Mitsubishi Electronics PUHY-HP-THMU-A installation manual Refrigerant piping system

Page 7

3Branching cannot be made after header branching (corresponding parts are marked with in the diagram below).

To the outdoor unit

To the outdoor unit

CAP

4Do not install outdoor unit piping when it is raining.

5Commercially available piping often contains dust and other materials. Always blow it clean with a dry inert gas.

6Use care to prevent dust, water or other contaminants from entering the piping during installation.

7Reduce the number of bending portions as much as possible, and make bend- ing radius as big as possible.

8For indoor and outdoor branching, be sure to use the following twinning pipe sets (sold separately).

9Use an adapter if a specified refrigerant pipe has a different diameter from that of a branching pipe.

0Braze only with non-oxide brazing material for piping. Failure to do so may damage the compressor. Be sure to perform the non-oxidation braz- ing with a nitrogen purge.

Do not use any commercially available anti-oxidizing agent since it may cause pipe corrosion and degrading of the refrigerant oil.

Please contact Mitsubishi Electric for more details.

(Refer to item 10.2. for details of the piping connection and valve operation)

AAlways insulate the piping properly. Insufficient insulation will result in a de- cline in heating/cooling performance, water drops from condensation forming and other such problems. (Refer to item 9 for installation of refrigerant piping.)

BWhen connecting the refrigerant piping, make sure the valve of the outdoor unit is completely closed (the factory setting). Do not operate it until the refrig- erant piping for the outdoor and indoor units has been connected, a refrigerant leakage test has been performed, and the evacuation process has been com- pleted.

CNever use refrigerant to perform an air purge. Always evacuate using a vacuum pump.

DBe sure to charge the system using liquid refrigerant.

EEither a lack or an excess of refrigerant causes the unit to make an emergency stop. Charge the system with an appropriate amount of refrigerant. When serv- icing, always check the notes concerning pipe length and amount of additional refrigerant at both locations, the refrigerant volume calculation table on the back of the service panel and the additional refrigerant section on the labels for the combined number of indoor units. (Refer to item 9.2. for detailed infor- mation on refrigerant piping system.)

GB

 

 

Indoor twinning pipe set model

 

 

Outdoor Twinning Kit model

 

Line branch

 

 

Header branch

 

 

Downstream indoor unit capacity

Downstream indoor unit capacity

Downstream indoor unit capacity

 

 

 

Total outdoor model

More than 73 and less than

More than 145 and less than

4 branches

8 branches

10 branches

Less than 72 in total

P144 ~ P192

144 in total

288 in total

 

 

 

 

 

 

 

 

CMY-Y102S-G2

CMY-Y102L-G2

CMY-Y202-G2

CMY-Y104-G

CMY-Y108G

CMY-Y1010-G

CMY-Y100VBK2

Warning:

When installing and moving the unit, do not charge the system with any other refrigerant other than the refrigerant specified on the unit.

- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to mal- function and may result in severe damage.

Caution:

Use a vacuum pump with a reverse flow check valve.

-If the vacuum pump does not have a reverse flow check valve, the vacuum pump oil may flow back into the refrigerant cycle and cause deterioration of the refrigerant oil.

Do not use the tools shown below used with conventional refrigerant. (Gauge manifold, charge hose, gas leak detector, check valve, refrigerant charge base, vacuum gauge, refrigerant recovery equipment)

-Mixing of conventional refrigerant and refrigerator oil may cause the refriger- ant oil to deteriorate.

-Mixing of water will cause the refrigerant oil to deteriorate.

-R410A refrigerant does not contain any chlorine. Therefore, gas leak detec- tors for conventional refrigerants will not react to it.

Manage the tools used for R410A more carefully than normal.

-If dust, dirt, or water gets in the refrigerant cycle, the refrigerant oil will dete- riorate.

Never use existing refrigerant piping.

-The large amount of chlorine in conventional refrigerant and refrigerant oil in the existing piping will cause the new refrigerant to deteriorate.

Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing.

-If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and the compressor may fail.

Do not use a charging cylinder.

-Using a charging cylinder may cause the refrigerant to deteriorate.

Do not use special detergents for washing piping.

9.2. Refrigerant piping system

Connection Example

[Fig. 9.2.1]

[Outdoor model : P72 ~ P96]

A

A

B C

B

a

 

b

C

C

c

C

D

d

C

e

 

A

A

 

 

F

B

 

a

b c d e D

C

C

C

C C C

7

Image 7
Contents Outdoor Unit Safety precautions ContentsBefore starting the test run Before installationBefore installation relocation electri- cal work About the productParts included list SpecificationsSpace required for unit installation and operation Combination of outdoor unitTransporting the unit Be very careful when carrying/moving the productOutlet Inlet Inlet Inlet Installation of unitRefrigerant piping installation InstallationRefrigerant piping system Outdoor model P144 ~ P192 Precautions for outdoor unit combinationsCalculation of additional refrigerant charge Additional refrigerant chargeØ9.52 3/8 22/220 Ø12.7 1/2 20/200 Appropriate tightening torqueCap N·m /kg·cm Shaft N·m /kg·cm Size of hexagonal Wrench mmEvacuation Airtight test, evacuation, and refrigerant chargingAirtight test Only use refrigerant R410ARefrigerant Charging Temperature ResistanceThermal insulation of refrigerant piping Outdoor Water-proof hemp cloth + Zinc plate + Oily paintWiring transmission cables Examples of transmission cable wiring Wiring examplesAutomatically identified. *1 Unnecessary address setting Necessary main/sub settingGround Sequence with the IC MainSchematic Drawing of Wiring Example Wiring of main power supply and equipment capacityThickness of wire for main power supply, on/off capacities Rating plate information Test run/Typical unit operationContenu Avant installation et travaux électriquesPrécautions de sécurité Avant de commencer lessai Avant linstallationAvant linstallation déménagement travaux électriques Propos du produitListe des pièces incluses Espace requis pour installer et utiliser lunitéCombinaison dunités extérieures SpécificationsTransport de lunité En cas dinstallation collective FigFaites très attention en portant/déménageant le produit Mise en garde Installation de lunitéInstallation de la tuyauterie du frigorigène InstallationNutilisez jamais la tuyauterie du frigorigène existante Système de tuyauterie du frigorigèneModèle extérieur P72 P96 Précautions pour les combinaisons dunités extérieures Modèle extérieur P144 P192Calcul de la charge supplémentaire de frigorigène Charge supplémentaire de frigorigèneCouple de serrage approprié Test dherméticité Test dherméticité, évacuation et chargement de frigorigèneUtilisez uniquement le frigorigène R410A Du frigorigène Isolation thermique de la tuyauterieChargement du frigorigène Raccordement des câbles de transmission Exemples de câblage 1 Télécommande M-NETÉlévateur du niveau des signaux de transmission Schéma du câblage exemple Fig ~208-230V L1, L2, L3 Terre ~208-230V L, NEssai de fonctionnement/Fonctionnement type dune unité Informations de la plaque signalétiquePage Page WT05234X02