Toshiba MMU-AP0151MH, MMU-AP0181MH Adjustment of Wind Direction, How to set up the air direction

Page 16

3-7. Adjustment of Wind Direction

While the air conditioner stops, the horizontal flap (Up/Down air direction adjustment plate) automati- cally directs upward.

While the air conditioner is in ready status for heating, the horizontal flap (Up/Down air direction

adjustment plate) directs upward. The swinging operation starts after heating ready status has been

cleared, but “SWING ” is displayed on the remote controller even if the status is ready to heating.

How to set up the air direction

Push

SWING/FIX

1 Every pushing the button, the air direction changes.

button during operation.

In Heating operation

 

In Cooling / Dry operation

 

Set the horizontal flap (Up/Down

 

Set the horizontal flap (Up/Down

 

air direction adjustment plate)

 

air direction adjustment plate)

 

downward. If directing it upward,

 

upward. If directing it downward,

 

the hot air may not come to the

Initial setup

the dew may fall on near the air

Initial setup

foot come to the foot.

air outlet port or it drips.

 

 

How to start swinging

2 Push SWING/FIX button.

Set direction of the horizontal flap (Up/Down air

TEMP.

ON / OFF

direction adjustment plate) to the lowest position and then push SWING/FIX button again.

[SWING ] is displayed and the air direction automatically changes upward/downward.

In case when one remote controller controls the multiple indoor units, each indoor unit can be se- lected and its air direction can be set up.

How to stop swinging

3 Push SWING/FIX button again during swinging of the horizontal flap.

 

TIMER SET

 

TIME

FILTER

 

RESET TEST

SET CL

1, 2, 3

FAN MODE

SWING/FIX VENT

UNIT

4

The horizontal flap can be stopped at the desired position. After then the air direction can be again set up from the uppermost position by pushing SWING/FIX button.

*While the horizontal flap is set downward in cool- ing/drying operation, it does not stop.

If stopping the horizontal flap which directs down- ward during swinging, it stops after moving to the

3rd position from the top position.

4 UNIT

UNIT

To set up the air direction individually, push button to display each indoor unit No. in a group control. Then set up the air direction to a displayed indoor unit.

If there is no display, all the indoor units can be operated collectively.

• Every pushing UNIT button, the display exchanges as shown in the figure.

No display Unit No. 1-1 Unit No. 1-2

Unit No. 1-4 Unit No. 1-3

In FAN operation

In all modes

Series of operation

Initial setup

Display when stopping the swing

Fan/HeatCool/Dry

operationoperation

16

Image 16 Contents
Compact 4-Way Air Discharge Cassette Type Contents Safety Caution Check the following items after reinstallation Catch the inner cablesFire is caused at user’s side Metal section Earth positionSafety Caution Concerned to New Refrigerant Pipe MaterialsPiping Flare nutR410A Conventional air Air conditioner installation Conditioner installationTools General tools Conventional tools can be usedRecharge of Refrigerant Environment4mm-hexagonal wrench is required Cylinder with siphonSpace required for Installation and servicing Wired remoteConstruction Views External Views Drain-up standing-up sizeWiring Diagram For Indoor unitMCC-1402 Control P.C. boardParts Rating Parts RatingName of Each Part ModelParts Name of Remote Controller Display section Remote controller sensor Operation section Button Wind direction and SwingTurn on the main power switch and/or the leakage breaker Correct UsagePreparation StopWhen restarting the operation after stop Automatic Operation Super Heat Recovery Type OnlyStart Timer Operation Timer operationCancel of timer operation To select SET TimeAdjustment of Wind Direction How to set up the air directionHow to start swinging How to stop swingingInformation Air Conditioner Operations and Performance When the Following Symptoms are Found StandbyPrecautions for Safety New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply Connect all of the installation wiring correctlySelection of Installation Place Installation spaceInstallation space Installable ceiling height listCase of wireless type Installation of Indoor UnitDimensional view Ceiling opening and installation of hanging bolts Installation of ceiling panel Sold separatelyInstallation of hanging bolt Installation of remote controller Sold separatelyDrain Piping Work Piping material and dimensions Refrigerant PipingThermal insulating process Permissible pipe length and permissible height differenceElectric Work Connection of refrigerant pipeAirtight test/Air purge, etc Open fully valves of the outdoor unit Gas leak checkPower supply specifications Indoor unit power supply *1Indoor/Outdoor inter-unit wiring, Central controller wiring Remote controller wiring *4Applicable Controls Case of installation to high ceiling Case of remote controller-less Group controlChange of lighting time of filter sign Increased heating effectHow to execute test operation Case of wireless remote controllerCase of wired remote controller Test RUNTroubleshooting Confirmation of error historyCheck code list Confirmation and check Check methodTroubleshooting Error detected by TCC-LINK central control deviceMaintenance Daily maintenanceNew check code Way Air Discharge Cassette TypeRefrigerating Cycle Diagram Functional part name Functional outlineControl Specifications Outline of specifications RemarksRemote controller Control outline Command Control OutlineReset conditions ValueTCB-AX21E Central control mode Central control mode 1 Cannot operateCentral control mode 4 Cannot select mode Procedure Execute the setup operation while the unit stops Applied ControlDescription At shipment HEAT, Heat → CoolIndoor unit capacity Applied Control in Indoor UnitRemote location ON/OFF control box TCB-IFCB-4E Ventilating fan control from remote controller WiringFunction OperationPower peak-cut from indoor unit Using the setup tempButton, set to the setup data Leaving-ON prevention controlTroubleshooting Troubleshooting SummaryBefore troubleshooting Troubleshooting procedureCheck code list Check MethodAuxiliary code Judging deviceMG-SW Sensor block displayError detected by TCC-LINK central control device Check code Outdoor 7-segment display Auxiliary codeCheck code Troubleshooting by Check Display on Remote Controller Case of wired remote controller RBC-AMT31EConfirmation of error history Procedure DescriptionCase of central remote controller TCB-SC642TLE Check code Outdoor 7-segment displayCheck code Auxiliary code RemoteSetup method of No. capacity-over Detection Check codeMain Outdoor 7-segment display Remote Convenient functionsMain Outdoor 7-segment display Check code Auxiliary codeRemote DetectedRemote Check code Check item positionDetected Main Status Error detection condition Check item positionPosition Remote Check code Main Outdoor 7-segment display H07Check all the outdoor units in the corresponding line Check clogging of oil equation pipe between compressorsCheck code Main Outdoor 7-segment display Remote H16L30 Detected indoor address L31 P01 P03 P04 Name TS error judgment standard temperatureHeating Remote Check code Auxiliary code Error detection condition Check item position Outdoor 7-segment display Check code nameOutdoor 7-segment display Detected position Device Check codeDisplay on Central controlHow to check inverter output How to check resistance of compressor windingHow to check the outdoor fan motor Measured position CriteriaDiagnosis Procedure for Each Check Code E03E04 E02E06 Decreased number of indoor units E07E08 E12E15 E09 Duplicated masterE16 E18E19 Reference∗ 1 How to clear the error E20E23 E25E31 F01F02 F03F04 TD1 sensor error F05 TD2 sensor errorF06 TE1 sensor error F08 To sensor errorF29 Indoor other error F15 Outdoor temp sensor miscablingTE1, TL F23F31 H02H01 H03H06 Low-pressure protective operation Clogging for SV3E valve Leakage check for SV3C valveClogging check for SV3D valve Clogging check for oil-equalization circuit H08Oil level detective circuit system error TK3 temperature detective circuit errorH16 TK4 temperature detective circuit error L04L05 L03L07 Group line in individual indoor unit L10L17 L08L18 L29L20 L28P01 Indoor fan motor error L30 Interlock in indoor unitP03 L31P05 Open phase, negative phase P04 ActuationHigh-pressure SW Auxiliary code Compressor 1 sideP07 Heat sink overheat error P10 Indoor overflow errorIndoor fan motor error P12P13 Outdoor liquid back detection error 1. PMV1/PMV2 error P15Gas leak detection TS condition Auxiliary codeDischarge temp TD2 error P15 Gas leak detectionP17 TD condition Auxiliary codeP20 High-pressure protective operation P19 Way valve operation errorJudgment criteria P22 Outdoor fan Ipdu error Auxiliary code 0 ∗P26 Tr short-circuit protection error Detective circuit errorP29 P31Check procedure in case of stop with trouble How to read the check monitor Segment displaySegment Display Function Segment display on the outdoor unit Interface P.C. boardSW01 SW02 SW03 Display contents There is auxiliary code Check code ∗ ∗ ∗ for 3 seconds Data display of outdoor cycle Displayed on each outdoor unit SW03 SW02 Indoor address Segment display aSensor Characteristics Temperature sensor characteristicsW01 SW02 SW03 Display contents Segment display Segment display A, BConfiguration of Control Circuit Wired remote controller Up to 2 unitsWeekly timer Indoor UnitKit Connection of wireless remote controllerCompact 4-way Air Discharge Cassette Type Wireless Cassette Type ControllerRemote Compact4-way Air Discharge Connection of both remoteAir Discharge TypeMCC-1402 Compact 4-way CassetteOptional Connector Specifications of Indoor P.C. Board Function Connector Pin Specifications RemarksPart name Procedure Remarks DetachmentsPreparing work Attachment100 No. Part name Procedure Remarks 101102 No. Part name Procedure 103Fan guard 1. Detachment Bell mouth 1. Detachment104 Fan motor 1. Detachment105 Drain pump 1. DetachmentDetails of sensor lead wire drawing 106Arrow view B Details of a part107 Exchanger Recover refrigerant gasHeat 10. P.C. Board Exchange Procedures Exchange of P.C. Board for Indoor ServiceExchange procedure 108Procedure 1 Readout setup contents from Eeprom Remote controller operation diagramProcedure 2 Exchange of P.C. board for service 110Procedure 3 Writing-in of setup contents to Eeprom Eeprom layoutMake a note of the setup contents. Item code list Example Exploded Views and Parts List Ceiling Panel113 DescriptionCompact 4-way Air Discharge Cassette Type MMU-AP0071MH, AP0091MH, AP0121MH, AP0151MH, AP0181MH211 114Description Remarks Model Name 1150071MH 0091MH 0121MH 0151MH 0181MH 116 Description Model NameToshiba Carrier Corporation