[Outdoor model : P144 ~ P192]
unit 1 | unit 2 |
|
A |
| A |
A1 | A2 |
|
|
| A |
| E | B |
|
|
B
a
C
C
b
C
D
c
C
d
C
e
C
unit 1 | unit 2 |
A | A |
A1 | A2 |
A |
|
| F |
|
B |
|
|
|
|
E |
|
|
|
|
a | b c | d | e D | |
C | C | C | C | C |
|
|
GB
A Outdoor unit | B 1st branch |
C Indoor unit | D Cap |
E Outdoor Twinning Kit | F Header |
* The total length of A1 and A2 is less than 10 m [32 ft].
A
(Unit: mm [in])
Outdoor model | Unit combination |
| A |
| A1 |
| A2 | |
| unit 1 | unit 2 | Liquid pipe | Gas pipe | Liquid pipe | Gas pipe | Liquid pipe | Gas pipe |
P72 | - | - | ø12.7 [1/2] Brazed | ø19.05 [3/4] Brazed | - | - | - | - |
|
|
|
|
|
|
|
|
|
P96 | - | - | ø12.7 [1/2] Brazed | ø22.2 [7/8] Brazed | - | - | - | - |
P144 | P72 | P72 | ø15.88 [5/8] Brazed | ø28.58 | ø9.52 [3/8] Flare | ø19.05 [3/4] Brazed | ø9.52 [3/8] Flare | ø19.05 [3/4] Brazed |
P192 | P96 | P96 | ø15.88 [5/8] Brazed | ø28.58 | ø9.52 [3/8] Flare | ø22.2 [7/8] Brazed | ø9.52 [3/8] Flare | ø22.2 [7/8] Brazed |
| B, C, D |
|
|
| (Unit: mm [in]) | |
|
|
|
|
|
| |
| Total capacity of indoor units |
| Liquid pipe |
| Gas pipe | |
| ~ 54 |
|
| ø9.52 [3/8] |
| ø15.88 [5/8] |
| 55 ~ 72 |
|
| ø9.52 [3/8] |
| ø19.05 [3/4] |
| 73 ~ 108 |
|
| ø9.52 [3/8] |
| ø22.2 [7/8] |
| 109 ~ 144 |
|
| ø12.7 [1/2] |
| ø28.58 |
| 145 ~ 234 |
|
| ø15.88 [5/8] |
| ø28.58 |
|
|
|
|
|
| |
a, b, c, d, e |
|
|
| (Unit: mm [in]) | ||
|
|
|
|
|
|
|
| Model number |
| Liquid pipe |
| Gas pipe | |
| 06, 08, 12, 15, 18 |
| ø6.35 [1/4] | ø12.7 [1/2] | ||
| 24, 27, 30, 36, 48, 54 |
| ø9.52 [3/8] | ø15.88 [5/8] | ||
| 72 |
| ø9.52 [3/8] | ø19.05 [3/4] | ||
| 96 |
| ø9.52 [3/8] | ø22.2 [7/8] | ||
|
|
|
|
|
|
|
Precautions for outdoor unit combinations
Refer to [Fig. 9.2.2] for the positioning of twinning pipes.
[Fig. 9.2.2]
Downstream unit model total |
|
|
| Joint |
|
| ||
~ 72 |
|
|
|
|
| |||
73 ~ 144 |
|
|
|
|
| |||
145 ~ 234 |
|
|
|
|
|
| ||
The 1st branch of P144 ~ P234 |
|
|
|
| ||||
|
|
|
|
|
| |||
|
|
|
|
|
| |||
|
|
|
|
|
| |||
|
| |||||||
(Downstream indoor |
| (Downstream indoor |
| (Downstream indoor | ||||
< |
| < | 144) |
| unit model total | < | 234) | |
unit model total = 72) |
| unit model total = |
| = | ||||
|
|
| ||||||
|
|
|
|
|
| |||
Outdoor model |
|
| Outdoor Twinning Kit |
|
| |||
P144 ~ P192 |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
<A> Make sure the pipes from the twinning pipe to the outdoor unit are sloped downwards (towards the twinning pipes).
A C C
FB F
<B> When the piping on the outdoor unit side (from the twinning pipe) exceeds 2 m [6 ft], ensure a trap (gas pipe only) within 2 m [6 ft]. Make sure the height of the trap is 200 mm
If there is no trap, oil can accumulate inside the pipe, causing a shortage of oil and may damage the compressor.
(Unit: m [ft])
F
C
2[6]
D
E
F
C
8