Toshiba MMU-AP0151MH Tools, General tools Conventional tools can be used, Used tool Usage

Page 6

4. Tools

(1)Required Tools for R410A

Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.

1)Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))

2)Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)

3)Tools commonly used for R410A and for conventional refrigerant (R22)

The table below shows the tools exclusive for R410A and their interchangeability.

Tools exclusive for R410A (The following tools for R410A are required.)

Tools whose specifications are changed for R410A and their interchangeability

 

 

 

 

R410A

Conventional air

 

 

 

air conditioner installation

conditioner installation

No.

Used tool

Usage

 

 

 

 

Existence of

 

Whether conven-

Whether new equipment

 

 

 

 

 

 

 

new equipment

 

tional equipment can

can be used with

 

 

 

for R410A

 

be used

conventional refrigerant

 

 

 

 

 

 

 

Q

Flare tool

Pipe flaring

Yes

 

*(Note 1)

Yes

 

 

 

 

 

 

 

 

Copper pipe gauge for

Flaring by conventional

 

 

 

 

R

adjusting projection

Yes

 

*(Note 1)

*(Note 1)

flare tool

 

 

margin

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

Torque wrench

Connection of flare nut

Yes

 

No

No

 

 

 

 

 

 

 

T

Gauge manifold

Evacuating, refrigerant

Yes

 

No

No

 

 

 

 

 

charge, run check, etc.

 

U

Charge hose

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V

Vacuum pump adapter

Vacuum evacuating

Yes

 

No

Yes

 

 

 

 

 

 

 

W

Electronic balance for

Refrigerant charge

Yes

 

Yes

Yes

refrigerant charging

 

 

 

 

 

 

 

 

X

Refrigerant cylinder

Refrigerant charge

Yes

 

No

No

 

 

 

 

 

 

 

Y

Leakage detector

Gas leakage check

Yes

 

No

Yes

 

 

 

 

 

 

 

Y

Charging cylinder

Refrigerant charge

(Note 2)

 

No

No

 

 

 

 

 

 

 

(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.

(Note 2) Charging cylinder for R410A is being currently developed.

General tools (Conventional tools can be used.)

In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.

(1)

Vacuum pump

(7)

Screwdriver (+, –)

 

Use vacuum pump by

(8)

Spanner or Monkey wrench

 

attaching vacuum pump adapter.

(9)

Hole core drill

(2)

Torque wrench

(10)

Hexagon wrench (Opposite side 4mm)

(3)

Pipe cutter

(11)

Tape measure

(4)

Reamer

(12)

Metal saw

 

 

(5)Pipe bender

(6)Level vial

Also prepare the following equipments for other installation method and run check.

(1)

Clamp meter

(3)

Insulation resistance tester

(2)

Thermometer

(4)

Electroscope

6

Image 6 Contents
Compact 4-Way Air Discharge Cassette Type Contents Safety Caution Fire is caused at user’s side Check the following items after reinstallationCatch the inner cables Metal section Earth positionPiping Safety Caution Concerned to New RefrigerantPipe Materials Flare nutTools R410A Conventional air Air conditioner installationConditioner installation General tools Conventional tools can be used4mm-hexagonal wrench is required Recharge of RefrigerantEnvironment Cylinder with siphonConstruction Views External Views Space required for Installation and servicingWired remote Drain-up standing-up sizeMCC-1402 Wiring DiagramFor Indoor unit Control P.C. boardName of Each Part Parts RatingParts Rating ModelParts Name of Remote Controller Display sectionButton Remote controller sensorOperation section Wind direction and SwingPreparation Turn on the main power switch and/or the leakage breakerCorrect Usage StopAutomatic Operation Super Heat Recovery Type Only When restarting the operation after stopStart Cancel of timer operation Timer OperationTimer operation To select SET TimeHow to start swinging Adjustment of Wind DirectionHow to set up the air direction How to stop swingingInformation Air Conditioner Operations and Performance When the Following Symptoms are Found StandbyTo Disconnect the Appliance from Main Power Supply Precautions for SafetyNew Refrigerant Air Conditioner Installation Connect all of the installation wiring correctlyInstallation space Selection of Installation PlaceInstallation space Installable ceiling height listInstallation of Indoor Unit Case of wireless typeDimensional view Installation of hanging bolt Ceiling opening and installation of hanging boltsInstallation of ceiling panel Sold separately Installation of remote controller Sold separatelyDrain Piping Work Thermal insulating process Piping material and dimensionsRefrigerant Piping Permissible pipe length and permissible height differenceAirtight test/Air purge, etc Electric WorkConnection of refrigerant pipe Open fully valves of the outdoor unit Gas leak checkIndoor/Outdoor inter-unit wiring, Central controller wiring Power supply specificationsIndoor unit power supply *1 Remote controller wiring *4Applicable Controls Change of lighting time of filter sign Case of installation to high ceilingCase of remote controller-less Group control Increased heating effectCase of wired remote controller How to execute test operationCase of wireless remote controller Test RUNCheck code list TroubleshootingConfirmation of error history Confirmation and check Check methodTroubleshooting Error detected by TCC-LINK central control deviceNew check code MaintenanceDaily maintenance Way Air Discharge Cassette TypeRefrigerating Cycle Diagram Functional part name Functional outlineRemote controller Control outline Command Control SpecificationsOutline of specifications Remarks Control OutlineReset conditions ValueTCB-AX21E Central control mode 1 Cannot operate Central control modeCentral control mode 4 Cannot select mode Procedure Execute the setup operation while the unit stops Applied ControlDescription At shipment HEAT, Heat → CoolApplied Control in Indoor Unit Indoor unit capacityRemote location ON/OFF control box TCB-IFCB-4E Function Ventilating fan control from remote controllerWiring OperationButton, set to the setup data Power peak-cut from indoor unitUsing the setup temp Leaving-ON prevention controlBefore troubleshooting TroubleshootingTroubleshooting Summary Troubleshooting procedureAuxiliary code Check code listCheck Method Judging deviceMG-SW Sensor block displayError detected by TCC-LINK central control device Check code Outdoor 7-segment display Auxiliary codeCheck code Confirmation of error history Troubleshooting by Check Display on Remote ControllerCase of wired remote controller RBC-AMT31E Procedure DescriptionCase of central remote controller TCB-SC642TLE Check code Auxiliary code Check codeOutdoor 7-segment display RemoteMain Outdoor 7-segment display Remote Setup method of No. capacity-over DetectionCheck code Convenient functionsRemote Main Outdoor 7-segment displayCheck code Auxiliary code DetectedRemote Check code Check item positionStatus Error detection condition Check item position Detected MainPosition Remote Check all the outdoor units in the corresponding line Check code Main Outdoor 7-segment displayH07 Check clogging of oil equation pipe between compressorsCheck code Main Outdoor 7-segment display Remote H16L30 Detected indoor address L31 P01 P03 P04 TS error judgment standard temperature NameHeating Remote Check code Auxiliary code Error detection condition Check item position Outdoor 7-segment display Check code nameDisplay on Outdoor 7-segment display Detected positionDevice Check code Central controlHow to check the outdoor fan motor How to check inverter outputHow to check resistance of compressor winding Measured position CriteriaE04 Diagnosis Procedure for Each Check CodeE03 E02E06 Decreased number of indoor units E07E15 E08E12 E09 Duplicated masterE19 E16E18 ReferenceE23 ∗ 1 How to clear the errorE20 E25F02 E31F01 F03F06 TE1 sensor error F04 TD1 sensor errorF05 TD2 sensor error F08 To sensor errorTE1, TL F29 Indoor other errorF15 Outdoor temp sensor miscabling F23H01 F31H02 H03H06 Low-pressure protective operation Leakage check for SV3C valve Clogging for SV3E valveClogging check for SV3D valve Clogging check for oil-equalization circuit H08Oil level detective circuit system error TK3 temperature detective circuit errorL05 H16 TK4 temperature detective circuit errorL04 L03L17 L07 Group line in individual indoor unitL10 L08L20 L18L29 L28P03 P01 Indoor fan motor errorL30 Interlock in indoor unit L31High-pressure SW P05 Open phase, negative phaseP04 Actuation Auxiliary code Compressor 1 sideIndoor fan motor error P07 Heat sink overheat errorP10 Indoor overflow error P12Gas leak detection P13 Outdoor liquid back detection error 1. PMV1/PMV2 errorP15 TS condition Auxiliary codeP17 Discharge temp TD2 errorP15 Gas leak detection TD condition Auxiliary codeP19 Way valve operation error P20 High-pressure protective operationJudgment criteria P22 Outdoor fan Ipdu error Auxiliary code 0 ∗P29 P26 Tr short-circuit protection errorDetective circuit error P31Segment Display Function Check procedure in case of stop with troubleHow to read the check monitor Segment display Segment display on the outdoor unit Interface P.C. boardSW01 SW02 SW03 Display contents There is auxiliary code Check code ∗ ∗ ∗ for 3 seconds Data display of outdoor cycle Displayed on each outdoor unit SW03 SW02 Indoor address Segment display aW01 SW02 SW03 Display contents Segment display Sensor CharacteristicsTemperature sensor characteristics Segment display A, BWeekly timer Configuration of Control CircuitWired remote controller Up to 2 units Indoor UnitConnection of wireless remote controller KitCompact 4-way Air Discharge Cassette Type Remote WirelessCassette Type Controller Compact4-way Air Discharge Connection of both remoteMCC-1402 Compact 4-way Air DischargeType CassetteOptional Connector Specifications of Indoor P.C. Board Function Connector Pin Specifications RemarksPreparing work Part name Procedure RemarksDetachments Attachment100 No. Part name Procedure Remarks 101102 Fan guard 1. Detachment No. Part name Procedure103 Bell mouth 1. Detachment104 Fan motor 1. Detachment105 Drain pump 1. DetachmentArrow view B Details of sensor lead wire drawing106 Details of a partExchanger Recover refrigerant gas 107Heat Exchange procedure 10. P.C. Board Exchange ProceduresExchange of P.C. Board for Indoor Service 108Procedure 1 Readout setup contents from Eeprom Remote controller operation diagramProcedure 2 Exchange of P.C. board for service 110Procedure 3 Writing-in of setup contents to Eeprom Eeprom layoutMake a note of the setup contents. Item code list Example 113 Exploded Views and Parts ListCeiling Panel Description211 Compact 4-way Air Discharge Cassette TypeMMU-AP0071MH, AP0091MH, AP0121MH, AP0151MH, AP0181MH 114115 Description Remarks Model Name0071MH 0091MH 0121MH 0151MH 0181MH 116 Description Model NameToshiba Carrier Corporation