D. Bin Control Check
1. Infrared Sensor Check
IMPORTANT
Make sure S1 dip switch 7 is in the "ON" position. This allows the control board to monitor the infrared sensor along with the mechanical backup bin control.
1)Remove the front panel.
2)Move the power switch to the "OFF" position, then unplug the unit from the electrical outlet.
3)Remove the control box cover and access CB. Confirm that S1 dip switch 1, 2, 3 are in the proper position for your application. See "II.C.3.b) Infrared Sensor Shutdown Delay (S1 dip switch 1, 2, 3)."
4)Confirm that IS is connected to the K6 connector on CB. Wipe down the IS lens with a clean, warm, damp cloth. If the bottom of the icemaker is not accessible in your application, remove the thumbscrew securing the IS housing, then remove the housing from the base. See Fig. 3.
5)Make sure the control switch is in the "ICE" position, then plug the icemaker into the electrical outlet.
6)Move the power switch to the "ON" position to start the automatic icemaking process.
Check that the IS green LED is on. The green LED confirms 20VDC power from CB to IS and remains on constantly. Diagnosis: If the green LED is not on, confirm 20VDC at K6 connector dark blue (DBU) to brown (BR). If 20VDC is present and the green LED is off, IS is bad and must be replaced. If not, see step "3) IS Power Supply," under "IV.C. Control Board Check."
7)Make sure the "GM" LED on CB is on. There is a delay of at least 30 seconds before the "GM" LED turns on after
8)"GM" and "COMP" LEDs are on. Use an object to cover IS lens. The yellow LED on IS turns on (flashing or steady). The yellow LED flashes when ice is at the outer limit of its range and turns steady as ice nears. After the yellow LED turns on (flashing or steady), IS shutdown delay timer starts . See "II.C.3.b)Infrared Sensor Shutdown Delay (S1 dip switch 1, 2, 3)." Comp and FMR should
33