Hoshizaki dcm-75ibah service manual 5VDC CB K9 Connector See Fig, High-Pressure Switch HPS

Page 19

2)5VDC Output Checks: There are seven 5VDC circuits on the appliance, "DRAIN" position through control switch, high-pressure switch (HPS), gear motor protect relay (GMPR), bin control (BC), float switch (FS), ice dispense switch, and water dispense switch.

5VDC CB K9 Connector: See Fig. 1.

5VDC CB K9 Connector

Component

Pin # (Wire Color)

 

 

"DRAIN" Position Through Control Switch

#1 (W/BK) and #2 (W/BK)

High-Pressure Switch (HPS)

#3 (Y) and #4 (Y)

 

 

Gear Motor Protect Relay (GMPR)

#5 (W/O) and #6 (W/O)

(terminals #3 and #5)

 

 

 

Red positive test lead to

red K4 connector pin closest

to black K3 connector

Red Positive Test Lead

Multimeter

5VDC

Black Negative Test Lead

"DRAIN" Position on Control Switch (W/BK)

High-Pressure Switch (HPS)

(Y)

Gear Motor Protect Relay (GMPR) Terminals #3 and #5 (W/O)

Control Board K9 Connector

Fig. 1

a. "DRAIN" Position on Control Switch

CB K9 connector pins #1 and #2 (W/BK):

When control switch is in the "ICE" position, CB K9 connector pin #1 and pin #2 are open. 5VDC is present between CB K9 connector pin #1 (W/BK) and pin

#2 (W/BK). If not, confirm 5VDC between pin #1 (W/BK) and CB red K4 connector, pin closest to CB black K3 connector. If 5VDC is not present, replace CB.

When control switch is in the "DRAIN" position, CB K9 connector pin #1 (W/BK) and pin #2 (W/BK) are closed. 5VDC is present between both CB K9 connector pin #1 (W/BK) and pin #2 (W/BK) to CB red K4 connector, pin closest to CB black K3 connector. If 5VDC is not present, replace CB.

b.High-Pressure Switch (HPS)

CB K9 connector pins #3 (Y) and #4 (Y): When HPS is closed, 5VDC is present between both CB K9 connector pins #3 (Y) and pin #4 (Y) to CB red K4 connector pin closest to CB black K3 connector. If 5VDC is not present on pin #3 (Y) or pin #4 (Y), replace CB. If 5VDC is present on CB K9 connector pin #3 (Y) and not on CB K9 connector pin #4 (Y), HPS is most likely open. CB sounds a 3-beep alarm. Check HPS continuity. If HPS is open and CB is not in alarm, replace CB.

19

Image 19
Contents DCM-751BAH-OS DCM-751BWH-OS Hoshizaki AMERICA, INC Contents Page Important Safety Information Page DCM-751BAH-OS Construction and Water/Refrigeration Circuit DiagramsDCM-751BWH-OS Ice Making Unit Water/Refrigeration Circuit Diagrams Spout Inlet Water Valve Water Supply Float Diagnosis Control Board Sequence Flow Chart DCM-751BH-OSChart OperationDiagnostic Procedure Service DiagnosisIce Production Check Page Page Page Page Control Board Check High-Pressure Switch HPS 5VDC CB K9 Connector See Fig5VDC CB K9 Connector Component Pin # Wire Color Bin Control BC 5VDC CB K8 Connector See Fig5VDC CB K8 Connector Component Pin # Wire Color Gear Motor Protect Relay Gmpr5VDC 0VDC Portion Signal #5 R Red K4 pin closest 5VDC Power Supply #3 W/BK Connector Pin # Wire Color Neutral LBU Open Closed 24VAC CB K2 ConnectorBin Control Check Float Switch Check Float Switch Check and CleaningFloat Switch Cleaning Page No Ice Production Diagnostic TablesNo Ice Production Possible Cause Startup Shutdown No Ice Production Possible CauseWater Dispense-Push Button Ice/Water DispensingIce Dispense-Push Button Ice Dispense-Opti-ServeIII. Controls and Adjustments DCM-751BH Control Board LayoutDCM-751BH-OS K2 Connector Drain Valve #10 W/BUEnergized Components Min Max LED Lights and Audible Alarm SafetiesNo. of Beeps Type of Alarm Reset Options Every 5 sec Icemaking Sequence Sequence StepDrain Frequency Control S1 dip switch Settings and AdjustmentsDefault Dip Switch Settings Infrared Sensor Shutdown Delay S1 dip switch 1, 2Factory Use S1 Dip Switch 9 Continuous Dispensing Timer S1 dip switch 5Bin Control Selector S1 dip switch Bin Control Shutdown Delay S1 dip switchDrain Power Switch, Control Switch, and Dispense Mode SwitchICE OFFContinuous Dispense Mode SwitchPortion Service for Refrigerant Lines IV. Removal and Replacement of ComponentsBrazing Refrigerant RecoveryEvacuation and Recharge R-404A Evaporator Assembly Components. See Fig Important Notes for Component ReplacementEvaporator Assembly Upper Bearing Wear Check Icemaking UnitRemoval and Replacement of Auger Removal and Replacement of Extruding HeadRemoval and Replacement of Evaporator 5b. Lower Housing Removal and Replacement of Gear Motor Dispense Auger and Agitator Dispense ComponentsDispense and Agitating Motors Maintenance Schedule MaintenanceFrequency Area Task VI. Preparing the Appliance for Periods of Non-Use Page VII. Disposal DCM-751BAH VIII. Technical Information Specification SheetsDesign without prior Potable Water WATER-COOLED Condenser DCM-751BWH779 758 Reference without *marks 738 719 ICE Production Performance Data800 363 Wiring Diagrams DCM-751BH-OS