KitchenAid UXI0600DYS, UXI01200DYS Installation Instructions EXTERIOR-MOUNTED Vent Motor

Page 16

INSTALLATION INSTRUCTIONS

EXTERIOR-MOUNTED VENT MOTOR

CAUTION: To reduce the risk of fire and electrical shock, install the downdraft only with remote blower systems that are sold by Whirlpool Corporation. Model numbers UXI0600DYS (600 cfm) and UXI01200DYS (1200 cfm).

NOTE: Exterior-mounted vent motor installations require an approved in-line blower motor system. Model numbers UXI0600DYS (600 cfm) and UXI1200DYS (1200 cfm) are available from your dealer or authorized parts supplier. See “Blower motor system” in the “Accessories” section.

Venting Methods

Determine which venting method is best for your application. Vent system can terminate through the wall or roof. A wall cap or roof cap is required.

NOTES:

Venting through a concrete slab is not recommended.

The in-line blower motor system must be placed in an enclosed area and can be located in a utility room, basement, crawl space or attic. Observe all governing codes and ordinances.

10" (25.4 cm) round vent duct is required for connections to the retractable downdraft vent system outlet cover and the in-line blower motor inlet and outlet covers. 10" (25.4 cm) round vent duct is recommended for the retractable downdraft vent system with in-line blower motor system. Transitioning to different size ducting will reduce the efficiency of the retractable downdraft vent system.

Built-In Cabinet Locations

To attic installed in-line blower motor system

To basement, crawlspace or utility room installed in-line blower motor system

Calculating Vent System Length

Island Location—Front Vent

To attic installed in-line blower motor system

Island Location—Rear Vent

To basement, crawlspace or utility room installed in-line blower motor system

To attic installed in-line blower motor system

It is recommended that you use round vent instead of rectangular vent, especially if elbows are required. If rectangular vent is required, it should be transitioned to 10" (25.4 cm) round vent as soon as possible.

Maximum Length of Vent System

Vent

Length

10" (25.4 cm) round

60 ft (18.3 m)

 

 

To calculate the length of the system you need, add the equivalent feet (meters) for each vent piece used in the system.

Vent Piece

10" (25.4 cm) Round

45° elbow

2.5 ft

 

(0.8 m)

 

 

90° elbow

5.0 ft

 

(1.5 m)

The maximum equivalent vent lengths of 10" (25.4 cm) round vents - 60 ft (18.3 m).

To basement, crawlspace or utility room installed in-line blower motor system

2 - 90° elbows

= 10.0 ft (3 m)

10 ft (3 m) straight

= 10.0 ft (3 m)

 

 

Length of 10" (25.4 cm)

= 20 ft (6 m)

system

 

NOTE: The exterior-mounted vent motor requires a separate wiring cable that should be installed at the same time the vent work is installed.

16

Image 16
Contents Table of Contents/Table des matières Retractable POP-UP Downdraft Vent SystemTable of Contents Table DES MatièresVent System Safety Your safety and the safety of others are very importantImportant Safety Instructions Tools and Parts Installation RequirementsLocation Requirements Product Dimensions Models with interior-mounted blower motorCabinet Dimensions Countertop Cutout DimensionsElectrical Requirements Venting RequirementsInstallation Instructions INTERIOR-MOUNTED Vent Motor Venting MethodsIsland Location Built-In Cabinet LocationsCalculating Vent System Length Example Vent SystemInstall Vent System Determine Which Vent Direction Is Best for Your InstallationRear Mounting-Blower Motor Bottom VentingLeft or Right Venting Front View Complete Installation Remove the screws from the wire mounting plate ¹⁄₄ x 10 8.3 x 25.4 cm Back Draft Damper Cm Round Vent Transition with DamperRemove 4 screws attaching the terminal box cover Tighten the lower support legs screwsMake Electrical Connections Check OperationInstallation Instructions EXTERIOR-MOUNTED Vent Motor Maximum Length of Vent SystemFront or Rear Venting Install Downdraft Vent In-Line External Type Blower Motor Complete Installation Exterior-Mounted MotorPrepare for Mounting the In-Line Blower System Install In-line Blower System Outlet Side Drill 4 mounting pilot holes using a ³⁄₁₆ 4.8 mm drill bitPrepare the In-line Blower System Inlet SideMake Electrical Connections for In-Line Blower Motor System Electrical Connection Inside In-line Blower SystemMake Electrical Power Supply Connection to Downdraft Vent Disconnect power Locate the downdraft vent terminal boxCheck Operation When Cooking Is Complete Vent System USEOperating Downdraft Vent To UseSurface of Downdraft Vent Vent System CareFilters Wiring Diagrams Interior-Mounted Blower MotorSEL0016521 Exterior-Mounted Blower MotorAssistance or Service AccessoriesU.S.A CanadaKitchenaid Ventilation Warranty This limited warranty does not coverSécurité DU Système DE Ventilation Votre sécurité et celle des autres est très importanteImportantes Instructions DE Sécurité Exigences demplacement Exigences DinstallationOutils et pièces Dimensions du produit Modèles à ventilateur monté à lintérieurDimensions du placard RemarquesPlan de travail Dimensions des ouvertures à découper Tableau des dimensions de l’ouverture du plan de travailLongueur recommandée pour le système d’extraction Installations dans les régions au climat froidSpécifications électriques Exigences concernant l’évacuationInstructions D’INSTALLATION Ventilateur Monté À L’INTÉRIEUR Configuration en îlotMéthodes d’évacuation Calcul de la longueur effective du circuit d’évacuationInstallation du conduit d’évacuation Exemple de circuit d’évacuationRectangulaire de 3¹⁄₄ x Composant Cm x 25,4 cmÉvacuation par le bas Montage du ventilateur à l’arrière Sortie par le côté gauche ou le côté droitVue de face Vue arrièreAchever l’installation Clapet anti-retour de 3¹⁄₄ x 10 8,3 x 25,4 cmRaccord de transition rond de 6 15,2 cm avec clapet Retirer les vis de la platine de montage du câbleRaccordements électriques Ôter les 4 vis du couvercle du boîtier de connexionSerrer les vis des pieds de soutien Déconnecter la source de courant électriqueAvertissement Contrôle du fonctionnementInstructions D’INSTALLATION Ventilateur Monté À L’EXTÉRIEUR Configuration avec encastrementConfiguration en îlot- Évacuation par l’avant Configuration en îlot- Évacuation par l’arrièreÉvacuation par l’avant ou par l’arrière Achever l’installation Ventilateur monté à l’extérieur Préparation du montage du système de ventilation en ligneInstallation du système de ventilation en ligne Préparation du système de ventilation en ligneCôté sortie Côté entréeInstaller les connecteurs de conduit et le conduit dans les De conduit de ¹⁄₂ 1,3 cm homologués UL ou CSAConduit de câblage de ¹⁄₂ 1,3 cm entre le logement du Suffisamment de conduit de câblage de ¹⁄₂ 1,3 cm pourConduit de câblage ¹⁄₂ 1,3 cm Homologation UL Par le bas Utilisation DU Système D’EXTRACTION Utilisation du système d’extraction par le basUtilisation Lorsque la cuisson est terminéeEntretien DU Système D’ÉVACUATION Surface du système d’extraction par le basSchéma DE Câblage Ventilateur monté à lintérieurSEL0016521 Ventilateur monté à lextérieurAssistance OU Service AccessoiresAux États-Unis Au CanadaLa présente garantie limitée ne couvre pas Garantie DU Système DE Ventilation KitchenaidComposer le 1-800-422-1230. Au Canada, composer le W10342489E