(2) Mechanical Bin Control (KM-1301SWH-E, KM-1301SRH-E)

When mechanical BC is activated (BC open), the yellow "BC OPEN" LED comes on. The unit then shuts down as outlined in the table below.

Cycle at

Shutdown

Mechanical Bin

 

Control Activation

 

 

 

Fill Cycle

15 seconds after activation.

Harvest Cycle

At the end of the harvest cycle, or up to 15 seconds into the freeze cycle if activated

 

at the end of the harvest cycle.

 

 

Freeze Cycle

15 seconds after activation if activated at least 15 seconds before the 5-minute short

 

cycle protection timer terminates. Otherwise, at the end of the next harvest cycle.

 

 

Legend: BC–bin control; CB–control board; Comp–compressor; FM–fan motor; FMR–fan motorremote; F/S–float switch; HGV–hot gas valve; LLV–liquid line valve; PM–pump motor; WV–inlet water valve

16

Image 16
Contents Superior Degree Reliability Hoshizaki AMERICA, INC Contents Page Important Safety Information Serious injuryIndicates important information about the use and care UnitSpecifications Icemaker KM-1301SAH-E air-cooledKM-1301SWH-E water-cooled KM-1301SRH-E remote air-cooled Condenser Unit URC-14FESpecifications II. General Information Construction KM-1301SWH-E water-cooled Separators Sequence of Operation Sequence Cycles and ShutdownMinute Fill Cycle Initial Harvest CycleS4 Dip Switch Setting Pump-Out 1st Pump-Out Frequency Freeze CyclePump-Out Cycle Harvest CycleMechanical Bin Control KM-1301SWH-E, KM-1301SRH-E Cycle at Shutdown Mechanical Bin Control ActivationSequence Flow Chart Cycle Steps Minute Fill Harvest CyclePump-Out Cycle Mechanical BC Bin Full Shutdown and RestartControl Board Control Board Layout Control BoardLED Lights and Audible Alarm Safeties No. of Beeps Type of Alarm Every 3 secSequence Step Time LEDs are OnDefault Dip Switch Settings Controls and AdjustmentsHarvest Timer S4 dip switch 1 Pump-Out Frequency Control S4 dip switch 5 Pump-Out Timer S4 dip switch 3Time seconds Inlet Harvest Pump Timer S4 dip switch Factory Use S4 dip switchFreeze Timer S4 dip switch 9 S4 Dip Switch Setting Pump Motor Time secondsFloat Switch Control S5 dip switch Control SwitchRefill Counter S5 dip switch 2 through Tank Water Tank Headmaster Service Drier Valve Thermistor Wiring Diagrams Auxiliary Code T-0, U-0KM-1301SAH-E air-cooled U-0 Auxiliary CodeAuxiliary Code U-1 and Later PressureSwitch KM-1301SRH-E remote air-cooled Performance Data 1330 12401780 13351270 11421950 2070IV. Service Diagnosis Diagnostic ProcedurePage S4 Dip Switch Setting Pump-Out 1st Pump-Out Frequency Shutdown Thermostatic Bin Control KM-1301SAH-E Mechanical Bin Control KM-1301SWH-E, KM-1301SRH-EControl Board Check Thermostatic Bin Control Check KM-1301SAH-E Bin Control CheckMechanical Bin Control Check Single Unit Connection Detail Stacked Unit Connection DetailMechanical Bin Control Cleaning Float Switch Check and Cleaning Float Switch CheckFloat Switch Cleaning Adjustment of Water Regulating Valve water-cooled model Thermistor CheckNo Ice Production Diagnostic ChartsNo Ice Production Possible Cause No Ice Production Possible Cause Freeze Up Freeze Up Possible Cause Harvest CycleFreeze Up Possible Cause Freeze Cycle Low Ice Production Possible Cause Long Harvest Cycle Low Ice ProductionLong Freeze Cycle Service for Refrigerant Lines Replacement of ComponentsRefrigerant Recovery Brazing Evacuation and Recharge R-404APage Important Notes for Component Replacement ComponentVI. Cleaning and Maintenance Cleaning ProcedureIce Chute Float Switch Assembly Drain Plug Sanitizing Procedure Following Cleaning Procedure Maintenance Remove the water from the icemaker water supply lineDrain the water tank