Toshiba MMU-AP0151MH Procedure 3 Writing-in of setup contents to Eeprom, Eeprom layout

Page 111

Procedure 3 : Writing-in of setup contents to EEPROM

(The EEPROM contents which are installed on the service P.C. board have been set up at shipment from the factory.)

1. Push SET + CL + TEST buttons simultaneously for 4 seconds or more. 1

(

is displayed in the UNIT No box.)

In this time, ￿￿ is displayed in the item code (DN). The fan of the indoor unit operates, and also starts swinging in a model with flap.

2.Using temperature setup / buttons, the item code (DN) can be moved one step up 1 or down one by one. 3

3.First set up the type and capacity code of the indoor unit.

(The data at shipment from the factory is written in EEPROM by changing the type and capacity code.)

1)Set ￿￿ to the item code (DN). (As before)

2)Using the timer time / buttons, set up the type. 4

(For example, 0001 indicates 4-way Air Discharge Cassette type.): Refer to the attached table.

3)Push SET button. (OK if display goes on.) 5

4)Using temperature setup / buttons, set ￿￿ to the item code (DN).

5)Using the timer time / buttons, set up the capacity code.

(For example, 0012 indicates 027 type.): Refer to the attached table.

6)Push

7)Push

SET

TEST

button. (OK if display goes on.)

button to return to the normal stop status.

4.In the next, the contents such as address setup, which were set up at the local site after installation are written in EEPROM. Execute again the operation in the above item 1.).

5.Using temperature setup / buttons, set ￿￿ to the item code (DN). (Lighting time setup for filter sign)

6.Compare the contents of the setup data which is displayed in this time with contents noted in a memo in Procedure 1 and customer’s information.

1)If data is incorrect, change it using the timer time / buttons so that it matches with contents noted in a memo, and then push SET button. (OK if display goes on.)

2)Do nothing if data is same as those in the memo.

7.Using temperature setup / buttons, change the item code (DN).

Check also the contents of the setup data and then change them it to those in the memo.

8.Then repeat operations in items 6. and 7.

9.After setup operation, push TEST button to return to the normal stop status. 6

In a group operation, turn off the power supply once, return the group wires between indoor units and CN41 connectors as before, and then turn on power of all the indoor units.

(It requires approx. 1 minute to operate the remote controller.)

The item code (DN) is consisted with ￿￿ to .. . DN No. may jump on the way.

Even if pushing SET button after changing the data incorrectly, the data can be returned to one before change by pushing CL button before changing the item code (DN).

<EEPROM layout>

EEPROM (IC10) is attached to IC socket. To remove it, use a pair of tweezers, etc.

To attach EEPROM, arrange the direction as shown in the following figures.

In exchanging time, pay attention not to bend the lead wire of IC.

P.C. board (MCC-1402)

P.C. board (MCC-1403)

EPROM (IC10)

Align notch directions of IC socket and EEPROM for installation.

Notch

IC socket Notch

EPROM

EPROM (IC10)

111

Image 111 Contents
Compact 4-Way Air Discharge Cassette Type Contents Safety Caution Metal section Earth position Check the following items after reinstallationCatch the inner cables Fire is caused at user’s sideFlare nut Safety Caution Concerned to New RefrigerantPipe Materials PipingGeneral tools Conventional tools can be used R410A Conventional air Air conditioner installationConditioner installation ToolsCylinder with siphon Recharge of RefrigerantEnvironment 4mm-hexagonal wrench is requiredDrain-up standing-up size Space required for Installation and servicingWired remote Construction Views External ViewsControl P.C. board Wiring DiagramFor Indoor unit MCC-1402Model Parts RatingParts Rating Name of Each PartDisplay section Parts Name of Remote ControllerWind direction and Swing Remote controller sensorOperation section ButtonStop Turn on the main power switch and/or the leakage breakerCorrect Usage PreparationAutomatic Operation Super Heat Recovery Type Only When restarting the operation after stopStart To select SET Time Timer OperationTimer operation Cancel of timer operationHow to stop swinging Adjustment of Wind DirectionHow to set up the air direction How to start swingingInformation Air Conditioner Operations and Performance Standby When the Following Symptoms are FoundConnect all of the installation wiring correctly Precautions for SafetyNew Refrigerant Air Conditioner Installation To Disconnect the Appliance from Main Power SupplyInstallable ceiling height list Selection of Installation PlaceInstallation space Installation spaceInstallation of Indoor Unit Case of wireless typeDimensional view Installation of remote controller Sold separately Ceiling opening and installation of hanging boltsInstallation of ceiling panel Sold separately Installation of hanging boltDrain Piping Work Permissible pipe length and permissible height difference Piping material and dimensionsRefrigerant Piping Thermal insulating processOpen fully valves of the outdoor unit Gas leak check Electric WorkConnection of refrigerant pipe Airtight test/Air purge, etcRemote controller wiring *4 Power supply specificationsIndoor unit power supply *1 Indoor/Outdoor inter-unit wiring, Central controller wiringApplicable Controls Increased heating effect Case of installation to high ceilingCase of remote controller-less Group control Change of lighting time of filter signTest RUN How to execute test operationCase of wireless remote controller Case of wired remote controllerConfirmation and check Check method TroubleshootingConfirmation of error history Check code listError detected by TCC-LINK central control device TroubleshootingWay Air Discharge Cassette Type MaintenanceDaily maintenance New check codeFunctional part name Functional outline Refrigerating Cycle DiagramControl Outline Control SpecificationsOutline of specifications Remarks Remote controller Control outline CommandValue Reset conditionsTCB-AX21E Central control mode 1 Cannot operate Central control modeCentral control mode 4 Cannot select mode Applied Control Procedure Execute the setup operation while the unit stopsHEAT, Heat → Cool Description At shipmentApplied Control in Indoor Unit Indoor unit capacityRemote location ON/OFF control box TCB-IFCB-4E Operation Ventilating fan control from remote controllerWiring FunctionLeaving-ON prevention control Power peak-cut from indoor unitUsing the setup temp Button, set to the setup dataTroubleshooting procedure TroubleshootingTroubleshooting Summary Before troubleshootingJudging device Check code listCheck Method Auxiliary codeSensor block display MG-SWCheck code Outdoor 7-segment display Auxiliary code Error detected by TCC-LINK central control deviceCheck code Procedure Description Troubleshooting by Check Display on Remote ControllerCase of wired remote controller RBC-AMT31E Confirmation of error historyCase of central remote controller TCB-SC642TLE Remote Check codeOutdoor 7-segment display Check code Auxiliary codeConvenient functions Setup method of No. capacity-over DetectionCheck code Main Outdoor 7-segment display RemoteDetected Main Outdoor 7-segment displayCheck code Auxiliary code RemoteCheck item position Remote Check codeStatus Error detection condition Check item position Detected MainPosition Remote Check clogging of oil equation pipe between compressors Check code Main Outdoor 7-segment displayH07 Check all the outdoor units in the corresponding lineH16 Check code Main Outdoor 7-segment display RemoteL30 Detected indoor address L31 P01 P03 P04 TS error judgment standard temperature NameHeating Remote Check code Auxiliary code Outdoor 7-segment display Check code name Error detection condition Check item positionCentral control Outdoor 7-segment display Detected positionDevice Check code Display onMeasured position Criteria How to check inverter outputHow to check resistance of compressor winding How to check the outdoor fan motorE02 Diagnosis Procedure for Each Check CodeE03 E04E07 E06 Decreased number of indoor unitsE09 Duplicated master E08E12 E15Reference E16E18 E19E25 ∗ 1 How to clear the errorE20 E23F03 E31F01 F02F08 To sensor error F04 TD1 sensor errorF05 TD2 sensor error F06 TE1 sensor errorF23 F29 Indoor other errorF15 Outdoor temp sensor miscabling TE1, TLH03 F31H02 H01H06 Low-pressure protective operation Leakage check for SV3C valve Clogging for SV3E valveClogging check for SV3D valve H08 Clogging check for oil-equalization circuitTK3 temperature detective circuit error Oil level detective circuit system errorL03 H16 TK4 temperature detective circuit errorL04 L05L08 L07 Group line in individual indoor unitL10 L17L28 L18L29 L20L31 P01 Indoor fan motor errorL30 Interlock in indoor unit P03Auxiliary code Compressor 1 side P05 Open phase, negative phaseP04 Actuation High-pressure SWP12 P07 Heat sink overheat errorP10 Indoor overflow error Indoor fan motor errorTS condition Auxiliary code P13 Outdoor liquid back detection error 1. PMV1/PMV2 errorP15 Gas leak detectionTD condition Auxiliary code Discharge temp TD2 errorP15 Gas leak detection P17P19 Way valve operation error P20 High-pressure protective operationJudgment criteria Auxiliary code 0 ∗ P22 Outdoor fan Ipdu errorP31 P26 Tr short-circuit protection errorDetective circuit error P29Segment display on the outdoor unit Interface P.C. board Check procedure in case of stop with troubleHow to read the check monitor Segment display Segment Display FunctionSW01 SW02 SW03 Display contents There is auxiliary code Check code ∗ ∗ ∗ for 3 seconds SW03 SW02 Indoor address Segment display a Data display of outdoor cycle Displayed on each outdoor unitSegment display A, B Sensor CharacteristicsTemperature sensor characteristics W01 SW02 SW03 Display contents Segment displayIndoor Unit Configuration of Control CircuitWired remote controller Up to 2 units Weekly timerConnection of wireless remote controller KitCompact 4-way Air Discharge Cassette Type Compact4-way Air Discharge Connection of both remote WirelessCassette Type Controller RemoteCassette Air DischargeType MCC-1402 Compact 4-wayFunction Connector Pin Specifications Remarks Optional Connector Specifications of Indoor P.C. BoardAttachment Part name Procedure RemarksDetachments Preparing work100 101 No. Part name Procedure Remarks102 Bell mouth 1. Detachment No. Part name Procedure103 Fan guard 1. DetachmentFan motor 1. Detachment 104Drain pump 1. Detachment 105Details of a part Details of sensor lead wire drawing106 Arrow view B Exchanger Recover refrigerant gas 107 Heat 108 10. P.C. Board Exchange ProceduresExchange of P.C. Board for Indoor Service Exchange procedureRemote controller operation diagram Procedure 1 Readout setup contents from Eeprom110 Procedure 2 Exchange of P.C. board for serviceEeprom layout Procedure 3 Writing-in of setup contents to EepromMake a note of the setup contents. Item code list Example Description Exploded Views and Parts ListCeiling Panel 113114 Compact 4-way Air Discharge Cassette TypeMMU-AP0071MH, AP0091MH, AP0121MH, AP0151MH, AP0181MH 211115 Description Remarks Model Name0071MH 0091MH 0121MH 0151MH 0181MH Description Model Name 116Toshiba Carrier Corporation