Henny PennyModel BCC/BCR-140, BCC/BCR-175, BFR/BCR-350

4-2. TROUBLESHOOTING

(Continued)

 

 

Problem

Cause

Correction

 

 

 

Slow to decrease

Condenser obstructed by dirt.

Clean the Condenser.

in temperature (decline in

 

 

performance)

Evaporator iced up.

Perform a de-icing cycle.

 

Refrigerating problem

Check refrigeration circuit and

 

 

components.

 

 

 

Display temperature does

In Frigiprobe mode, the display

Normal

not match the actual inlet air

shows the product temperature.

 

temperature. (No alarm)

In timer mode, or hold mode,

Ohm out the probe and check

 

 

the probe may be showing the

the reading with the table on

 

wrong temperature.

page 4-5. Change the probe if

 

 

it is out of tolerance.

 

 

 

Green compressor indicator

Compressor and condenser fan

 

light on and the compressor

do not work:

 

not working, or working

- Faulty contactor

Check contactor and change if

sometimes.

 

neccessary.

 

- Faulty control board relay-no

Replace control board.

 

voltage across terminals 10-11.

 

 

Compressor works, but condenser

 

 

fan does not:

 

 

- Faulty condenser fan

Replace fan.

 

Compressor and condenser fan

 

 

work together:

 

 

- Faulty protection component

Check items and replace if

 

for the compressor (overload

neccessary.

 

protector, potential relay, start

 

 

and run capacitor)

 

 

- Faulty overload protector of

Check fan and replace if

 

condenser fan.

necessary.

 

 

 

 

 

 

4-3

100

Image 27
Contents Page Henny Penny Blast Chiller/Freezer Limited Warranty for Henny Penny Appliances Table Ofcontents Assistance FeaturesBlast Chiller Proper CareSafety Unpacking IntroductionBCR-140 ElectricalBCC-140 BCC-175BFR LocationBFR-350 Refrigerant InformationRefrigeration CapacitiesDescription Function Operating ControlsOn BFR units Only applicableHenny Penny Model BCC/BCR-140, BCC/BCR-175, BFR/BCR-350 100 Start-up Basic OperationBasic Operation Convenience Temperature conversion chart is provided for yourDE-ICING Cleaning DailyMonthly BCC-140 Only Seasonal or Prolonged Shutdown CleaningNot Available at this time ProgrammingMaximum duration of de-icing cycle minutes. Press To prevent freezing of the product. Press the Alarm Duration of time the temperatures, in 9Above, must remain at before the alarms will sound International Only. a Frigiprobe sensor temperatureFrigiprobe, end of cycle temperature setting. Press Blast chilling, low side air temperature limit, when usingFrigiprobe, in of this section. Press the Alarm Blast chilling, high side air temperature limit, when usingHas reached the danger zone temperature, and must be Frigiprobe temperature for when the buzzer sounds atStart of a cycle. Press the Alarm button 17 times, Temperature that the buzzer will sound when the productDisplay Cause Correction TroubleshootingTroubleshooting AlarmsProblem Cause Correction 100 Troubleshooting Henny Penny Model BCC/BCR-140, BCC/BCR-175, BFR/BCR-350 100 Henny Penny Model BCC/BCR-140, BCC/BCR-175, BFR/BCR-350 201 Henny Penny Model BCC/BCR-140, BCC/BCR-175, BFR/BCR-350 201 Henny Penny Model BCC/BCR-140, BCC/BCR-175, BFR/BCR-350 201 Quantity BCC BCRDescription 140 175 350 Part Page CPE-USALCO Page Henny Penny International Distributor Network Oman