Toshiba MMU-AP0151MH P19 Way valve operation error, P20 High-pressure protective operation

Page 86

Check code name

Check code name

Cause of operation

[P19]

4-way valve operation error

1.

4-way valve error

 

 

2.

TS1 sensor/TE1 sensor error

 

 

3.

Pd sensor/Ps sensor error

 

 

4.

TE sensor/TL sensor misconnection

Check code name

Check code name

Cause of operation

[P20]

High-pressure protective operation 1.

Pd sensor error

 

2.

Service valve closed.

 

3.

Indoor/outdoor fan error

 

4.

Indoor/outdoor PMV clogging

 

5.

Indoor/outdoor heat exchanger clogging

 

6.

SV2 circuit error

Auxiliary code : Detected outdoor unit No.

Is 4-way valve coil

NO

connector connected?

 

 

YES

 

 

 

 

 

 

Correct connector connection.

(4-way valve coil: CN317)

Correct connector connection.

7.

SV4 circuit error

8.

SV5 circuit error

9.

Outdoor I/F P.C. board error

10.

Operation error of check valve of main

 

discharge pipe

11.

Refrigerant overcharge

Are TS1, TE1, Pd, Ps sensor

NO

connectors connected?

 

 

 

YES

 

 

 

 

 

 

 

NO

Are characteristics of resistance value

 

of TS1 and TE1 sensors normal?

 

 

 

YES

 

 

 

 

 

 

 

NO

Are output voltage characteristics

 

of Pd and Ps sensors normal?

 

86

 

YES

 

 

 

 

 

NO

 

 

Are connection and installation

 

of TE1 and TL sensors correct?

 

TS1 sensor: CN504

TE1 sensor: CN505 Pd sensor: CN501 Ps sensor: CN500

Replace sensor.

Replace sensor.

Correct connection

and installation.

Are service valves fully opened?

YES

Are characteristics of

high-pressure sensor normal?

YES

Check mispiping of discharge gas/

suction gas main pipes.

Normal

Check operation of PMV3 SV12.

Normal

Is the flow selector unit normal?

Normal

Reset power supply, and start a test operation corresponded to the season.

NO

NO

Abnormal

Abnormal

Abnormal

All cooling operation

To

B

All heating operation

To

C

Open service valves fully.

Check parts.

Failure Replace

Correct piping.

Replace defective parts.

Repair the flow selector unit.

YES

B All cooling operation

1. Pressure by pressure gauge (Check joint)

2.

Pressure display on 7-segment display

3.

Output voltage of I/F P.C. board

 

If 1 and 2, 3 are different, an error of pressure sensor is considered.

Reset the power supply and start heating test operation.

Does cooling outdoor fan normally operate?

YES

Is there no fan crack or coming-off?

If 2 and 3 are different, check I/F P.C. board.

NO

Correct faulty parts.

YES

Correct faulty parts.

Is the flow selector unit normal?

YES

Does 4-way valve operate?

NO

4-way valve error

NO

YES

Does not discharge

NO

refrigerant gas bypass to

 

 

 

 

 

suction side through

 

 

 

4-way valve?

*1

 

YES

Check 4-way valve.

Replace the FS unit.

If an error did not occur in test operation, restart the operation.

NO

Is outdoor PMV1, 2 normal?

YES

Is there a cause to interfere operation of heat exchanger of outdoor unit?

1.Heat exchanger clogging

2.Air short circuit

NO

Is SV2 circuit normal?

YES

Is SV4 circuit normal?

(Connector connection, fan IPDU, fan motor, wiring)

NO

Correct faulty position.

(Connector connection wiring, coil mounting, valve clogging, etc)

YES

Eliminate the interfered causes.

NO

Repair SV2 circuit.

(Coil error, clogging, disconnection of cable, etc.)

NO

Repair SV4 circuit.

*1 Check TS and TE temperature of the outdoor unit which compressors is operated.

(I/F) SW01=[1], SW02=[6], SW03=[2]

TS sensor temperature

SW01=[1], SW02=[7], SW03=[2]

ÆTE sensor temperature

<Judgment criteria>

TE sensor: Normal if TE 20˚C except summer season (Outside temp 20˚C or lower)

TS sensor: Normal if TS 40˚C except summer season (Outside temp 20˚C or lower)

YES

Does check valve of main

discharge pipe normally operate?

YES

Refrigerant overcharge, clogging, pipe breakage, abnormal overload condition

(Coil error, clogging, disconnection of cable, etc.)

NO

Repair check valve. Replace

Image 86
Contents Compact 4-Way Air Discharge Cassette Type Contents Safety Caution Fire is caused at user’s side Check the following items after reinstallationCatch the inner cables Metal section Earth positionPiping Safety Caution Concerned to New RefrigerantPipe Materials Flare nutTools R410A Conventional air Air conditioner installationConditioner installation General tools Conventional tools can be used4mm-hexagonal wrench is required Recharge of RefrigerantEnvironment Cylinder with siphonConstruction Views External Views Space required for Installation and servicingWired remote Drain-up standing-up sizeMCC-1402 Wiring DiagramFor Indoor unit Control P.C. boardName of Each Part Parts RatingParts Rating ModelParts Name of Remote Controller Display sectionButton Remote controller sensorOperation section Wind direction and SwingPreparation Turn on the main power switch and/or the leakage breakerCorrect Usage StopStart Automatic Operation Super Heat Recovery Type OnlyWhen restarting the operation after stop Cancel of timer operation Timer OperationTimer operation To select SET TimeHow to start swinging Adjustment of Wind DirectionHow to set up the air direction How to stop swingingInformation Air Conditioner Operations and Performance When the Following Symptoms are Found StandbyTo Disconnect the Appliance from Main Power Supply Precautions for SafetyNew Refrigerant Air Conditioner Installation Connect all of the installation wiring correctlyInstallation space Selection of Installation PlaceInstallation space Installable ceiling height listDimensional view Installation of Indoor UnitCase of wireless type Installation of hanging bolt Ceiling opening and installation of hanging boltsInstallation of ceiling panel Sold separately Installation of remote controller Sold separatelyDrain Piping Work Thermal insulating process Piping material and dimensionsRefrigerant Piping Permissible pipe length and permissible height differenceAirtight test/Air purge, etc Electric WorkConnection of refrigerant pipe Open fully valves of the outdoor unit Gas leak checkIndoor/Outdoor inter-unit wiring, Central controller wiring Power supply specificationsIndoor unit power supply *1 Remote controller wiring *4Applicable Controls Change of lighting time of filter sign Case of installation to high ceilingCase of remote controller-less Group control Increased heating effectCase of wired remote controller How to execute test operationCase of wireless remote controller Test RUNCheck code list TroubleshootingConfirmation of error history Confirmation and check Check methodTroubleshooting Error detected by TCC-LINK central control deviceNew check code MaintenanceDaily maintenance Way Air Discharge Cassette TypeRefrigerating Cycle Diagram Functional part name Functional outlineRemote controller Control outline Command Control SpecificationsOutline of specifications Remarks Control OutlineReset conditions ValueTCB-AX21E Central control mode 4 Cannot select mode Central control mode 1 Cannot operateCentral control mode Procedure Execute the setup operation while the unit stops Applied ControlDescription At shipment HEAT, Heat → CoolRemote location ON/OFF control box TCB-IFCB-4E Applied Control in Indoor UnitIndoor unit capacity Function Ventilating fan control from remote controllerWiring OperationButton, set to the setup data Power peak-cut from indoor unitUsing the setup temp Leaving-ON prevention controlBefore troubleshooting TroubleshootingTroubleshooting Summary Troubleshooting procedureAuxiliary code Check code listCheck Method Judging deviceMG-SW Sensor block displayError detected by TCC-LINK central control device Check code Outdoor 7-segment display Auxiliary codeCheck code Confirmation of error history Troubleshooting by Check Display on Remote ControllerCase of wired remote controller RBC-AMT31E Procedure DescriptionCase of central remote controller TCB-SC642TLE Check code Auxiliary code Check codeOutdoor 7-segment display RemoteMain Outdoor 7-segment display Remote Setup method of No. capacity-over DetectionCheck code Convenient functionsRemote Main Outdoor 7-segment displayCheck code Auxiliary code DetectedRemote Check code Check item positionPosition Remote Status Error detection condition Check item positionDetected Main Check all the outdoor units in the corresponding line Check code Main Outdoor 7-segment displayH07 Check clogging of oil equation pipe between compressorsCheck code Main Outdoor 7-segment display Remote H16L30 Detected indoor address L31 P01 P03 P04 Heating TS error judgment standard temperatureName Remote Check code Auxiliary code Error detection condition Check item position Outdoor 7-segment display Check code nameDisplay on Outdoor 7-segment display Detected positionDevice Check code Central controlHow to check the outdoor fan motor How to check inverter outputHow to check resistance of compressor winding Measured position CriteriaE04 Diagnosis Procedure for Each Check CodeE03 E02E06 Decreased number of indoor units E07E15 E08E12 E09 Duplicated masterE19 E16E18 ReferenceE23 ∗ 1 How to clear the errorE20 E25F02 E31F01 F03F06 TE1 sensor error F04 TD1 sensor errorF05 TD2 sensor error F08 To sensor errorTE1, TL F29 Indoor other errorF15 Outdoor temp sensor miscabling F23H01 F31H02 H03H06 Low-pressure protective operation Clogging check for SV3D valve Leakage check for SV3C valveClogging for SV3E valve Clogging check for oil-equalization circuit H08Oil level detective circuit system error TK3 temperature detective circuit errorL05 H16 TK4 temperature detective circuit errorL04 L03L17 L07 Group line in individual indoor unitL10 L08L20 L18L29 L28P03 P01 Indoor fan motor errorL30 Interlock in indoor unit L31High-pressure SW P05 Open phase, negative phaseP04 Actuation Auxiliary code Compressor 1 sideIndoor fan motor error P07 Heat sink overheat errorP10 Indoor overflow error P12Gas leak detection P13 Outdoor liquid back detection error 1. PMV1/PMV2 errorP15 TS condition Auxiliary codeP17 Discharge temp TD2 errorP15 Gas leak detection TD condition Auxiliary codeJudgment criteria P19 Way valve operation errorP20 High-pressure protective operation P22 Outdoor fan Ipdu error Auxiliary code 0 ∗P29 P26 Tr short-circuit protection errorDetective circuit error P31Segment Display Function Check procedure in case of stop with troubleHow to read the check monitor Segment display Segment display on the outdoor unit Interface P.C. boardSW01 SW02 SW03 Display contents There is auxiliary code Check code ∗ ∗ ∗ for 3 seconds Data display of outdoor cycle Displayed on each outdoor unit SW03 SW02 Indoor address Segment display aW01 SW02 SW03 Display contents Segment display Sensor CharacteristicsTemperature sensor characteristics Segment display A, BWeekly timer Configuration of Control CircuitWired remote controller Up to 2 units Indoor UnitCompact 4-way Air Discharge Cassette Type Connection of wireless remote controllerKit Remote WirelessCassette Type Controller Compact4-way Air Discharge Connection of both remoteMCC-1402 Compact 4-way Air DischargeType CassetteOptional Connector Specifications of Indoor P.C. Board Function Connector Pin Specifications RemarksPreparing work Part name Procedure RemarksDetachments Attachment100 No. Part name Procedure Remarks 101102 Fan guard 1. Detachment No. Part name Procedure103 Bell mouth 1. Detachment104 Fan motor 1. Detachment105 Drain pump 1. DetachmentArrow view B Details of sensor lead wire drawing106 Details of a partHeat Exchanger Recover refrigerant gas107 Exchange procedure 10. P.C. Board Exchange ProceduresExchange of P.C. Board for Indoor Service 108Procedure 1 Readout setup contents from Eeprom Remote controller operation diagramProcedure 2 Exchange of P.C. board for service 110Procedure 3 Writing-in of setup contents to Eeprom Eeprom layoutMake a note of the setup contents. Item code list Example 113 Exploded Views and Parts ListCeiling Panel Description211 Compact 4-way Air Discharge Cassette TypeMMU-AP0071MH, AP0091MH, AP0121MH, AP0151MH, AP0181MH 1140071MH 0091MH 0121MH 0151MH 0181MH 115Description Remarks Model Name 116 Description Model NameToshiba Carrier Corporation

MMU-AP0181MH, MMU-AP0071MH, MMU-AP0091MH, MMU-AP0151MH, MMU-AP0121MH specifications

The Toshiba MMU-AP series, consisting of models MMU-AP0121MH, MMU-AP0151MH, MMU-AP0091MH, MMU-AP0071MH, and MMU-AP0181MH, represents a significant advancement in the realm of power management and energy efficiency for a variety of applications. These modules are designed to optimize performance while ensuring minimal energy consumption, making them suitable for both commercial and industrial uses.

One of the standout features of the MMU-AP series is its intelligent power management technology. This feature allows for adaptive energy distribution based on real-time demands. By leveraging precise control algorithms, the modules can adjust their output to match the specific requirements of connected devices, ultimately leading to reduced power loss and increased efficiency. This adaptability not only benefits end-users by lowering operational costs but also contributes to a greener environment by minimizing waste.

The versatility of the MMU-AP series is evident in its wide range of operational capabilities. These power modules are designed to work effectively in various voltage levels and load conditions. With input voltage ranges suitable for standard industrial environments, they can easily be integrated into existing systems, enhancing overall functionality without requiring extensive modifications.

Moreover, the compact design of the MMU-AP modules is another notable characteristic. Their size and light weight facilitate easier installation and integration into tight spaces, making them ideal for applications where real estate is a premium. This compact profile does not compromise performance, as these modules are engineered to deliver robust power output while maintaining thermal efficiency.

In terms of reliability, the MMU-AP series is built with high-grade components that withstand harsh operating conditions. With features such as over-voltage protection, short-circuit protection, and thermal shutdown capabilities, users can trust that their equipment would operate safely and efficiently, thereby extending the lifespan of both the power modules and the devices they serve.

Finally, Toshiba’s commitment to innovation ensures that the MMU-AP series incorporates cutting-edge technology. The series supports communication protocols that enable seamless integration with smart systems, paving the way for advanced monitoring and control functions. This levels up the user experience, providing insights into performance and diagnostics that are crucial for uptime and reliability in demanding environments.

In conclusion, the Toshiba MMU-AP series offers a blend of efficiency, adaptability, and advanced technology, making it a valuable asset for various industrial and commercial applications. Its intelligent design and robust features ensure that users can optimize energy use while maintaining high performance and reliability.