Manitowoc Ice Cooling Tower Applications Water-Cooled Models, Water Supply, Water Inlet Lines

Page 25

Section 2

Installation Instructions

 

 

Water Supply and Drain Requirements

WATER SUPPLY

Local water conditions may require treatment of the water to inhibit scale formation, filter sediment, and remove chlorine odor and taste.

Important

If you are installing a Manitowoc Arctic Puref water filter system, refer to the Installation Instructions supplied with the filter system for ice making water inlet connections.

WATER INLET LINES

Follow these guidelines to install water inlet lines:

Do not connect the ice machine to a hot water supply. Be sure all hot water restrictors installed for other equipment are working. (Check valves on sink faucets, dishwashers, etc.)

If water pressure exceeds the maximum recommended pressure (80 psi), obtain a water pressure regulator from your Manitowoc distributor.

Install a water shut-off valve for both the ice making and condenser water lines.

Insulate water inlet lines to prevent condensation.

!Caution

Do not apply heat to water valve inlet fitting. This will damage plastic valve body.

DRAIN CONNECTIONS

Follow these guidelines when installing drain lines to prevent drain water from flowing back into the ice machine and storage bin:

Drain lines must have a 1.5 inch drop per 5 feet of run (2.5 cm per meter), and must not create traps.

The floor drain must be large enough to accommodate drainage from all drains.

Run separate bin and ice machine drain lines. Insulate them to prevent condensation.

Vent the bin and ice machine drain to the atmosphere. Do not vent the condenser drain on water-cooled models.

Cooling Tower Applications

(Water-Cooled Models)

A water cooling tower installation does not require modification of the ice machine. The water regulator valve for the condenser continues to control the refrigeration discharge pressure.

It is necessary to know the amount of heat rejection, and the pressure drop through the condenser and water valves (inlet and outlet) when using a cooling tower on an ice machine.

Water entering the condenser must not exceed 90°F (32.2°C).

Water flow through the condenser must not exceed 5 gallons (19 liters) per minute.

Allow for a pressure drop of 7 psi (48 kPA) between the condenser water inlet and the outlet of the ice machine.

Water exiting the condenser must not exceed 110°F (43.3°C).

Part Number 80-1620-3

2-13

Image 25
Contents Model Ice Machines Personal Injury Potential Read These Before ProceedingPage Manitowoc ICE, INC Table of Contents Section Ice Machine Operation Table of ContentsSection Section Before Calling For Service Table of Contents MaintenanceTable of Contents Model Numbers How to Read a Model NumberIce Cube Sizes Self-Contained Remote Air-CooledGeneral Information Section Accessories Model/Serial Number Location Section General Information Model/Serial Number LocationWarranty Coverage Ice Machine Dimension W Dimension D Dimension H Ice Machine DimensionsGeneral S320/S420 AIR and WATER-COOLED ICE MachinesS600 AIR and WATER-COOLED ICE Machines Installation Instructions SectionS600 Remote ICE Machines Electrical and AuCS Dimensions Width, Depth, and Height DimensionsBin Model Dimension a Dimension B Ice Storage Bin DimensionsS500/S850/S1000 Remote ICE Machines Inch 76 CM ICE Storage Bins Inch 56 CM ICE Storage BinsS1400 / S1800 Remote ICE Machines S1400/S1600/S1800 AIR and WATER-COOLED ICE MachinesB970 Inch 130 CM ICE Storage BinsIce Machine Heat of Rejection Section Installation Instructions Location of Ice MachineLeveling Leg and Foot Air-Cooled BaffleAir Baffle Voltage Section Installation Instructions Electrical ServiceFuse/Circuit Breaker Minimum Circuit AmpacityMaximum Breaker Size & Minimum Circuit Amperage Chart Self Contained ICE Machine 115/1/60 or 208-230/1/60 For United Kingdom OnlySelf Contained ICE Machine 208-230/3/60 Self Contained ICE Machine 230/1/50Single Water Supply Cooling Tower Applications Water-Cooled ModelsWater Inlet Lines Drain ConnectionsWater Supply and Drain Line SIZING/CONNECTIONS Typical Water Supply Drain InstallationCondenser Bin DrainRemote ICE Machines Refrigerant Charge Air Temperature Around the CondenserIce Machine Remote Single Line Set Circuit Condenser Line Set Discharge Line Liquid LineRouting Line Sets Guidelines for Routing Line SetsCalculating Remote Condenser Installation Distances Remote Receiver Service Valve Connecting a Line SETBackseating the Receiver Service Valve Lengthening or Reducing Line SET LengthsInternal Condenser Volume WarrantyHead Pressure Control Valve FAN MotorTypical Single Circuit Remote Condenser Installation NON-MANITOWOC MULTI-CIRCUIT Condenser Sizing ChartAdditional Checks for Remote Models Section Installation Instructions Installation Check ListAuCS Automatic Cleaning System Component Identification Section Ice Machine OperationInitial START-UP or START-UP After Automatic SHUT-OFF Ice Machine Operation Section Sequence Of OperationHarvest Sequence 5. Water Purge Safety TimersHarvest Automatic SHUT-OFF 7. Automatic Shut-OffWater Level Ice Machine Operation Section Operational ChecksICE Thickness Check Ice Thickness CheckHarvest Sequence Water Purge Water Purge AdjustmentIce Machine Operation Section Exterior Cleaning Section MaintenanceCleaning the Condenser Ice Machine InspectionWater-Cooled Condenser Water Regulating Valve Maintenance SectionAlphaSan Straighten Bent Condenser FinsGuardianf Location GUARDIANf Sachet Replacement Frequency Section Maintenance GuardianfSachet INSTALLATION/REPLACEMENT Procedure Clean UP Procedure for Damaged Sachet PacketCleaning Procedure Maintenance Section Interior Cleaning and SanitizingModel Amount of Cleaner StepSolution Type Water Mixed With Sanitizing ProcedureModel Amount of Sanitizer Removal of Parts for CLEANING/SANITIZING Water Curtain Removal Ice Thickness Probe Water CurtainIce Thickness Probe Removal Water Trough Water Distribution TubeWater Distribution Tube Removal Water Pump Water Level ProbeWater Pump Removal Water Dump Valve Dump Valve DisassemblyDrain Line Check Valve Evaporator Tray RemovalWater Inlet Valve Removing the Front PanelsSELF-CONTAINED AIR-COOLED ICE Machines Section Maintenance Removal from Service/WinterizationWATER-COOLED ICE Machines Remote ICE MachinesThis page Intentionally Left Blank Problem Possible Cause To Correct ChecklistSafety Limit Feature Before Calling For Service Section