Toshiba MMU-AP0091MH Installation of Indoor Unit, Case of wireless type, Dimensional view

Page 22

2 SELECTION OF INSTALLATION PLACE

In case of wireless type

The wireless remote controller can be operated up to a maximum of 8 m from the infra-red receiver.

Therefore ensure that the remote controller will be mounted and used within this stated parameter.

To prevent malfunction do not mount or operate in a location that is subjected to either a fluorescent lamp or direct sunlight.

A maximum of 6 indoor units with wireless remote controller can be installed within the same room.

3 INSTALLATION OF INDOOR UNIT

22

WARNING

The installation of the air conditioning unit must be positioned in a location that can sufficiently support its weight

 

and give protection against adverse environmental conditions.

Failure to do so may result in unit damage and possible human injury.

Any incomplete installation may also cause possible risk of human injury.

Unpack the package, take out the product and then place it on the floor so that the same surface directs underneath as it is placed in the package.

Never put the products taken out from the packing box in a

pile, or put other load on them; otherwise there is a

OK

NO GOOD

possibility to damage electric parts, fan parts, draining

 

 

mechanism, and etc.

 

 

If the both sides are turned over, a deformation of mounting metal of the ceiling panel which is sold separately, etc may be caused. Accordingly the product may be damaged and the installation becomes impossible in some cases.

REQUIREMENT

Strictly comply to the following rules to prevent damage of the indoor units and human injury.

Do not place heavy objects on the indoor unit. (Even when units are still packaged)

Always carry the unit as packaged from the factory wherever possible.

If carrying in the indoor unit unpacked by necessity, be sure to use buffering cloth, etc. to prevent damaging the unit.

To move the indoor unit, hold the hanging brackets (4 positions) only.

Do not apply force to other parts (refrigerant pipe, drain pan, foamed parts, or resin parts etc.).

• To be carried by two or more persons. Do not strap the unit in positions other than that stated.

Dimensional view

 

1000 or more

1000 or more

595 to 660 Ceiling open dimension

15 or more

 

 

Obstacle

 

1000 or more

15 or more

Space required for

installation and servicing

207

175

149

 

 

 

 

 

 

64

29

142

64

368.5

 

Knockout for 100 diameter

 

fresh air intake

 

145.5

Bottom face

700 Panel external dimension

93

595 to 660 Ceiling open dimension

of ceiling

 

 

 

525 Hanging bolt pitch

 

 

 

105

70

 

 

 

235

dimension

 

 

105

external

 

 

235

575 Unit

 

Ø162

 

 

4 screw holes

Electric parts box

320.5

 

 

(For 4 mm tapping screw)

 

For 150 diameter

575 Unit external dimension

 

 

branch duct knockout

 

 

square hole

 

 

Bottom face of ceiling

 

 

 

 

 

 

 

200

 

 

 

 

 

Check port

 

 

dimension

 

200

(

 

450)

 

200

Check port

 

 

 

 

 

 

(o450)

 

 

 

Check port

 

 

 

 

 

 

 

(

450)

 

Ceiling660open

 

Drain-up standing-up size

 

 

300 or less

Stand-up

627.5

lessor

up-Stand

lessor850

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling

 

 

 

 

to

Note)

 

 

 

 

 

 

 

595

 

 

 

 

 

 

 

As ABS is used for the drain discharge port of the main unit,

 

the vinyl chloride paste cannot be used.

 

Use the flexible hose (Band fix) included in the package.

 

 

 

4

2.7

 

 

Wired remote

 

 

 

120

 

 

controller

 

 

 

 

 

(RBC-AMT31E)

 

 

 

 

 

 

 

 

120

 

16

 

 

 

 

 

 

 

 

 

268

27

 

 

 

220.5

 

 

 

Drain discharge port

145.5

 

 

 

Hanging bolt

 

 

134

 

Bottom face

 

 

 

 

of ceiling

 

M10 or W3/8

 

 

63

 

 

local arrange

 

 

Ceiling panel

 

 

 

 

 

Hanging525bolt pitch Ceiling660to595open dimension externalPanel700 dimension

105214 256

 

 

177

14842

 

21120

158142

 

 

 

Ø162

 

 

 

 

Refrigerant pipe

97.5

 

Wiring connection

 

 

 

 

 

55

port

 

 

(Liquid) Ø6.4

 

 

 

 

 

 

 

 

For 150 diameter 70 105 93

branch duct

 

 

 

 

 

 

 

 

139.5

knockout square hole

 

 

 

 

 

Refrigerant pipe (Gas)

190.5

0151, 0181MH : Ø12.7

 

 

 

 

0071 to 0121MH : Ø9.5

 

 

 

 

Image 22
Contents Compact 4-Way Air Discharge Cassette Type Contents Safety Caution Fire is caused at user’s side Check the following items after reinstallationCatch the inner cables Metal section Earth positionPiping Safety Caution Concerned to New RefrigerantPipe Materials Flare nutTools R410A Conventional air Air conditioner installationConditioner installation General tools Conventional tools can be used4mm-hexagonal wrench is required Recharge of RefrigerantEnvironment Cylinder with siphonConstruction Views External Views Space required for Installation and servicingWired remote Drain-up standing-up sizeMCC-1402 Wiring DiagramFor Indoor unit Control P.C. boardName of Each Part Parts RatingParts Rating ModelParts Name of Remote Controller Display sectionButton Remote controller sensorOperation section Wind direction and SwingPreparation Turn on the main power switch and/or the leakage breakerCorrect Usage StopWhen restarting the operation after stop Automatic Operation Super Heat Recovery Type OnlyStart Cancel of timer operation Timer OperationTimer operation To select SET TimeHow to start swinging Adjustment of Wind DirectionHow to set up the air direction How to stop swingingInformation Air Conditioner Operations and Performance When the Following Symptoms are Found StandbyTo Disconnect the Appliance from Main Power Supply Precautions for SafetyNew Refrigerant Air Conditioner Installation Connect all of the installation wiring correctlyInstallation space Selection of Installation PlaceInstallation space Installable ceiling height listCase of wireless type Installation of Indoor UnitDimensional view Installation of hanging bolt Ceiling opening and installation of hanging boltsInstallation of ceiling panel Sold separately Installation of remote controller Sold separatelyDrain Piping Work Thermal insulating process Piping material and dimensionsRefrigerant Piping Permissible pipe length and permissible height differenceAirtight test/Air purge, etc Electric WorkConnection of refrigerant pipe Open fully valves of the outdoor unit Gas leak checkIndoor/Outdoor inter-unit wiring, Central controller wiring Power supply specificationsIndoor unit power supply *1 Remote controller wiring *4Applicable Controls Change of lighting time of filter sign Case of installation to high ceilingCase of remote controller-less Group control Increased heating effectCase of wired remote controller How to execute test operationCase of wireless remote controller Test RUNCheck code list TroubleshootingConfirmation of error history Confirmation and check Check methodTroubleshooting Error detected by TCC-LINK central control deviceNew check code MaintenanceDaily maintenance Way Air Discharge Cassette TypeRefrigerating Cycle Diagram Functional part name Functional outlineRemote controller Control outline Command Control SpecificationsOutline of specifications Remarks Control OutlineReset conditions ValueTCB-AX21E Central control mode Central control mode 1 Cannot operateCentral control mode 4 Cannot select mode Procedure Execute the setup operation while the unit stops Applied ControlDescription At shipment HEAT, Heat → CoolIndoor unit capacity Applied Control in Indoor UnitRemote location ON/OFF control box TCB-IFCB-4E Function Ventilating fan control from remote controllerWiring OperationButton, set to the setup data Power peak-cut from indoor unitUsing the setup temp Leaving-ON prevention controlBefore troubleshooting TroubleshootingTroubleshooting Summary Troubleshooting procedureAuxiliary code Check code listCheck Method Judging deviceMG-SW Sensor block displayError detected by TCC-LINK central control device Check code Outdoor 7-segment display Auxiliary codeCheck code Confirmation of error history Troubleshooting by Check Display on Remote ControllerCase of wired remote controller RBC-AMT31E Procedure DescriptionCase of central remote controller TCB-SC642TLE Check code Auxiliary code Check codeOutdoor 7-segment display RemoteMain Outdoor 7-segment display Remote Setup method of No. capacity-over DetectionCheck code Convenient functionsRemote Main Outdoor 7-segment displayCheck code Auxiliary code DetectedRemote Check code Check item positionDetected Main Status Error detection condition Check item positionPosition Remote Check all the outdoor units in the corresponding line Check code Main Outdoor 7-segment displayH07 Check clogging of oil equation pipe between compressorsCheck code Main Outdoor 7-segment display Remote H16L30 Detected indoor address L31 P01 P03 P04 Name TS error judgment standard temperatureHeating Remote Check code Auxiliary code Error detection condition Check item position Outdoor 7-segment display Check code nameDisplay on Outdoor 7-segment display Detected positionDevice Check code Central controlHow to check the outdoor fan motor How to check inverter outputHow to check resistance of compressor winding Measured position CriteriaE04 Diagnosis Procedure for Each Check CodeE03 E02E06 Decreased number of indoor units E07E15 E08E12 E09 Duplicated masterE19 E16E18 ReferenceE23 ∗ 1 How to clear the errorE20 E25F02 E31F01 F03F06 TE1 sensor error F04 TD1 sensor errorF05 TD2 sensor error F08 To sensor errorTE1, TL F29 Indoor other errorF15 Outdoor temp sensor miscabling F23H01 F31H02 H03H06 Low-pressure protective operation Clogging for SV3E valve Leakage check for SV3C valveClogging check for SV3D valve Clogging check for oil-equalization circuit H08Oil level detective circuit system error TK3 temperature detective circuit errorL05 H16 TK4 temperature detective circuit errorL04 L03L17 L07 Group line in individual indoor unitL10 L08L20 L18L29 L28P03 P01 Indoor fan motor errorL30 Interlock in indoor unit L31High-pressure SW P05 Open phase, negative phaseP04 Actuation Auxiliary code Compressor 1 sideIndoor fan motor error P07 Heat sink overheat errorP10 Indoor overflow error P12Gas leak detection P13 Outdoor liquid back detection error 1. PMV1/PMV2 errorP15 TS condition Auxiliary codeP17 Discharge temp TD2 errorP15 Gas leak detection TD condition Auxiliary codeP20 High-pressure protective operation P19 Way valve operation errorJudgment criteria P22 Outdoor fan Ipdu error Auxiliary code 0 ∗P29 P26 Tr short-circuit protection errorDetective circuit error P31Segment Display Function Check procedure in case of stop with troubleHow to read the check monitor Segment display Segment display on the outdoor unit Interface P.C. boardSW01 SW02 SW03 Display contents There is auxiliary code Check code ∗ ∗ ∗ for 3 seconds Data display of outdoor cycle Displayed on each outdoor unit SW03 SW02 Indoor address Segment display aW01 SW02 SW03 Display contents Segment display Sensor CharacteristicsTemperature sensor characteristics Segment display A, BWeekly timer Configuration of Control CircuitWired remote controller Up to 2 units Indoor UnitKit Connection of wireless remote controllerCompact 4-way Air Discharge Cassette Type Remote WirelessCassette Type Controller Compact4-way Air Discharge Connection of both remoteMCC-1402 Compact 4-way Air DischargeType CassetteOptional Connector Specifications of Indoor P.C. Board Function Connector Pin Specifications RemarksPreparing work Part name Procedure RemarksDetachments Attachment100 No. Part name Procedure Remarks 101102 Fan guard 1. Detachment No. Part name Procedure103 Bell mouth 1. Detachment104 Fan motor 1. Detachment105 Drain pump 1. DetachmentArrow view B Details of sensor lead wire drawing106 Details of a part107 Exchanger Recover refrigerant gasHeat Exchange procedure 10. P.C. Board Exchange ProceduresExchange of P.C. Board for Indoor Service 108Procedure 1 Readout setup contents from Eeprom Remote controller operation diagramProcedure 2 Exchange of P.C. board for service 110Procedure 3 Writing-in of setup contents to Eeprom Eeprom layoutMake a note of the setup contents. Item code list Example 113 Exploded Views and Parts ListCeiling Panel Description211 Compact 4-way Air Discharge Cassette TypeMMU-AP0071MH, AP0091MH, AP0121MH, AP0151MH, AP0181MH 114Description Remarks Model Name 1150071MH 0091MH 0121MH 0151MH 0181MH 116 Description Model NameToshiba Carrier Corporation

MMU-AP0181MH, MMU-AP0071MH, MMU-AP0091MH, MMU-AP0151MH, MMU-AP0121MH specifications

The Toshiba MMU-AP series, consisting of models MMU-AP0121MH, MMU-AP0151MH, MMU-AP0091MH, MMU-AP0071MH, and MMU-AP0181MH, represents a significant advancement in the realm of power management and energy efficiency for a variety of applications. These modules are designed to optimize performance while ensuring minimal energy consumption, making them suitable for both commercial and industrial uses.

One of the standout features of the MMU-AP series is its intelligent power management technology. This feature allows for adaptive energy distribution based on real-time demands. By leveraging precise control algorithms, the modules can adjust their output to match the specific requirements of connected devices, ultimately leading to reduced power loss and increased efficiency. This adaptability not only benefits end-users by lowering operational costs but also contributes to a greener environment by minimizing waste.

The versatility of the MMU-AP series is evident in its wide range of operational capabilities. These power modules are designed to work effectively in various voltage levels and load conditions. With input voltage ranges suitable for standard industrial environments, they can easily be integrated into existing systems, enhancing overall functionality without requiring extensive modifications.

Moreover, the compact design of the MMU-AP modules is another notable characteristic. Their size and light weight facilitate easier installation and integration into tight spaces, making them ideal for applications where real estate is a premium. This compact profile does not compromise performance, as these modules are engineered to deliver robust power output while maintaining thermal efficiency.

In terms of reliability, the MMU-AP series is built with high-grade components that withstand harsh operating conditions. With features such as over-voltage protection, short-circuit protection, and thermal shutdown capabilities, users can trust that their equipment would operate safely and efficiently, thereby extending the lifespan of both the power modules and the devices they serve.

Finally, Toshiba’s commitment to innovation ensures that the MMU-AP series incorporates cutting-edge technology. The series supports communication protocols that enable seamless integration with smart systems, paving the way for advanced monitoring and control functions. This levels up the user experience, providing insights into performance and diagnostics that are crucial for uptime and reliability in demanding environments.

In conclusion, the Toshiba MMU-AP series offers a blend of efficiency, adaptability, and advanced technology, making it a valuable asset for various industrial and commercial applications. Its intelligent design and robust features ensure that users can optimize energy use while maintaining high performance and reliability.