Toshiba MMU-AP0151MH Troubleshooting, Confirmation and check Check method, Check code list

Page 31

9 TROUBLESHOOTING

Confirmation and check

Check method

When a fault occurs in the air conditioner, the check code and the indoor unit No. will appear on the display part of the remote controller.

The check code will only be displayed while the unit is in operation.

If the display disappears, operate the air conditioner according to the following “Confirmation of error history” for confirmation.

Confirmation of error history

When a fault occurs in the air conditioner, the error history can be confirmed with the following procedure. (The error history is stored in memory and can contain up to 4 errors).

This history can be confirmed from either the operating status or the stop status.

31

CODE No.

UNIT No.

R.C. No.

Check code

Indoor unit No. in which

 

an error occurred

TEMP.

 

ON / OFF

2

 

 

TIMER SET

FAN

MODE

TIME

SWING/FIX

VENT

FILTER

 

 

RESET TEST SET CL

UNIT

 

3 1

On the remote controller (Main remote controller, Central control remote controller) and the interface P.C. board of the outdoor unit, a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C. board) operation is provided. Therefore the operation status can be known. Using this self-diagnosis function, a fault and the location of this fault within the air conditioning system can be located, as shown in the table below.

Check code list

The following list shows each check code. Find the check contents from the list according to part to be checked.

In case of a fault from the indoor remote controller: See “Main remote controller display” in the list.

In case of a fault from the outdoor unit: See “Outdoor 7-segment display” in the list.

In case of a fault from the indoor unit with a wireless remote controller: See “Sensor block display of receiving unit” in the list.

Terminology

IPDU : Intelligent Power Drive Unit

¡ : Lighting,

¤: Flashing,

l : Goes off

 

ALT. : Flashing is alternately when there are two flashing LED.

SIM : Simultaneous flashing when there are two flashing LED.

 

 

 

Check code

Wireless remote controller

 

 

 

 

 

 

 

 

 

 

 

Main

 

 

Outdoor 7-segment display

Sensor block display

Check code name

Judging device

remote

 

 

 

of receiving unit

 

 

 

 

 

 

 

 

controller

 

 

 

 

 

 

 

 

 

display

 

 

Auxiliary code

Operation

Timer

Ready

Flash

 

 

 

 

 

 

 

 

 

 

 

 

E01

 

¤ l

l

 

Communication error between indoor and remote

Remote controller

 

 

controller (Detected at remote controller side)

E02

 

¤

l

l

 

Remote controller transmission error

Remote controller

E03

 

¤ l

l

 

Communication error between indoor and remote

Indoor

 

 

controller (Detected at indoor side)

E04

 

l

l

¤

 

Communication circuit error between indoor/outdoor

Indoor

Procedure

Description

 

 

 

 

 

 

 

When pushing the SET and TEST buttons simultaneously for 4 seconds

 

 

 

or more, the display similar to the one shown in the figure to the right

 

 

 

will appear.

 

CODE No.

 

 

 

1

If [Service Check] is displayed, the fault code will be stored in the

 

 

UNIT No.

error history mode.

 

 

 

R.C. No.

01 (Order of error history) is displayed in CODE No. window.

Check Code is displayed in the CHECK window.

The indoor unit address, where the fault has occurred will be displayed in the UNIT No. window.

When pushing the TEMP. buttons, the error history stored within the memory will be displayed in chronological order.

2

The numbers displayed within the CODE No. window can vary between 1 and 4. 1 being the most recent fault

and 4 being the oldest.

 

CAUTION

 

Do not push the CL button as this will erase all of the error history for that indoor unit.

 

 

3

After confirmation, push the TEST button. This will return the display back to its original mode.

 

 

 

 

 

 

 

 

(Detected at indoor side)

 

 

 

 

 

 

 

 

 

 

E06

E06

No. of indoor units in which sensor has

l

l

¤

 

Decrease of No. of indoor units

I/F

been normally received

 

E07

l

l

¤

 

Communication circuit error between indoor/outdoor

I/F

 

(Detected at outdoor side)

E08

E08

Duplicated indoor addresses

¤ l

l

Duplicated indoor addresses

Indoor / I/F

E09

¤

l

l

Duplicated main remote controllers

Remote controller

E10

¤ l

l

Communication error between indoor MCU

Indoor

E12

E12

01: Indoor/Outdoor communication

¤ l

l

Automatic address start error

I/F

02: Communication between outdoor units

E15

E15

l

l

¤

 

Indoor is nothing during automatic addressing

I/F

E16

E16

00: Capacity over

l

l

¤

 

Capacity over / No. of connected indoor units

I/F

01 ~: No. of connected units

 

E18

¤

l

l

Communication error between indoor units

Indoor

E19

E19

00: Header is nothing

l

l

¤

 

Outdoor header units quantity error

I/F

02: Two or more header units

 

E20

E20

01: Outdoor of other line connected

l

l

¤

 

Other line connected during automatic address

I/F

02: Indoor of other line connected

 

E23

E23

l

l

¤

 

Sending error in communication between outdoor units

I/F

E25

E25

l

l

¤

 

Duplicated follower outdoor addresses

I/F

E26

E26

No. of outdoor units which received signal

l

l

¤

 

Decrease of No. of connected outdoor units

I/F

normally

 

E28

E28

Detected outdoor unit number

l

l

¤

 

Follower outdoor unit error

I/F

01:IPDU1 error

02:IPDU2 error

03:IPDU1, 2 error

E31

E31 04: Fan IPDU error

l

l

¤

IPDU communication error

I/F

05:IPDU + Fan IPDU error

06:IPDU2 + Fan IPDU error

07:All IPDU error

Image 31
Contents Compact 4-Way Air Discharge Cassette Type Contents Safety Caution Metal section Earth position Check the following items after reinstallationCatch the inner cables Fire is caused at user’s sideFlare nut Safety Caution Concerned to New RefrigerantPipe Materials PipingGeneral tools Conventional tools can be used R410A Conventional air Air conditioner installationConditioner installation ToolsCylinder with siphon Recharge of RefrigerantEnvironment 4mm-hexagonal wrench is requiredDrain-up standing-up size Space required for Installation and servicingWired remote Construction Views External ViewsControl P.C. board Wiring DiagramFor Indoor unit MCC-1402Model Parts RatingParts Rating Name of Each PartDisplay section Parts Name of Remote ControllerWind direction and Swing Remote controller sensorOperation section ButtonStop Turn on the main power switch and/or the leakage breakerCorrect Usage PreparationWhen restarting the operation after stop Automatic Operation Super Heat Recovery Type OnlyStart To select SET Time Timer OperationTimer operation Cancel of timer operationHow to stop swinging Adjustment of Wind DirectionHow to set up the air direction How to start swingingInformation Air Conditioner Operations and Performance Standby When the Following Symptoms are FoundConnect all of the installation wiring correctly Precautions for SafetyNew Refrigerant Air Conditioner Installation To Disconnect the Appliance from Main Power SupplyInstallable ceiling height list Selection of Installation PlaceInstallation space Installation spaceCase of wireless type Installation of Indoor UnitDimensional view Installation of remote controller Sold separately Ceiling opening and installation of hanging boltsInstallation of ceiling panel Sold separately Installation of hanging boltDrain Piping Work Permissible pipe length and permissible height difference Piping material and dimensionsRefrigerant Piping Thermal insulating processOpen fully valves of the outdoor unit Gas leak check Electric WorkConnection of refrigerant pipe Airtight test/Air purge, etcRemote controller wiring *4 Power supply specificationsIndoor unit power supply *1 Indoor/Outdoor inter-unit wiring, Central controller wiringApplicable Controls Increased heating effect Case of installation to high ceilingCase of remote controller-less Group control Change of lighting time of filter signTest RUN How to execute test operationCase of wireless remote controller Case of wired remote controllerConfirmation and check Check method TroubleshootingConfirmation of error history Check code listError detected by TCC-LINK central control device TroubleshootingWay Air Discharge Cassette Type MaintenanceDaily maintenance New check codeFunctional part name Functional outline Refrigerating Cycle DiagramControl Outline Control SpecificationsOutline of specifications Remarks Remote controller Control outline CommandValue Reset conditionsTCB-AX21E Central control mode Central control mode 1 Cannot operateCentral control mode 4 Cannot select mode Applied Control Procedure Execute the setup operation while the unit stopsHEAT, Heat → Cool Description At shipmentIndoor unit capacity Applied Control in Indoor UnitRemote location ON/OFF control box TCB-IFCB-4E Operation Ventilating fan control from remote controllerWiring FunctionLeaving-ON prevention control Power peak-cut from indoor unitUsing the setup temp Button, set to the setup dataTroubleshooting procedure TroubleshootingTroubleshooting Summary Before troubleshootingJudging device Check code listCheck Method Auxiliary codeSensor block display MG-SWCheck code Outdoor 7-segment display Auxiliary code Error detected by TCC-LINK central control deviceCheck code Procedure Description Troubleshooting by Check Display on Remote ControllerCase of wired remote controller RBC-AMT31E Confirmation of error historyCase of central remote controller TCB-SC642TLE Remote Check codeOutdoor 7-segment display Check code Auxiliary codeConvenient functions Setup method of No. capacity-over DetectionCheck code Main Outdoor 7-segment display RemoteDetected Main Outdoor 7-segment displayCheck code Auxiliary code RemoteCheck item position Remote Check codeDetected Main Status Error detection condition Check item positionPosition Remote Check clogging of oil equation pipe between compressors Check code Main Outdoor 7-segment displayH07 Check all the outdoor units in the corresponding lineH16 Check code Main Outdoor 7-segment display RemoteL30 Detected indoor address L31 P01 P03 P04 Name TS error judgment standard temperatureHeating Remote Check code Auxiliary code Outdoor 7-segment display Check code name Error detection condition Check item positionCentral control Outdoor 7-segment display Detected positionDevice Check code Display onMeasured position Criteria How to check inverter outputHow to check resistance of compressor winding How to check the outdoor fan motorE02 Diagnosis Procedure for Each Check CodeE03 E04E07 E06 Decreased number of indoor unitsE09 Duplicated master E08E12 E15Reference E16E18 E19E25 ∗ 1 How to clear the errorE20 E23F03 E31F01 F02F08 To sensor error F04 TD1 sensor errorF05 TD2 sensor error F06 TE1 sensor errorF23 F29 Indoor other errorF15 Outdoor temp sensor miscabling TE1, TLH03 F31H02 H01H06 Low-pressure protective operation Clogging for SV3E valve Leakage check for SV3C valveClogging check for SV3D valve H08 Clogging check for oil-equalization circuitTK3 temperature detective circuit error Oil level detective circuit system errorL03 H16 TK4 temperature detective circuit errorL04 L05L08 L07 Group line in individual indoor unitL10 L17L28 L18L29 L20L31 P01 Indoor fan motor errorL30 Interlock in indoor unit P03Auxiliary code Compressor 1 side P05 Open phase, negative phaseP04 Actuation High-pressure SWP12 P07 Heat sink overheat errorP10 Indoor overflow error Indoor fan motor errorTS condition Auxiliary code P13 Outdoor liquid back detection error 1. PMV1/PMV2 errorP15 Gas leak detectionTD condition Auxiliary code Discharge temp TD2 errorP15 Gas leak detection P17P20 High-pressure protective operation P19 Way valve operation errorJudgment criteria Auxiliary code 0 ∗ P22 Outdoor fan Ipdu errorP31 P26 Tr short-circuit protection errorDetective circuit error P29Segment display on the outdoor unit Interface P.C. board Check procedure in case of stop with troubleHow to read the check monitor Segment display Segment Display FunctionSW01 SW02 SW03 Display contents There is auxiliary code Check code ∗ ∗ ∗ for 3 seconds SW03 SW02 Indoor address Segment display a Data display of outdoor cycle Displayed on each outdoor unitSegment display A, B Sensor CharacteristicsTemperature sensor characteristics W01 SW02 SW03 Display contents Segment displayIndoor Unit Configuration of Control CircuitWired remote controller Up to 2 units Weekly timerKit Connection of wireless remote controllerCompact 4-way Air Discharge Cassette Type Compact4-way Air Discharge Connection of both remote WirelessCassette Type Controller RemoteCassette Air DischargeType MCC-1402 Compact 4-wayFunction Connector Pin Specifications Remarks Optional Connector Specifications of Indoor P.C. BoardAttachment Part name Procedure RemarksDetachments Preparing work100 101 No. Part name Procedure Remarks102 Bell mouth 1. Detachment No. Part name Procedure103 Fan guard 1. DetachmentFan motor 1. Detachment 104Drain pump 1. Detachment 105Details of a part Details of sensor lead wire drawing106 Arrow view B107 Exchanger Recover refrigerant gasHeat 108 10. P.C. Board Exchange ProceduresExchange of P.C. Board for Indoor Service Exchange procedureRemote controller operation diagram Procedure 1 Readout setup contents from Eeprom110 Procedure 2 Exchange of P.C. board for serviceEeprom layout Procedure 3 Writing-in of setup contents to EepromMake a note of the setup contents. Item code list Example Description Exploded Views and Parts ListCeiling Panel 113114 Compact 4-way Air Discharge Cassette TypeMMU-AP0071MH, AP0091MH, AP0121MH, AP0151MH, AP0181MH 211Description Remarks Model Name 1150071MH 0091MH 0121MH 0151MH 0181MH Description Model Name 116Toshiba Carrier Corporation

MMU-AP0181MH, MMU-AP0071MH, MMU-AP0091MH, MMU-AP0151MH, MMU-AP0121MH specifications

The Toshiba MMU-AP series, consisting of models MMU-AP0121MH, MMU-AP0151MH, MMU-AP0091MH, MMU-AP0071MH, and MMU-AP0181MH, represents a significant advancement in the realm of power management and energy efficiency for a variety of applications. These modules are designed to optimize performance while ensuring minimal energy consumption, making them suitable for both commercial and industrial uses.

One of the standout features of the MMU-AP series is its intelligent power management technology. This feature allows for adaptive energy distribution based on real-time demands. By leveraging precise control algorithms, the modules can adjust their output to match the specific requirements of connected devices, ultimately leading to reduced power loss and increased efficiency. This adaptability not only benefits end-users by lowering operational costs but also contributes to a greener environment by minimizing waste.

The versatility of the MMU-AP series is evident in its wide range of operational capabilities. These power modules are designed to work effectively in various voltage levels and load conditions. With input voltage ranges suitable for standard industrial environments, they can easily be integrated into existing systems, enhancing overall functionality without requiring extensive modifications.

Moreover, the compact design of the MMU-AP modules is another notable characteristic. Their size and light weight facilitate easier installation and integration into tight spaces, making them ideal for applications where real estate is a premium. This compact profile does not compromise performance, as these modules are engineered to deliver robust power output while maintaining thermal efficiency.

In terms of reliability, the MMU-AP series is built with high-grade components that withstand harsh operating conditions. With features such as over-voltage protection, short-circuit protection, and thermal shutdown capabilities, users can trust that their equipment would operate safely and efficiently, thereby extending the lifespan of both the power modules and the devices they serve.

Finally, Toshiba’s commitment to innovation ensures that the MMU-AP series incorporates cutting-edge technology. The series supports communication protocols that enable seamless integration with smart systems, paving the way for advanced monitoring and control functions. This levels up the user experience, providing insights into performance and diagnostics that are crucial for uptime and reliability in demanding environments.

In conclusion, the Toshiba MMU-AP series offers a blend of efficiency, adaptability, and advanced technology, making it a valuable asset for various industrial and commercial applications. Its intelligent design and robust features ensure that users can optimize energy use while maintaining high performance and reliability.