Hoshizaki KM-1301SRH-E, KM-1301SAH-E Controls and Adjustments, Default Dip Switch Settings

Page 21

2. Controls and Adjustments

CAUTION

Dip switches are factory set. Failure to maintain factory settings may adversely affect performance and warranty coverage. For more information, contact Hoshizaki Technical Support at 1-800-233-1940.

a)Default Dip Switch Settings

The dip switches are factory set to the following positions:

S4 Dip Switch

S4 Dip Switch No.

1

2

3

4

5

6

7

8

9

10

 

 

 

 

 

 

 

 

 

 

 

KM-1301SAH-E

OFF

OFF

ON

ON

ON

ON

ON

OFF

ON

ON

 

 

 

 

 

 

 

 

 

 

 

KM-1301SWH-E

OFF

OFF

ON

ON

ON

ON

ON

OFF

ON

ON

 

 

 

 

 

 

 

 

 

 

 

KM-1301SRH-E

ON

OFF

ON

ON

ON

ON

ON

OFF

ON

ON

 

 

 

 

 

 

 

 

 

 

 

S5 Dip Switch (Do Not Adjust)

S5 Dip Switch No.

1

2

3

4

5

 

 

 

 

 

 

KM-1301SAH-E

OFF

OFF

OFF

OFF

OFF

 

 

 

 

 

 

KM-1301SWH-E

OFF

OFF

OFF

OFF

OFF

 

 

 

 

 

 

KM-1301SRH-E

OFF

OFF

OFF

OFF

OFF

 

 

 

 

 

 

Freeze Timer (9 & 10)

Factory Use (8)

Harvest Pump Timer (7) (Do not adjust)

Pump-Out Frequency Control (5 & 6)

Pump-Out Timer (3 & 4)

(Do not adjust to 3 off and 4 on) Harvest Timer (1 & 2)

b)Harvest Timer (S4 dip switch 1 & 2)

The harvest timer starts when the thermistor reads 48°F (9°C) at the evaporator outlet and the control board reads the thermistor's 3.9 kΩ signal. The harvest timer is factory set, and generally no adjustment is required. However, a setting longer than the factory setting may be advised in cases where the flush provided at harvest needs to be prolonged for extra cleaning. Before changing this setting, contact Hoshizaki Technical Support at 18002331940 for recommendations. Keep in mind that setting the harvest timer to a longer setting decreases 24-hour production.

Note that the pump-out timer (S4 dip switch 3 & 4) acts in place of the harvest timer during cycles with a pump-out. For details, see "II.C.2.c) Pump-Out Timer (S4 dip switch 3 & 4)."

S4 Dip Switch Setting

Time

 

 

(seconds)

No. 1

No. 2

 

 

 

 

OFF

OFF

60

 

 

 

ON

OFF

90

 

 

 

OFF

ON

120

 

 

 

ON

ON

180

 

 

 

21

Image 21
Contents Superior Degree Reliability Hoshizaki AMERICA, INC Contents Page Serious injury Important Safety InformationIndicates important information about the use and care UnitKM-1301SAH-E air-cooled Specifications IcemakerKM-1301SWH-E water-cooled KM-1301SRH-E remote air-cooled URC-14FE Condenser UnitSpecifications II. General Information Construction KM-1301SWH-E water-cooled Separators Sequence Cycles and Shutdown Sequence of OperationMinute Fill Cycle Initial Harvest CycleFreeze Cycle S4 Dip Switch Setting Pump-Out 1st Pump-Out FrequencyPump-Out Cycle Harvest CycleCycle at Shutdown Mechanical Bin Control Activation Mechanical Bin Control KM-1301SWH-E, KM-1301SRH-ECycle Steps Minute Fill Harvest Cycle Sequence Flow ChartPump-Out Cycle Mechanical BC Bin Full Shutdown and RestartControl Board Control Board Control Board LayoutNo. of Beeps Type of Alarm Every 3 sec LED Lights and Audible Alarm SafetiesSequence Step Time LEDs are OnControls and Adjustments Default Dip Switch SettingsHarvest Timer S4 dip switch 1 Pump-Out Timer S4 dip switch 3 Pump-Out Frequency Control S4 dip switch 5Time seconds Inlet Factory Use S4 dip switch Harvest Pump Timer S4 dip switchFreeze Timer S4 dip switch 9 S4 Dip Switch Setting Pump Motor Time secondsControl Switch Float Switch Control S5 dip switchRefill Counter S5 dip switch 2 through Tank Water Tank Headmaster Service Drier Valve Thermistor Auxiliary Code T-0, U-0 Wiring DiagramsKM-1301SAH-E air-cooled U-0 Auxiliary CodeAuxiliary Code U-1 and Later PressureSwitch KM-1301SRH-E remote air-cooled Performance Data 1240 13301780 13351142 12701950 2070Diagnostic Procedure IV. Service DiagnosisPage S4 Dip Switch Setting Pump-Out 1st Pump-Out Frequency Mechanical Bin Control KM-1301SWH-E, KM-1301SRH-E Shutdown Thermostatic Bin Control KM-1301SAH-EControl Board Check Bin Control Check Thermostatic Bin Control Check KM-1301SAH-EMechanical Bin Control Check Stacked Unit Connection Detail Single Unit Connection DetailMechanical Bin Control Cleaning Float Switch Check Float Switch Check and CleaningFloat Switch Cleaning Thermistor Check Adjustment of Water Regulating Valve water-cooled modelDiagnostic Charts No Ice ProductionNo Ice Production Possible Cause No Ice Production Possible Cause Freeze Up Possible Cause Harvest Cycle Freeze UpFreeze Up Possible Cause Freeze Cycle Low Ice Production Low Ice Production Possible Cause Long Harvest CycleLong Freeze Cycle Replacement of Components Service for Refrigerant LinesRefrigerant Recovery Evacuation and Recharge R-404A BrazingPage Component Important Notes for Component ReplacementCleaning Procedure VI. Cleaning and MaintenanceIce Chute Float Switch Assembly Drain Plug Sanitizing Procedure Following Cleaning Procedure Remove the water from the icemaker water supply line MaintenanceDrain the water tank