Henny PennyModel
4-2. TROUBLESHOOTING (Continued)
|
| ALARMS | |
|
|
|
|
Display | Cause |
| Correction |
|
|
|
|
Temperature too low |
|
| |
| in the hold mode. |
| Faulty control board - replace control board. |
|
|
| Faulty contactor - replace contactor. |
Temperature too high in |
|
| |
| the hold mode. |
| Faulty control board - Replace board. |
|
|
| Door opened too much - Make sure door stays |
|
|
| closed as much as possible. |
|
|
|
|
|
|
|
|
Problem | Cause | Correction |
The evaporator is | Faulty | Replace |
after a | Evaporator temperature at end | Increase the setting of step 8 |
| ||
| of | in Section 3. |
| Maximum time of | Increase the setting of step 7 |
| too short. | in Section 3. |
|
|
|
Too much water on evaporator | The unit has been shut down without | Start a |
fins. | a |
|
|
|
|
Slow to decrease | Compressor not working properly | Check compressor and re- |
in temperature (decline in |
| place if neccessary. |
performance) | Evaporator fan not working properly | Check the fan and replace if |
| ||
|
| neccessary. |
| Temperature of room too high. | Ventilate the room. |
| Not enough clearance around unit. | Change the location of the |
|
| unit. (See section |
|
|
|
300 |