Manitowoc Ice S manual Warranty, Head Pressure Control Valve, FAN Motor, Internal Condenser Volume

Page 31

Section 2

Installation Instructions

 

 

Remote Ice Machine Usage with Non-Manitowoc Multi-Circuit Condensers

WARRANTY

The sixty (60) month compressor warranty, including thirty six (36) month labor replacement warranty, shall not apply when the remote ice machine is not installed within the remote specifications. The foregoing warranty shall not apply to any ice machine installed and/or maintained inconsistent with the technical instructions provided by Manitowoc Ice, Inc. Performance may vary from Sales specifications. S-Model ARI certified standard ratings only apply when used with a Manitowoc remote condenser.

If the design of the condenser meets the specifications, Manitowoc’s only approval is for full warranty coverage to be extended to the Manitowoc manufactured part of the system. Since Manitowoc does not test the condenser in conjunction with the ice machine, Manitowoc will not endorse, recommend, or approve the condenser, and will not be responsible for its performance or reliability.

Important

Manitowoc warrants only complete new and unused remote packages. Guaranteeing the integrity of a new ice machine under the terms of our warranty prohibits the use of pre-existing (used) tubing or condensers.

HEAD PRESSURE CONTROL VALVE

Any remote condenser connected to a Manitowoc S- Model Ice Machine must have a head pressure control valve #836809-3 (available from Manitowoc Distributors) installed on the condenser package. Manitowoc will not accept substitute “off the shelf” head pressure control valves.

!Caution

Do not use a fan cycling control to try to maintain discharge pressure. Compressor failure will result.

FAN MOTOR

The condenser fan must be on during the complete ice machine freeze cycle (do not cycle on fan cycle control). The ice maker has a condenser fan motor circuit for use with a Manitowoc condenser. It is recommended that this circuit be used to control the condenser fan(s) on the multi-circuit condenser to assure it is on at the proper time. Do not exceed the rated amps for the fan motor circuit listed on the ice machine’s serial tag.

INTERNAL CONDENSER VOLUME

The multi-circuit condenser internal volume must not be less than or exceed that used by Manitowoc (see chart on next page). Do not exceed internal volume and try to add charge to compensate, as compressor failure will result.

CONDENSER T

T is the difference in temperature between the condensing refrigerant and entering air. The T should be 15 to 20°F (-9.4 to -6.6°C) at the beginning of the freeze cycle (peak load conditions) and drop down to 12 to 17°F (-11.1 to -8.3°C) during the last 75% of the freeze cycle (average load conditions).

REFRIGERANT CHARGE

Remote ice machines have the serial plate refrigerant charge (total system charge) located in the ice maker section. (Remote condensers and line sets are supplied with only a vapor charge.)

!Caution

Never add more than nameplate charge to ice machine for any application.

QUICK CONNECT FITTINGS

The ice machine and line sets come with quick connect fittings. It is recommended that matching quick connects (available through Manitowoc Distributors) be installed in the multi-circuit condenser, and that a vapor “holding” charge (5 oz.) of proper refrigerant be added to the condenser prior to connection of the ice machine or line set to the condenser.

Part Number 80-1620-3

2-19

Image 31 Contents
Model Ice Machines Personal Injury Potential Read These Before ProceedingPage Manitowoc ICE, INC Table of Contents Section Ice Machine Operation Table of ContentsSection Section Before Calling For Service Table of Contents MaintenanceTable of Contents Self-Contained Remote Air-Cooled How to Read a Model NumberModel Numbers Ice Cube SizesGeneral Information Section Accessories Model/Serial Number Location Section General Information Model/Serial Number LocationWarranty Coverage S320/S420 AIR and WATER-COOLED ICE Machines Ice Machine DimensionsIce Machine Dimension W Dimension D Dimension H GeneralS600 AIR and WATER-COOLED ICE Machines Installation Instructions SectionS600 Remote ICE Machines Electrical and AuCS Dimensions Width, Depth, and Height DimensionsInch 76 CM ICE Storage Bins Inch 56 CM ICE Storage Bins Ice Storage Bin DimensionsBin Model Dimension a Dimension B S500/S850/S1000 Remote ICE MachinesS1400 / S1800 Remote ICE Machines S1400/S1600/S1800 AIR and WATER-COOLED ICE MachinesB970 Inch 130 CM ICE Storage BinsIce Machine Heat of Rejection Section Installation Instructions Location of Ice MachineLeveling Leg and Foot Air-Cooled BaffleAir Baffle Minimum Circuit Ampacity Section Installation Instructions Electrical ServiceVoltage Fuse/Circuit BreakerMaximum Breaker Size & Minimum Circuit Amperage Chart Self Contained ICE Machine 230/1/50 For United Kingdom OnlySelf Contained ICE Machine 115/1/60 or 208-230/1/60 Self Contained ICE Machine 208-230/3/60Single Drain Connections Cooling Tower Applications Water-Cooled ModelsWater Supply Water Inlet LinesBin Drain Typical Water Supply Drain InstallationWater Supply and Drain Line SIZING/CONNECTIONS Condenser Line Set Discharge Line Liquid Line Air Temperature Around the Condenser Remote ICE Machines Refrigerant Charge Ice Machine Remote Single Line Set Circuit CondenserRouting Line Sets Guidelines for Routing Line SetsCalculating Remote Condenser Installation Distances Lengthening or Reducing Line SET Lengths Connecting a Line SETRemote Receiver Service Valve Backseating the Receiver Service ValveFAN Motor WarrantyInternal Condenser Volume Head Pressure Control ValveTypical Single Circuit Remote Condenser Installation NON-MANITOWOC MULTI-CIRCUIT Condenser Sizing ChartAdditional Checks for Remote Models Section Installation Instructions Installation Check ListAuCS Automatic Cleaning System Component Identification Section Ice Machine OperationInitial START-UP or START-UP After Automatic SHUT-OFF Ice Machine Operation Section Sequence Of OperationAutomatic SHUT-OFF 7. Automatic Shut-Off Safety TimersHarvest Sequence 5. Water Purge HarvestIce Thickness Check Ice Machine Operation Section Operational ChecksWater Level ICE Thickness CheckHarvest Sequence Water Purge Water Purge AdjustmentIce Machine Operation Section Ice Machine Inspection Section MaintenanceExterior Cleaning Cleaning the CondenserStraighten Bent Condenser Fins Maintenance SectionWater-Cooled Condenser Water Regulating Valve AlphaSanClean UP Procedure for Damaged Sachet Packet Section Maintenance GuardianfGuardianf Location GUARDIANf Sachet Replacement Frequency Sachet INSTALLATION/REPLACEMENT ProcedureStep Maintenance Section Interior Cleaning and SanitizingCleaning Procedure Model Amount of CleanerSolution Type Water Mixed With Sanitizing ProcedureModel Amount of Sanitizer Removal of Parts for CLEANING/SANITIZING Water Curtain Removal Ice Thickness Probe Water CurtainIce Thickness Probe Removal Water Trough Water Distribution TubeWater Distribution Tube Removal Water Pump Water Level ProbeWater Pump Removal Water Dump Valve Dump Valve DisassemblyDrain Line Check Valve Evaporator Tray RemovalWater Inlet Valve Removing the Front PanelsRemote ICE Machines Section Maintenance Removal from Service/WinterizationSELF-CONTAINED AIR-COOLED ICE Machines WATER-COOLED ICE MachinesThis page Intentionally Left Blank Problem Possible Cause To Correct ChecklistSafety Limit Feature Before Calling For Service Section