Hoshizaki KM-1301SAH-E Pump-Out Timer S4 dip switch 3, Pump-Out Frequency Control S4 dip switch 5

Page 22

c) Pump-Out Timer (S4 dip switch 3 & 4)

CAUTION

Do not adjust S4 dip switch 3 off and S4 dip switch 4 on for this model. Otherwise, pump motor does not rotate in the pump-out direction.

When a pump-out is called for, the pump motor stops after the preceding freeze cycle. The pump motor restarts 2 seconds later in the reverse direction, taking water from the bottom of the tank and forcing pressure against the check valve seat allowing water to go through the check valve and down the drain. At the same time, water flows through the small tube to power flush the float switch. The pump motor drains the water tank for the time determined by the pumpout timer. The pumpout timer also acts in place of the harvest timer during cycles with a pump-out. The pump-out timer is factory set, and generally no adjustment is required. The pump-out timer control can be set to pump-out for 10 or 20 seconds.

S4 Dip Switch Setting

Time (seconds)

Inlet

Water

 

 

 

 

No. 3

No. 4

T1

T2

Valve

 

 

 

 

 

OFF

OFF

10

150

closed

 

 

 

 

 

ON

OFF

10

180

closed

 

 

 

 

 

OFF

ON

10

120

open

 

 

 

 

 

ON

ON

20

180

closed

 

 

 

 

 

T1: Time to drain the water tank

T2: Harvest timer at pump-out

d)Pump-Out Frequency Control (S4 dip switch 5 & 6)

The pump-out frequency control is factory set to drain the water tank every 10 cycles, and generally no adjustment is required. However, where water quality is bad and the icemaker needs a pump-out more often, the pump-out frequency can be adjusted. The pump-out frequency control can be set to have a pump-out occur every cycle, or every 2, 5, or 10 cycles.

Timing of the first pumpout is dependent on S4 dip switch 5 & 6 settings. The first pumpout is factory set to occur after the 11th freeze cycle. See the table below.

S4 Dip Switch Setting

Pump-Out

1st Pump-Out

No. 5

No. 6

Frequency

 

 

 

 

 

OFF

OFF

Every cycle

After 2nd freeze cycle

 

 

 

 

ON

OFF

Every 2 cycles

After 3rd freeze cycle

 

 

 

 

OFF

ON

Every 5 cycles

After 6th freeze cycle

ON

ON

Every 10 cycles

After 11th freeze cycle

 

 

 

 

22

Image 22 Contents
Superior Degree Reliability Hoshizaki AMERICA, INC Contents Page Indicates important information about the use and care Important Safety InformationSerious injury UnitSpecifications Icemaker KM-1301SAH-E air-cooledKM-1301SWH-E water-cooled KM-1301SRH-E remote air-cooled Condenser Unit URC-14FESpecifications II. General Information Construction KM-1301SWH-E water-cooled Separators Minute Fill Cycle Sequence of OperationSequence Cycles and Shutdown Initial Harvest CyclePump-Out Cycle S4 Dip Switch Setting Pump-Out 1st Pump-Out FrequencyFreeze Cycle Harvest CycleMechanical Bin Control KM-1301SWH-E, KM-1301SRH-E Cycle at Shutdown Mechanical Bin Control ActivationPump-Out Cycle Sequence Flow ChartCycle Steps Minute Fill Harvest Cycle Mechanical BC Bin Full Shutdown and Restart Control Board Control Board Layout Control BoardSequence Step LED Lights and Audible Alarm SafetiesNo. of Beeps Type of Alarm Every 3 sec Time LEDs are OnDefault Dip Switch Settings Controls and AdjustmentsHarvest Timer S4 dip switch 1 Pump-Out Frequency Control S4 dip switch 5 Pump-Out Timer S4 dip switch 3Time seconds Inlet Freeze Timer S4 dip switch 9 Harvest Pump Timer S4 dip switchFactory Use S4 dip switch S4 Dip Switch Setting Pump Motor Time secondsFloat Switch Control S5 dip switch Control SwitchRefill Counter S5 dip switch 2 through Tank Water Tank Headmaster Service Drier Valve Thermistor KM-1301SAH-E air-cooled Wiring DiagramsAuxiliary Code T-0, U-0 U-0 Auxiliary CodeAuxiliary Code U-1 and Later PressureSwitch KM-1301SRH-E remote air-cooled Performance Data 1780 13301240 13351950 12701142 2070IV. Service Diagnosis Diagnostic ProcedurePage S4 Dip Switch Setting Pump-Out 1st Pump-Out Frequency Shutdown Thermostatic Bin Control KM-1301SAH-E Mechanical Bin Control KM-1301SWH-E, KM-1301SRH-EControl Board Check Thermostatic Bin Control Check KM-1301SAH-E Bin Control CheckMechanical Bin Control Check Single Unit Connection Detail Stacked Unit Connection DetailMechanical Bin Control Cleaning Float Switch Check and Cleaning Float Switch CheckFloat Switch Cleaning Adjustment of Water Regulating Valve water-cooled model Thermistor CheckNo Ice Production Diagnostic ChartsNo Ice Production Possible Cause No Ice Production Possible Cause Freeze Up Freeze Up Possible Cause Harvest CycleFreeze Up Possible Cause Freeze Cycle Low Ice Production Possible Cause Long Harvest Cycle Low Ice ProductionLong Freeze Cycle Service for Refrigerant Lines Replacement of ComponentsRefrigerant Recovery Brazing Evacuation and Recharge R-404APage Important Notes for Component Replacement ComponentVI. Cleaning and Maintenance Cleaning ProcedureIce Chute Float Switch Assembly Drain Plug Sanitizing Procedure Following Cleaning Procedure Maintenance Remove the water from the icemaker water supply lineDrain the water tank