INSTALLATION INSTRUCTIONS
EXTERIOR-MOUNTED VENT MOTOR
CAUTION: To reduce the risk of fire and electrical shock, install the downdraft only with remote blower systems that are sold by Whirlpool Corporation. Model numbers UXI0600DYS (600 cfm) and UXI01200DYS (1200 cfm).
NOTE:
Venting Methods
Determine which venting method is best for your application. Vent system can terminate through the wall or roof. A wall cap or roof cap is required.
NOTES:
■Venting through a concrete slab is not recommended.
■The
■10" (25.4 cm) round vent duct is required for connections to the retractable downdraft vent system outlet cover and the
Built-In Cabinet Locations
To attic installed
To basement, crawlspace or utility room installed
Calculating Vent System Length
Island
To attic installed
Island Location—Rear Vent
To basement, crawlspace or utility room installed
To attic installed
It is recommended that you use round vent instead of rectangular vent, especially if elbows are required. If rectangular vent is required, it should be transitioned to 10" (25.4 cm) round vent as soon as possible.
Maximum Length of Vent System
Vent | Length |
10" (25.4 cm) round | 60 ft (18.3 m) |
|
|
To calculate the length of the system you need, add the equivalent feet (meters) for each vent piece used in the system.
Vent Piece | 10" (25.4 cm) Round |
45° elbow | 2.5 ft |
| (0.8 m) |
|
|
90° elbow | 5.0 ft |
| (1.5 m) |
The maximum equivalent vent lengths of 10" (25.4 cm) round vents - 60 ft (18.3 m).
To basement, crawlspace or utility room installed
2 - 90° elbows | = 10.0 ft (3 m) |
10 ft (3 m) straight | = 10.0 ft (3 m) |
|
|
Length of 10" (25.4 cm) | = 20 ft (6 m) |
system |
|
NOTE: The
16