Hoshizaki FS-1022MLH-C service manual

Page 28

8)Freeze Cycle "GM" and "COMP" LEDs are on. "GM" LED, GMR (X2 on CB), GM, GMPR, and EH continue. "COMP" LED turns on and PDS energizes. Once the refrigeration circuit low-side pressure rises to 29 PSIG, CLPS closes, energizing MC, which energizes Comp and FMR. Ice production begins 4 to 6 minutes after Comp and FMR energize depending on ambient and water conditions.

FS Diagnosis: Check that "COMP" LED is on and that PDS energizes. If "COMP" LED is off, check DC voltage across GMPR terminals 3 and 5 white/orange (W/O) wires.

If 5VDC is present, GMPR contacts are open. Check GMPR solenoid voltage and solenoid continuity. Replace GMPR if necessary. If "COMP" LED remains off, CB is bad and must be replaced. If "COMP" LED is on and PDS is not energized, confirm 115VAC at CB X1 relay brown (BR) to white (W) neutral and CB X1 relay dark blue (DBU) to white (W) neutral. If 115VAC is present on CB X1 brown (BR) and not on CB X1 dark blue (DBU) CB is bad and must be replaced. Next, check for 115VAC from PDS dark blue (DBU) to white (W) neutral. If 115VAC is present and PDS is closed, check for continuity through PDS solenoid. If open or if PDS is sticking closed, replace PDS. SRC Diagnosis: Confirm that CLPS closes. Once CLPS closes, MC energizes, energizing Comp and FMR. If not, check CLPS, SLPS (manual reset), and HPS (automatic reset).

CLPS: When PDS is energized, CLPS closes when refrigeration circuit low-side pressure rises to 29 PSIG. If CLPS is open, check that refrigeration circuit low-side pressure has reached 29 PSIG. If refrigeration circuit low-side pressure is too low, confirm proper TXV operation, check for refrigerant restrictions (drier, PDS), and correct refrigerant charge. Recover, evacuate, and recharge if necessary.

SLPS: If SLPS is open, manually reset SLPS. Confirm proper TXV operation, check for refrigerant restriction (drier, PDS), and correct refrigerant charge. Recover, evacuate, and recharge if necessary.

HPS: HPS automatically resets when refrigeration circuit high-side pressure is within an acceptable range. If HPS does not reset (open), allow pressures to equalize and HPS to reset. If refrigeration circuit high-side pressure does not drop, recover, evacuate, and recharge if necessary. Before restarting unit, check for dirty or clogged condenser. Once unit is restarted, check for proper FMR operation and fan blade for binding. Check for refrigeration circuit refrigerant restriction (receiver, service valves, PDS, and drier). Also check for proper HM operation. If refrigerant pressures have returned to an acceptable range and HPS does not close, replace HPS.

MC: If MC energizes and Comp does not energize, check 208-230VAC at MC T1 black (BK) to MC T2 red (R). If 208-230VAC is not present, check incoming power supply and MC contact continuity. If 208-230VAC is present and Comp does not start, check Comp start relay, start capacitor, run capacitor, and Comp motor windings. If FMR does not energize, check 115VAC at MC T3 dark blue (DBU) to white (W) neutral. If 115VAC is present and FM does not energize, check FM capacitor and motor windings.

28

Image 28
Contents SRC-10H Hoshizaki AMERICA, INC Contents Page Important Safety Information Serious injuryIndicates important information about the use and care UnitFor SRC Specifications Icemaker FS-1022MLH-CCondensing Unit SRC-10HII. General Information Construction Icemaker FS-1022MLH-CCondensing Unit a SRC-10H Icemaking Unit Sequence of Operation Sequence Cycles and ShutdownDrain Cycle Shutdown Cycle Control Board Sequence Flow Chart FS-1022MLH-C/SRC-10H Sequence Flow ChartControl Board Control Board Layout Control BoardLED Lights and Audible Alarm Safeties No. of Beeps Type of Alarm Reset Options Every 5 secSequence Step Energized Components Min MaxS1 Dip Switch Setting Infrared Sensor Shutdown Delay Controls and AdjustmentsSeconds 1.6 minutes Factory Default S1 Dip Switch Setting Drain Timer Interval S1 Dip Switch Setting Dispense TimeS1 Dip Switch Mechanical BackupShutdown Delay Bin ControlIII Wiring Diagrams Safety Low-Pressure Switch Manual Reset Control Low-Pressure SwitchHigh-Pressure Switch Performance Data FS-1022MLH-C with SRC-10HDiagnostic Procedure IV. Service DiagnosisIce Production Check Page Page Page Control Board Check 5VDC Page Bin Control Check Infrared Sensor CheckMechanical Backup Bin Control Check Page Float Switch Check Float Switch Check and CleaningFloat Switch Cleaning Page No Ice Production Diagnostic ChartsNo Ice Production Possible Cause Startup No Ice Production Possible Cause Shutdown Removal and Replacement of Components Service for Refrigerant LinesBrazing Refrigerant RecoveryEvacuation and Recharge R-404A Evaporator Assembly Components. See Fig Important Notes for Component ReplacementComponent Evaporator Assembly Removal and Replacement of Cutter Upper Bearing Wear CheckRemoval and Replacement of Extruding Head Removal and Replacement of AugerRemoval and Replacement of Evaporator Page 6b. Lower Housing Removal and Replacement of Gear MotorPage VI. Cleaning and Maintenance Cleaning and Sanitizing InstructionsCleaning Solution Cleaning ProcedureFloat Switch Assembly Reservoir Cover Sanitizing Solution Sanitizing Procedure InitialSanitizing Procedure Final Maintenance Maintenance Schedule Frequency Area TaskRemove the water from the icemaker water supply line Preparing the Icemaker for Long StorageDrain the evaporator