Check code name | | Check code name | | | | Cause of operation | |
| | | | | | | |
[H07] | | Oil level down | 1. Valves of balance pipes closed. | |
| | detection protection | 2. Miscabling or misinstallation of TK1 to TK4 sensors |
| | | | 3. | TK1 to TK4 sensor error | |
| | | | 4. | Gas leak or oil leak of all outdoor units | |
| | | | 5. | Refrigerant stagnation of compressor case | |
| | | | 6. | SV3A, 3B, 3D, 3C, 3E valve error | |
| | | | 7. | Clogging of oil return circuit from oil separator | |
| | | | 8. | Clogging of oil-equation circuit system | |
| | | | | | | |
Are TK1, TK2, TK3, and | | NO | | | | |
| | | | Correct miswiring and misinstallation. |
TK4 sensors connected correctly? | | | | | TK1: CN514, TK2: CN515 | ) |
| | |
Is there no sensor coming-off or misinstallation? | | | | ( TK3: CN516, TK4: CN523 |
YES
In some cases, it may be difficult to check the leakage of clogging in the following condition of refrigerant stagnation in low ambient temperature condition.
In this case, take a longer operating time prior to check.
(Criterion: Discharge temperature of TD1 and TD2 are 60°C or higher)
(*1)
a) | Leakage check for SV3A valve (For multiple outdoor unit system) |
| • | Turn off the power supply, take off connector of SV3A valve, and then start a test operation after power-ON. |
| • | Check the temperature change at secondary side of SV3A valve during operation . (• in the figure.) |
| | → If temperature is raised, it is a leakage of SV3A valve. Replace SV3A valve. |
b) | Leakage check for SV3C valve |
| • | Turn off the power supply, take off connector of SV3C valve, and then start a test operation after power-ON. |
| • | After operation for several minutes, check temperature at secondary side of SV3C valve. (‚ in the figure.) |
| | → If temperature is high (equivalent to discharge temperature TD), it is a leakage of SV3C valve. Replace |
| | SV3C valve. |
Are TK1 and TK2 sensors connected correctly? Is there no sensor coming-off or misinstallation?
Are sensor characteristics normal?
YES
Check leakage of SV6 circuit.
Normal
NO
Characteristics-2
Abnormal
Correct miswiring and misinstallation.
(TS1: CN504, TS2: CN522)
Sensor error Replace
Replace defective parts.
(Even if there is leakage from SV3C valve does not occur, temperature of SV3C valve at secondary side |
rises during operation. When the checked temperature is equivalent to TD temperature, it is a leakage of |
SV3C valve. Replace SV3C valve.) |
c) Clogging check for SV3B valve (For multiple outdoor unit system) |
• While outdoor unit is operated, set up SW01/02/03 = [2] [1] [3] to 7-segment display [Hr] [ 2], and push SW04 |
for 2 seconds or more. |
Check whether there is setup missing | | | | Abnormal | Set up to cooling only operation mode. |
| | | | | | Item code (DN) OF |
of cooling only indoor unit. | | | | | | | |
| | | | | | | Cooling only operation mode: 0001 |
| | | | | | | | | | |
| | Normal | | | | | NO | | | |
Are characteristics of TK1 to TK4 normal? | | | | | | |
| | | Characteristics-4 | | Sensor error Replace |
| | YES | | | | | | | |
| | | | | | | | | | | |
| | | | | | | |
Check gas leak of outdoor unit. | | | | Abnormal | Specify a position where |
Check oil stain in the | | | | | | | | gas leaked and repair it. |
| | | | | | |
( machine room of outdoor unit. ) | | | | | | | | (Recharge, refill oil.) |
| | Normal | | | | | | | | | | |
| | | | | | | | NO | | | |
Is the flow selector unit normal? | | | | | | | Repair the flow selector unit. |
| | | | | |
| YES | | | | | | | | | | |
| | | | | | | | | | |
Check accumulation of | | NO | | | | ( 1) Check leakage of | YES | |
| | | | solenoid valve. (SV3C) | | | Replace defective parts |
refrigerant in compressor case. | | | | | Check clogging. | | |
| Refrigerant accumulation | | | | (SV3E) | | | |
| | | | | No leakage or clogging |
| | | | | | | | |
Correct accumulation of | | | | | | | | | | | |
refrigerant in compressor case, | | | | | | | | | | | |
reset power supply and | | | | | | ( 2) Check clogging in oil | | | |
then start operation. | | | | | | YES | |
| | | | | | | | recovery circuit of the oil separator. | | | Replace defective parts |
| | | | | | | | (Capillary, Strainer) | | | |
| | | | | | | | Check clogging of SV3D valve. | | | |
| | | | | | | | | | | | | |
Check oil level judgment | | | | | | | No clogging | | | |
of each compressor. | | | | | | | | | |
| | | | | | | | | | |
| | | | | | | | | | | | | |
| | SW01/02/03=1/16/1 | are | | | | | |
| | displayed on 7- | segment display. | | | | | |
| | | | | | | | | | | | |
Are all the oil levels appropriate? | | | | | | | | | | | |
| NO | | | | | | | | | |
| YES | | | | | | | Clogging | |
| | | | | | | |
| | | | | | | | |
Eliminate cause of accumulation. | | | | | | Check clogging of oil-equation circuit. | | | Replace defective parts |
| | | | | ( 3) | | | |
| | | | | | | |
| | | | | | | | | | | | | |
Indoor/outdoor PMV error
(Cause of refrigerant accumulation) Discharge check valve error, etc.
• Set up SW02 = [9], and turn on SV3A, SV3B, SV3C valves. (7-segment display [Hr] [ 3–]) |
• While outdoor unit is operating, check temperature change at secondary side of SV3B valve. (ƒ in the figure.) |
→ If temperature does not rise (equivalent to suction temperature), it is a clogging of SV3B valve. |
Replace SV3B valve. |
d) Clogging for SV3E valve |
Reset the power supply. |
ò
Referring to “Valve forced open/close function” of the outdoor unit, check ON/OFF operation (Sound, coil surface temp up) of SV3E valve is performed.
ò
Start test operation in COOL or HEAT mode.
ò
After operation for several minutes, check the pipe temperature at the secondary side of SV3E valve whether temperature changes or not. If it is equivalent to outside temperature, clogging of SV3E is considered.
(„ in the figure.)
(Reference)
If SV3E valve is clogged, temperature of all TK1, TK2, TK3, and TK4 do not change.
(*2) Clogging check for SV3D valve of oil return circuit from oil separator
a)Oil return circuit
•While outdoor unit is operating, check temperature (secondary side of capillary) on oil return circuit. (… in the figure.)
→If temperature is low equivalent to suction temperature), a clogging of strainer of oil return circuit or capillary is considered. Repair the clogged part.
b)Clogging check for SV3D valve
•While outdoor unit is operating, set up SW01/02/03 = [2] [1] [3] to 7-segment display [Hr] [ 2], and push SW04 for 2 seconds or more.
•Set up SW02 = [6], and turn on SV3D valve. (7-segment display [Hr] [ 3d])
•If temperature is low at secondary side of the valve or it does not change, clogging of valve, capillary, or strainer is considered. († in the figure.)
(Reference) If refrigerant is accumulated in the compressor case, oil level short may be judged.
Compact 4-Way Air Discharge Cassette Type
Contents
Safety Caution
Metal section Earth position
Check the following items after reinstallation
Catch the inner cables
Fire is caused at user’s side
Flare nut
Safety Caution Concerned to New Refrigerant
Pipe Materials
Piping
General tools Conventional tools can be used
R410A Conventional air Air conditioner installation
Conditioner installation
Tools
Cylinder with siphon
Recharge of Refrigerant
Environment
4mm-hexagonal wrench is required
Drain-up standing-up size
Space required for Installation and servicing
Wired remote
Construction Views External Views
Control P.C. board
Wiring Diagram
For Indoor unit
MCC-1402
Model
Parts Rating
Parts Rating
Name of Each Part
Display section
Parts Name of Remote Controller
Wind direction and Swing
Remote controller sensor
Operation section
Button
Stop
Turn on the main power switch and/or the leakage breaker
Correct Usage
Preparation
Automatic Operation Super Heat Recovery Type Only
When restarting the operation after stop
Start
To select SET Time
Timer Operation
Timer operation
Cancel of timer operation
How to stop swinging
Adjustment of Wind Direction
How to set up the air direction
How to start swinging
Information
Air Conditioner Operations and Performance
Standby
When the Following Symptoms are Found
Connect all of the installation wiring correctly
Precautions for Safety
New Refrigerant Air Conditioner Installation
To Disconnect the Appliance from Main Power Supply
Installable ceiling height list
Selection of Installation Place
Installation space
Installation space
Installation of Indoor Unit
Case of wireless type
Dimensional view
Installation of remote controller Sold separately
Ceiling opening and installation of hanging bolts
Installation of ceiling panel Sold separately
Installation of hanging bolt
Drain Piping Work
Permissible pipe length and permissible height difference
Piping material and dimensions
Refrigerant Piping
Thermal insulating process
Open fully valves of the outdoor unit Gas leak check
Electric Work
Connection of refrigerant pipe
Airtight test/Air purge, etc
Remote controller wiring *4
Power supply specifications
Indoor unit power supply *1
Indoor/Outdoor inter-unit wiring, Central controller wiring
Applicable Controls
Increased heating effect
Case of installation to high ceiling
Case of remote controller-less Group control
Change of lighting time of filter sign
Test RUN
How to execute test operation
Case of wireless remote controller
Case of wired remote controller
Confirmation and check Check method
Troubleshooting
Confirmation of error history
Check code list
Error detected by TCC-LINK central control device
Troubleshooting
Way Air Discharge Cassette Type
Maintenance
Daily maintenance
New check code
Functional part name Functional outline
Refrigerating Cycle Diagram
Control Outline
Control Specifications
Outline of specifications Remarks
Remote controller Control outline Command
Value
Reset conditions
TCB-AX21E
Central control mode 1 Cannot operate
Central control mode
Central control mode 4 Cannot select mode
Applied Control
Procedure Execute the setup operation while the unit stops
HEAT, Heat → Cool
Description At shipment
Applied Control in Indoor Unit
Indoor unit capacity
Remote location ON/OFF control box TCB-IFCB-4E
Operation
Ventilating fan control from remote controller
Wiring
Function
Leaving-ON prevention control
Power peak-cut from indoor unit
Using the setup temp
Button, set to the setup data
Troubleshooting procedure
Troubleshooting
Troubleshooting Summary
Before troubleshooting
Judging device
Check code list
Check Method
Auxiliary code
Sensor block display
MG-SW
Check code Outdoor 7-segment display Auxiliary code
Error detected by TCC-LINK central control device
Check code
Procedure Description
Troubleshooting by Check Display on Remote Controller
Case of wired remote controller RBC-AMT31E
Confirmation of error history
Case of central remote controller TCB-SC642TLE
Remote
Check code
Outdoor 7-segment display
Check code Auxiliary code
Convenient functions
Setup method of No. capacity-over Detection
Check code
Main Outdoor 7-segment display Remote
Detected
Main Outdoor 7-segment display
Check code Auxiliary code
Remote
Check item position
Remote Check code
Status Error detection condition Check item position
Detected Main
Position Remote
Check clogging of oil equation pipe between compressors
Check code Main Outdoor 7-segment display
H07
Check all the outdoor units in the corresponding line
H16
Check code Main Outdoor 7-segment display Remote
L30 Detected indoor address L31
P01 P03 P04
TS error judgment standard temperature
Name
Heating
Remote Check code Auxiliary code
Outdoor 7-segment display Check code name
Error detection condition Check item position
Central control
Outdoor 7-segment display Detected position
Device Check code
Display on
Measured position Criteria
How to check inverter output
How to check resistance of compressor winding
How to check the outdoor fan motor
E02
Diagnosis Procedure for Each Check Code
E03
E04
E07
E06 Decreased number of indoor units
E09 Duplicated master
E08
E12
E15
Reference
E16
E18
E19
E25
∗ 1 How to clear the error
E20
E23
F03
E31
F01
F02
F08 To sensor error
F04 TD1 sensor error
F05 TD2 sensor error
F06 TE1 sensor error
F23
F29 Indoor other error
F15 Outdoor temp sensor miscabling
TE1, TL
H03
F31
H02
H01
H06 Low-pressure protective operation
Leakage check for SV3C valve
Clogging for SV3E valve
Clogging check for SV3D valve
H08
Clogging check for oil-equalization circuit
TK3 temperature detective circuit error
Oil level detective circuit system error
L03
H16 TK4 temperature detective circuit error
L04
L05
L08
L07 Group line in individual indoor unit
L10
L17
L28
L18
L29
L20
L31
P01 Indoor fan motor error
L30 Interlock in indoor unit
P03
Auxiliary code Compressor 1 side
P05 Open phase, negative phase
P04 Actuation
High-pressure SW
P12
P07 Heat sink overheat error
P10 Indoor overflow error
Indoor fan motor error
TS condition Auxiliary code
P13 Outdoor liquid back detection error 1. PMV1/PMV2 error
P15
Gas leak detection
TD condition Auxiliary code
Discharge temp TD2 error
P15 Gas leak detection
P17
P19 Way valve operation error
P20 High-pressure protective operation
Judgment criteria
Auxiliary code 0 ∗
P22 Outdoor fan Ipdu error
P31
P26 Tr short-circuit protection error
Detective circuit error
P29
Segment display on the outdoor unit Interface P.C. board
Check procedure in case of stop with trouble
How to read the check monitor Segment display
Segment Display Function
SW01 SW02 SW03 Display contents
There is auxiliary code Check code ∗ ∗ ∗ for 3 seconds
SW03 SW02 Indoor address Segment display a
Data display of outdoor cycle Displayed on each outdoor unit
Segment display A, B
Sensor Characteristics
Temperature sensor characteristics
W01 SW02 SW03 Display contents Segment display
Indoor Unit
Configuration of Control Circuit
Wired remote controller Up to 2 units
Weekly timer
Connection of wireless remote controller
Kit
Compact 4-way Air Discharge Cassette Type
Compact4-way Air Discharge Connection of both remote
Wireless
Cassette Type Controller
Remote
Cassette
Air Discharge
Type
MCC-1402 Compact 4-way
Function Connector Pin Specifications Remarks
Optional Connector Specifications of Indoor P.C. Board
Attachment
Part name Procedure Remarks
Detachments
Preparing work
100
101
No. Part name Procedure Remarks
102
Bell mouth 1. Detachment
No. Part name Procedure
103
Fan guard 1. Detachment
Fan motor 1. Detachment
104
Drain pump 1. Detachment
105
Details of a part
Details of sensor lead wire drawing
106
Arrow view B
Exchanger Recover refrigerant gas
107
Heat
108
10. P.C. Board Exchange Procedures
Exchange of P.C. Board for Indoor Service
Exchange procedure
Remote controller operation diagram
Procedure 1 Readout setup contents from Eeprom
110
Procedure 2 Exchange of P.C. board for service
Eeprom layout
Procedure 3 Writing-in of setup contents to Eeprom
Make a note of the setup contents. Item code list Example
Description
Exploded Views and Parts List
Ceiling Panel
113
114
Compact 4-way Air Discharge Cassette Type
MMU-AP0071MH, AP0091MH, AP0121MH, AP0151MH, AP0181MH
211
115
Description Remarks Model Name
0071MH 0091MH 0121MH 0151MH 0181MH
Description Model Name
116
Toshiba Carrier Corporation