| Check code | |
Main | Outdoor | ||
remote |
|
| |
Check code | Auxiliary code | ||
controller | |||
|
|
| |
E12 | E12 | 01: Indoor/outdoor communication | |
|
| 02: Between outdoors communication | |
|
|
| |
E15 | E15 | — | |
|
|
| |
E16 | E16 | 00: Capacity over | |
|
| 01 to: No. of connected units |
52 | E18 | — | — |
| |||
|
|
|
|
| E19 | E19 | 00: No header unit |
|
|
| 02: Two or more header units |
|
|
|
|
| E20 | E20 | 01: Connection of outdoor of other line |
|
|
| 02: Connection of indoor of other line |
|
|
|
|
| E23 | E23 | — |
|
|
|
|
| E25 | E25 | — |
|
|
|
|
| E26 | E26 | No. of normally received outdoor units |
|
|
|
|
| E28 | E28 | No. of detected outdoor units |
Detected | Check code name | Status |
| Error detection condition |
|
| Check item (position) | ||
position |
|
|
| ||||||
|
|
|
|
|
|
|
|
| |
I/F | Automatic address | All stop | • | When indoor automatic address started, |
| • | Setup the address again after disconnecting communication | ||
| start error |
|
| other refrigerant circuit system was setting |
|
| connection with other refrigerant circuit system. | ||
|
|
|
| automatic address. |
|
|
|
| |
|
|
| • | When outdoor automatic address started, |
|
|
|
| |
|
|
|
| indoor automatic address was executed. |
|
|
|
| |
I/F | No corresponding | All stop | Indoor unit is not found when indoor automatic |
| • Check the communication line connection between indoor and outdoor. | ||||
| indoor unit during |
| address start was set up. |
| • | Check the electric power line error in indoor. | |||
| automatic address |
|
|
|
|
| • | Check the noise of surrounding devices. | |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| • | Power failure | |
|
|
|
|
|
|
| • Check indoor P.C. board error. | ||
I/F | No. of connected | All stop | • | Total capacity of indoor units exceeded |
| • | Check the connection capacity of indoor unit. | ||
| indoor units / |
|
| 135% of total outdoor capacity. |
| • | Check the HP capacity of indoor unit. | ||
| Capacity over |
| • No. of connected indoor units are more than |
| • | Check the indoor/outdoor capacity setup | |||
|
|
|
| 48 units. |
| • Check the No. of connected indoor units. | |||
|
|
| [Note] |
| |||||
|
|
|
| • | Check the outdoor I/F P.C. board error | ||||
|
|
| If this code appears after backup setup of |
| |||||
|
|
|
|
|
|
| |||
|
|
| outdoor unit trouble, set up “No. |
|
|
|
| ||
|
|
| detection”. |
|
|
|
| ||
|
|
| <Setup method of “No. |
|
|
|
| ||
|
|
| detection”> |
|
|
|
| ||
|
|
| Turn on SW09/Bit 2 on I/F P.C. board of |
|
|
|
| ||
|
|
| outdoor header unit. |
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
Indoor | Communication error | Corresponding | Regular communication between indoor |
| • | Check cable of the remote controller. | |||
unit | between indoor header | unit only stops. | header and follower units |
| • | Check power cabling of indoor. | |||
| and follower units |
|
|
|
|
| • Check P.C. board of indoor. | ||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| |
I/F | Outdoor unit quantity | All stop | • | There are multiple outdoor units in 1 line. |
| The outdoor unit connected with communication cable between | |||
| error |
| • | There is none of outdoor unit in 1 line. |
| indoor and outdoor (U1.U2) is the outdoor unit. | |||
|
|
|
|
|
|
| • | Check connection of communication line between indoor and outdoor. | |
|
|
|
|
|
|
| • Check outdoor P.C. board(I/F) error. | ||
|
|
|
|
|
|
|
| ||
I/F | Other line unit | All stop | Unit of other line was connected when indoor |
| Separate the cable between lines according to automatic address | ||||
| connected during |
| automatic address started. |
| setup method in “Address setup”. | ||||
| automatic address |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
I/F | Communication | All stop | Transmission of other outdoor unit was |
| In this model, only one outdoor unit is provided to one refrigerant line. | ||||
| sending error between |
| unavailable for 30 seconds or more. |
| Be sure to check there is no communication connection with outdoor | ||||
| outdoor units |
|
|
|
|
| unit in the other refrigerant line. | ||
|
|
|
|
|
|
|
| ||
I/F | Duplicated outdoor | All stop | Outdoor addresses manually set up are |
| Note) | ||||
| follower address setup |
| duplicated. |
| Do not set up the outdoor address manually. | ||||
|
|
|
|
|
|
|
| ||
I/F | Decreased number of | All stop | The signal was not returned for constant from |
| In this model, only one outdoor unit is provided to one refrigerant line. | ||||
| connected outdoor |
| the outdoor unit which was receiving signal. |
| Be sure to check there is no communication connection with outdoor | ||||
| units |
|
|
|
|
| unit in the other refrigerant line. | ||
|
|
|
|
|
|
|
|
| |
I/F | Outdoor follower unit | All stop | Outdoor header unit received error code from |
| • | Check the check code of outdoor follower unit. | |||
| error |
| outdoor follower unit. |
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| <Convenient functions> |
| ||
|
|
|
|
|
|
| is displayed on | ||
|
|
|
| When pushing SW04 for 1 second or more under condition that [E28] | |||||
|
|
|
| outdoor header unit, the fan of outdoor unit which stopped abnormally starts rotating. | |||||
|
|
|
| If pushing SW04 and SW05 simultaneously, the fan of normal outdoor unit operates. | |||||
|
|
|
| When pushing SW05 singly, the operation of fan is cleared. | |||||
|
|
|
|
|
|
|
|
|
|