Toshiba MMU-AP0181MH, MMU-AP0151MH, MMU-AP0091MH Precautions for Safety, Refrigerant piping

Page 20

Accessory parts and Parts to be procured locally

HAccessory parts

 

Part name

Q’ty

Shape

Usage

 

 

 

 

 

 

Installation Manual

1

This manual

(Ensure hand over to customer)

 

 

 

 

 

 

Heat insulating pipe

2

 

For heat insulation of the pipe connecting section

 

 

 

 

 

 

Installation pattern

1

——

For checking of ceiling opening and the main unit position

 

 

 

 

 

 

Installation gauge

2

 

For positioning of the ceiling position

 

 

(To be used with the installation pattern)

 

 

 

 

 

 

 

 

 

 

Pattern fixing screw

4

M5 × 16L

For attach the installation pattern

 

 

 

 

 

 

Heat insulator

1

 

For heat insulation of drain connecting section

 

 

 

 

 

 

Washer

8

 

For hanging unit

 

 

 

 

 

 

Hose band

1

 

For connecting drain pipe

 

 

 

 

 

 

Flexible hose

1

 

For adjusting core-out of drain pipe

 

 

 

 

 

20

Heat insulator A

1

 

For sealing of wire connecting port

 

 

 

 

Heat insulator B

1

 

For sealing of wire connecting port

 

 

 

 

 

 

 

Refrigerant piping

Piping material used for the conventional refrigerant cannot be used.

Use copper pipe only with a wall thickness of 0.8 mm or more for Ø6.4, Ø9.5, Ø12.7.

Flare nut and flare operations are also different from those of the conventional refrigerant. Use the flare nut fitted to the indoor unit of the air conditioner.

1 PRECAUTIONS FOR SAFETY

Ensure that all Local, National and International regulations are satisfied.

Important safety information are described in this installation manual. Please ensure this manual is read thoroughly and kept for future reference.

After the installation work, perform a trial operation to check for any problem.

Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.

Turn off the main power supply switch (or breaker) before any unit maintenance.

Ask the customer to keep the Installation Manual together with the Owner’s Manual.

CAUTION

New Refrigerant Air Conditioner Installation

THIS AIR CONDITIONER FEATURES A NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DEPLETE OZONE LAYER.

The pressure of R410A is 1.6 times higher than that of former refrigerant R22. The refrigerating oil has also been changed. Therefore be sure that any former refrigerant, refrigerant oil or any other contaminants do not enter the refrigerating cycle of the air conditioner, during either installation or service work. If incorrect tools or operating procedures are used, there is a possibility of a serious accident. Use only tools and materials that have been designed to operate with R410A.

To prevent the risk of charging with an incorrect refrigerant, the dimensions of the charging port connections are different to those used for conventional refrigerant. Therefore only tools designed to operate with R410A can be used.

For connecting pipes, use piping specifically designed for R410A.

During installation, ensure pipes are clean and ensure contaminants do not enter in the pipes as the system is affected by impurities such as water, oxide scales, dirt, oil, etc. Do not use existing pipe work from previous installation as this will cause problems due to pressure resistances and impurities within the pipe.

CAUTION

To Disconnect the Appliance from Main Power Supply.

This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm.

WARNING

Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner. Inappropriate installation may result in water leakage, electric shock or fire.

Turn off the main power supply switch or breaker before attempting any electrical work. Make sure all power switches are off. Failure to do so may cause an electric shock.

Connect all of the installation wiring correctly.

If the installation wiring is incorrect electrical parts may be damaged.

During the transportation and installation of the air conditioning unit, ensure that gaseous matter other than the specified refrigerant does not enter into the refrigeration cycle.

If a refrigerant becomes contaminated with foreign gases, the gas pressure within the refrigerant cycle will become abnormally high and may result in the fracture of pipe work and possible human injury.

Do not modify this unit by removing any of the safety guards or by overriding any of the safety interlock switches.

Exposure of the unit to water or other forms of moisture before installation may cause a short-circuit of the electrical parts.

Do not store it in a wet basement or expose to rain or water.

After unpacking the unit, examine for possible damage.

Do not install in a place that might increase the vibration of the unit.

To avoid personal injury (with sharp edges), be careful when handling parts.

Perform installation work properly according to the Installation Manual. Inappropriate installation may result in water leakage, electric shock or fire.

When the air conditioner is installed in a small room, provide appropriate measures to ensure that in the event of a refrigerant leak the rooms does not exceed the critical level.

Image 20
Contents Compact 4-Way Air Discharge Cassette Type Contents Safety Caution Check the following items after reinstallation Catch the inner cablesFire is caused at user’s side Metal section Earth positionSafety Caution Concerned to New Refrigerant Pipe MaterialsPiping Flare nutR410A Conventional air Air conditioner installation Conditioner installationTools General tools Conventional tools can be usedRecharge of Refrigerant Environment4mm-hexagonal wrench is required Cylinder with siphonSpace required for Installation and servicing Wired remoteConstruction Views External Views Drain-up standing-up sizeWiring Diagram For Indoor unitMCC-1402 Control P.C. boardParts Rating Parts RatingName of Each Part ModelParts Name of Remote Controller Display sectionRemote controller sensor Operation sectionButton Wind direction and SwingTurn on the main power switch and/or the leakage breaker Correct UsagePreparation StopStart Automatic Operation Super Heat Recovery Type OnlyWhen restarting the operation after stop Timer Operation Timer operationCancel of timer operation To select SET TimeAdjustment of Wind Direction How to set up the air directionHow to start swinging How to stop swingingInformation Air Conditioner Operations and Performance When the Following Symptoms are Found StandbyPrecautions for Safety New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply Connect all of the installation wiring correctlySelection of Installation Place Installation spaceInstallation space Installable ceiling height listDimensional view Installation of Indoor UnitCase of wireless type Ceiling opening and installation of hanging bolts Installation of ceiling panel Sold separatelyInstallation of hanging bolt Installation of remote controller Sold separatelyDrain Piping Work Piping material and dimensions Refrigerant PipingThermal insulating process Permissible pipe length and permissible height differenceElectric Work Connection of refrigerant pipeAirtight test/Air purge, etc Open fully valves of the outdoor unit Gas leak checkPower supply specifications Indoor unit power supply *1Indoor/Outdoor inter-unit wiring, Central controller wiring Remote controller wiring *4Applicable Controls Case of installation to high ceiling Case of remote controller-less Group controlChange of lighting time of filter sign Increased heating effectHow to execute test operation Case of wireless remote controllerCase of wired remote controller Test RUNTroubleshooting Confirmation of error historyCheck code list Confirmation and check Check methodTroubleshooting Error detected by TCC-LINK central control deviceMaintenance Daily maintenanceNew check code Way Air Discharge Cassette TypeRefrigerating Cycle Diagram Functional part name Functional outlineControl Specifications Outline of specifications RemarksRemote controller Control outline Command Control OutlineReset conditions ValueTCB-AX21E Central control mode 4 Cannot select mode Central control mode 1 Cannot operateCentral control mode Procedure Execute the setup operation while the unit stops Applied ControlDescription At shipment HEAT, Heat → CoolRemote location ON/OFF control box TCB-IFCB-4E Applied Control in Indoor UnitIndoor unit capacity Ventilating fan control from remote controller WiringFunction OperationPower peak-cut from indoor unit Using the setup tempButton, set to the setup data Leaving-ON prevention controlTroubleshooting Troubleshooting SummaryBefore troubleshooting Troubleshooting procedureCheck code list Check MethodAuxiliary code Judging deviceMG-SW Sensor block displayError detected by TCC-LINK central control device Check code Outdoor 7-segment display Auxiliary codeCheck code Troubleshooting by Check Display on Remote Controller Case of wired remote controller RBC-AMT31EConfirmation of error history Procedure DescriptionCase of central remote controller TCB-SC642TLE Check code Outdoor 7-segment displayCheck code Auxiliary code RemoteSetup method of No. capacity-over Detection Check codeMain Outdoor 7-segment display Remote Convenient functionsMain Outdoor 7-segment display Check code Auxiliary codeRemote DetectedRemote Check code Check item positionPosition Remote Status Error detection condition Check item positionDetected Main Check code Main Outdoor 7-segment display H07Check all the outdoor units in the corresponding line Check clogging of oil equation pipe between compressorsCheck code Main Outdoor 7-segment display Remote H16L30 Detected indoor address L31 P01 P03 P04 Heating TS error judgment standard temperatureName Remote Check code Auxiliary code Error detection condition Check item position Outdoor 7-segment display Check code nameOutdoor 7-segment display Detected position Device Check codeDisplay on Central controlHow to check inverter output How to check resistance of compressor windingHow to check the outdoor fan motor Measured position CriteriaDiagnosis Procedure for Each Check Code E03E04 E02E06 Decreased number of indoor units E07E08 E12E15 E09 Duplicated masterE16 E18E19 Reference∗ 1 How to clear the error E20E23 E25E31 F01F02 F03F04 TD1 sensor error F05 TD2 sensor errorF06 TE1 sensor error F08 To sensor errorF29 Indoor other error F15 Outdoor temp sensor miscablingTE1, TL F23F31 H02H01 H03H06 Low-pressure protective operation Clogging check for SV3D valve Leakage check for SV3C valveClogging for SV3E valve Clogging check for oil-equalization circuit H08Oil level detective circuit system error TK3 temperature detective circuit errorH16 TK4 temperature detective circuit error L04L05 L03L07 Group line in individual indoor unit L10L17 L08L18 L29L20 L28P01 Indoor fan motor error L30 Interlock in indoor unitP03 L31P05 Open phase, negative phase P04 ActuationHigh-pressure SW Auxiliary code Compressor 1 sideP07 Heat sink overheat error P10 Indoor overflow errorIndoor fan motor error P12P13 Outdoor liquid back detection error 1. PMV1/PMV2 error P15Gas leak detection TS condition Auxiliary codeDischarge temp TD2 error P15 Gas leak detectionP17 TD condition Auxiliary codeJudgment criteria P19 Way valve operation errorP20 High-pressure protective operation P22 Outdoor fan Ipdu error Auxiliary code 0 ∗P26 Tr short-circuit protection error Detective circuit errorP29 P31Check procedure in case of stop with trouble How to read the check monitor Segment displaySegment Display Function Segment display on the outdoor unit Interface P.C. boardSW01 SW02 SW03 Display contents There is auxiliary code Check code ∗ ∗ ∗ for 3 seconds Data display of outdoor cycle Displayed on each outdoor unit SW03 SW02 Indoor address Segment display aSensor Characteristics Temperature sensor characteristicsW01 SW02 SW03 Display contents Segment display Segment display A, BConfiguration of Control Circuit Wired remote controller Up to 2 unitsWeekly timer Indoor UnitCompact 4-way Air Discharge Cassette Type Connection of wireless remote controllerKit Wireless Cassette Type ControllerRemote Compact4-way Air Discharge Connection of both remoteAir Discharge TypeMCC-1402 Compact 4-way CassetteOptional Connector Specifications of Indoor P.C. Board Function Connector Pin Specifications RemarksPart name Procedure Remarks DetachmentsPreparing work Attachment100 No. Part name Procedure Remarks 101102 No. Part name Procedure 103Fan guard 1. Detachment Bell mouth 1. Detachment104 Fan motor 1. Detachment105 Drain pump 1. DetachmentDetails of sensor lead wire drawing 106Arrow view B Details of a partHeat Exchanger Recover refrigerant gas107 10. P.C. Board Exchange Procedures Exchange of P.C. Board for Indoor ServiceExchange procedure 108Procedure 1 Readout setup contents from Eeprom Remote controller operation diagramProcedure 2 Exchange of P.C. board for service 110Procedure 3 Writing-in of setup contents to Eeprom Eeprom layoutMake a note of the setup contents. Item code list Example Exploded Views and Parts List Ceiling Panel113 DescriptionCompact 4-way Air Discharge Cassette Type MMU-AP0071MH, AP0091MH, AP0121MH, AP0151MH, AP0181MH211 1140071MH 0091MH 0121MH 0151MH 0181MH 115Description Remarks Model Name 116 Description Model NameToshiba Carrier Corporation

MMU-AP0181MH, MMU-AP0071MH, MMU-AP0091MH, MMU-AP0151MH, MMU-AP0121MH specifications

The Toshiba MMU-AP series, consisting of models MMU-AP0121MH, MMU-AP0151MH, MMU-AP0091MH, MMU-AP0071MH, and MMU-AP0181MH, represents a significant advancement in the realm of power management and energy efficiency for a variety of applications. These modules are designed to optimize performance while ensuring minimal energy consumption, making them suitable for both commercial and industrial uses.

One of the standout features of the MMU-AP series is its intelligent power management technology. This feature allows for adaptive energy distribution based on real-time demands. By leveraging precise control algorithms, the modules can adjust their output to match the specific requirements of connected devices, ultimately leading to reduced power loss and increased efficiency. This adaptability not only benefits end-users by lowering operational costs but also contributes to a greener environment by minimizing waste.

The versatility of the MMU-AP series is evident in its wide range of operational capabilities. These power modules are designed to work effectively in various voltage levels and load conditions. With input voltage ranges suitable for standard industrial environments, they can easily be integrated into existing systems, enhancing overall functionality without requiring extensive modifications.

Moreover, the compact design of the MMU-AP modules is another notable characteristic. Their size and light weight facilitate easier installation and integration into tight spaces, making them ideal for applications where real estate is a premium. This compact profile does not compromise performance, as these modules are engineered to deliver robust power output while maintaining thermal efficiency.

In terms of reliability, the MMU-AP series is built with high-grade components that withstand harsh operating conditions. With features such as over-voltage protection, short-circuit protection, and thermal shutdown capabilities, users can trust that their equipment would operate safely and efficiently, thereby extending the lifespan of both the power modules and the devices they serve.

Finally, Toshiba’s commitment to innovation ensures that the MMU-AP series incorporates cutting-edge technology. The series supports communication protocols that enable seamless integration with smart systems, paving the way for advanced monitoring and control functions. This levels up the user experience, providing insights into performance and diagnostics that are crucial for uptime and reliability in demanding environments.

In conclusion, the Toshiba MMU-AP series offers a blend of efficiency, adaptability, and advanced technology, making it a valuable asset for various industrial and commercial applications. Its intelligent design and robust features ensure that users can optimize energy use while maintaining high performance and reliability.