2.Connect the indoor - outdoor transmission line to the terminal block (TB3) for the indoor - outdoor transmission line.

If multiple outdoor units are connected in the same refrigerant system, daisy- chain TB3 (M1, M2, ground terminal ) on the outdoor units. Connect the indoor - outdoor transmission line for the outdoor units to TB3 (M1, M2, ground terminal ) of only one of the outdoor units.

3.Connect the transmission lines for centralized control (between the centralized control system and the outdoor unit of different refrigerant systems) to the terminal block for centralized control (TB7). If the multiple outdoor units are connected to the same refrigerant system, daisy-chain TB7 (M1, M2, S Termi- nal) on the outdoor units in the same refrigerant system. (*1)

*1: If TB7 on the outdoor unit in the same refrigerant system is not daisy- chained, connect the transmission line for centralized control to TB7 on the OC (*2). If the OC is out of order, or if the centralized control is being conducted during the power supply shut-off, daisy-chain TB7 on the OC and OS. (In the case that the outdoor unit whose power supply connector CN41 on the control board has been replaced with CN40 is out of order or the power is shut-off, centralized control will not be conducted even when TB7 is daisy-chained.)

*2: OC and OS of the outdoor units in the same refrigerant system are auto- matically identified. They are identified as OC and OS in descending order of capacity. (If the capacity is the same, they will be in ascending order of their address number.)

4.In the case of indoor-outdoor transmission line, connect the shield ground to the ground terminal . In the case of transmission lines for centralized con- trol, connect it to the shield terminal (S) on the terminal block for centralized

control (TB7). Furthermore, in the case of the outdoor units whose power

supply connector CN41 is replaced with CN40, short circuit the shield terminal

(S) and the ground terminal in addition to the above.

5.Fix the connected wires securely in place with the cable strap at the bottom of the terminal block. External force applied to the terminal block may damage it and may cause a short circuit, ground fault, or a fire.

[Fig. 11.2.1]

A

B

 

Power supply terminal block

Terminal block for indoor –

Terminal block for

(TB1)

outdoor transmission line

centralized control

Control box

(TB3)

(TB7)

 

L1 L2 L3

 

 

 

C

 

A Power source

B Transmission line

CGround screw

4 5

B C

A Cable strap

B Power source line

CTransmission line

When using wire size AWG 6, be sure to use knockout hole 4.

When using wire size AWG 4, AWG 3, AWG 2, or AWG 1, be sure to use knockout hole 2.

When using wire size AWG 0, AWG 0/2, or AWG 0/3, be sure to use knockout hole 5.

If there are any gaps around the wires, please be sure to fill these in with a suitable material.

2Conduit tube installation

Close by hammering the knockout holes for the conduit tube located on the base and the bottom part of the front panel.

When installing the conduit tube directly through the knockout holes, remove the burr and protect the tube with masking tape.

Use the conduit tube to narrow down the opening if there is a possibility of small animal’s entering the unit.

11.3. Wiring transmission cables

1Types of control cables

1. Wiring transmission cables

Types of transmission cables: Shielding wire CVVS, CPEVS or MVVS

Cable diameter: More than 1.25 mm2 [AWG 16]

Maximum wiring length: Within 200 m [656 ft]

Maximum length of transmission lines for centralized control and indoor/out- door transmission lines (Maximum length via outdoor units): 500 m [1640 ft]

MAX

The maximum length of the wiring between power supply unit for transmission lines (on the transmission lines for centralized control) and each outdoor unit and system controller is 200 m [656 ft].

2. Remote control cables

M-NET Remote Controller

Kind of remote control cable

Sheathed 2-core cable (unshielded) CVV

Cable diameter

0.3 to 1.25 mm2 [AWG 22 to 16] (0.75 to

 

1.25 mm2 [AWG 18 to 16])*

Remarks

When 10 m [32 ft] is exceeded, use cable with

 

the same specifications as 1. Wiring

 

transmission cables.

 

 

• MA Remote Controller

 

 

 

Kind of remote control cable

Sheathed 2-core cable (unshielded) CVV

Cable diameter

0.3 to 1.25 mm2 [AWG 22 to 16] (0.75 to

 

1.25 mm2 [AWG 18 to 16] )*

Remarks

Within 200 m [656 ft]

 

 

*Connected with simple remote controller.

GB

13

Image 13
Contents Outdoor Unit Safety precautions ContentsBefore installation relocation electri- cal work Before installationAbout the product Before starting the test runSpace required for unit installation and operation SpecificationsCombination of outdoor unit Parts included listTransporting the unit Be very careful when carrying/moving the productRefrigerant piping installation Installation of unitInstallation Outlet Inlet Inlet InletRefrigerant piping system Outdoor model P144 ~ P192 Precautions for outdoor unit combinationsCalculation of additional refrigerant charge Additional refrigerant chargeCap N·m /kg·cm Shaft N·m /kg·cm Size of hexagonal Appropriate tightening torqueWrench mm Ø9.52 3/8 22/220 Ø12.7 1/2 20/200Airtight test Airtight test, evacuation, and refrigerant chargingOnly use refrigerant R410A EvacuationThermal insulation of refrigerant piping Temperature ResistanceOutdoor Water-proof hemp cloth + Zinc plate + Oily paint Refrigerant ChargingWiring transmission cables Examples of transmission cable wiring Wiring examplesGround Unnecessary address setting Necessary main/sub settingSequence with the IC Main Automatically identified. *1Schematic Drawing of Wiring Example Wiring of main power supply and equipment capacityThickness of wire for main power supply, on/off capacities Rating plate information Test run/Typical unit operationContenu Avant installation et travaux électriquesPrécautions de sécurité Avant linstallation déménagement travaux électriques Avant linstallationPropos du produit Avant de commencer lessaiCombinaison dunités extérieures Espace requis pour installer et utiliser lunitéSpécifications Liste des pièces inclusesTransport de lunité En cas dinstallation collective FigFaites très attention en portant/déménageant le produit Installation de la tuyauterie du frigorigène Installation de lunitéInstallation Mise en gardeNutilisez jamais la tuyauterie du frigorigène existante Système de tuyauterie du frigorigèneModèle extérieur P72 P96 Précautions pour les combinaisons dunités extérieures Modèle extérieur P144 P192Calcul de la charge supplémentaire de frigorigène Charge supplémentaire de frigorigèneCouple de serrage approprié Test dherméticité Test dherméticité, évacuation et chargement de frigorigèneUtilisez uniquement le frigorigène R410A Du frigorigène Isolation thermique de la tuyauterieChargement du frigorigène Raccordement des câbles de transmission Exemples de câblage 1 Télécommande M-NETÉlévateur du niveau des signaux de transmission Schéma du câblage exemple Fig ~208-230V L1, L2, L3 Terre ~208-230V L, NEssai de fonctionnement/Fonctionnement type dune unité Informations de la plaque signalétiquePage Page WT05234X02