Carrier 48TCA04---A12 appendix Supply Air Temperature SAT Sensor, Outdoor Air Lockout Sensor

Page 58

Supply Air Temperature (SAT) Sensor

The supply air temperature sensor is a 3 K thermistor located at the inlet of the indoor fan. (See Fig. 75.) This sensor is factory installed. The operating range of temperature measurement is 0° to 158_F (-18_to 70_C). See Table 15 for sensor temperature/resistance values.

and D. See Fig. 77 for the corresponding temperature changeover values.

48TC

SUPPLY AIR

TEMPERATURE

SENSOR

MOUNTING

LOCATION

SUPPLY AIR

TEMPERATURE

SENSOR

C06033

Fig. 75 - Supply Air Sensor Location

The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.

Outdoor Air Lockout Sensor

The EconoMi$er IV is equipped with an ambient temperature lockout switch located in the outdoor airstream which is used to lock out the compressors below

a42_F (6_C) ambient temperature. (See Fig. 70.)

EconoMi$er IV Control Modes

IMPORTANT: The optional EconoMi$er2 does not include a controller. The EconoMi$er2 is operated by a 4 to 20 mA signal from an existing field-supplied controller (such as PremierLinkcontrol). See Fig. 72 for wiring information.

Determine the EconoMi$er IV control mode before set up of the control. Some modes of operation may require different sensors. (See Table 22.) The EconoMi$er IV is supplied from the factory with a supply-air temperature sensor and an outdoor- air temperature sensor. This allows for operation of the EconoMi$er IV with outdoor air dry bulb changeover control. Additional accessories can be added to allow for different types of changeover control and operation of the EconoMi$er IV and unit.

Outdoor Dry Bulb Changeover

The standard controller is shipped from the factory configured for outdoor dry bulb changeover control. The outdoor air and supply air temperature sensors are included as standard. For this control mode, the outdoor temperature is compared to an adjustable setpoint selected on the control. If the outdoor-air temperature is above the setpoint, the EconoMi$er IV will adjust the outside air dampers to minimum position. If the outdoor-air temperature is below the setpoint, the position of the outside air dampers will be controlled to provided free cooling using outdoor air. When in this mode, the LED next to the free cooling setpoint potentiometer will be on. The changeover temperature setpoint is controlled by the free cooling setpoint potentiometer located on the control. (See Fig. 76.) The scale on the potentiometer is A, B, C,

C06034

Fig. 76 - EconoMi$er IV Controller Potentiometer

and LED Locations

 

19

 

 

 

 

 

 

 

 

 

 

 

 

 

18

LED ON

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

LED OFF

LED ON

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mA

14

 

 

 

LED OFF

 

LED ON

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

LED OFF

LED ON

 

 

11

 

 

 

 

 

 

 

 

 

 

A

 

 

10

 

 

 

 

 

 

 

 

 

LED OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

50

 

 

 

 

 

 

 

 

 

100

 

40

45

55

60

65

70

75

80

85

90

95

 

 

 

 

 

DEGREES FAHRENHEIT

 

 

 

 

C06035

Fig. 77 - Outside Air Temperature Changeover

Setpoints

(cfm)

30

MINUTE

25

 

PER

20

15

FEET

10

CUBICIN

0

 

5

FLOW

0.13

0.20

0.22

0.25

0.30

0.35

0.40

0.45

0.50

 

 

STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

C06031

Fig. 78 - Outdoor-Air Damper Leakage

Differential Dry Bulb Control

For differential dry bulb control the standard outdoor dry bulb sensor is used in conjunction with an additional accessory dry bulb sensor (part number CRTEMPSN002A00). The accessory sensor must be mounted in the return airstream. (See Fig. 79.) Wiring is

58

Image 58
Contents Table of Contents Safety ConsiderationsGeneral Unit Arrangement and AccessRoutine Maintenance What to do if you smell gasSeasonal Maintenance Supply FAN Blower Section Supply Fan Belt-DriveCooling Condenser Coil Maintenance and Cleaning RecommendationCondenser Coil Remove Surface Loaded Fibers Periodic Clean Water RinseRoutine Cleaning of Coil Surfaces One-Row CoilEvaporator Coil Refrigerant System Pressure Access PortsCleaning the Evaporator Coil Evaporator Coil Metering DevicesRefrigerant Charge To Use Cooling Charging ChartsPuronr R-410A Refrigerant No ChargeCooling Charging Charts Size Designation Nominal Tons ReferenceCooling Charging Charts C08229 C08437 C08438 C08439 Cooling Service Analysis Problem Cause RemedyConvenience Outlets Condenser-Fan AdjustmentTroubleshooting Cooling System CompressorController Smoke DetectorsSystem Unit Connect Primary TransformerSensor Smoke Detector LocationsCompleting Installation of Return Air Smoke Sensor Fiop Smoke Detector Wiring and ResponseController Alarm Test Sensor Alarm TestSensor Alarm Test Procedure Sensor and Controller TestsDirty Sensor Test Procedure Controller Alarm Test ProcedureDirty Controller Test Procedure To Configure the Dirty Sensor Test OperationDetector Cleaning Troubleshooting Compressor Protection Protective DevicesGAS Heating System Relief DeviceNatural Gas Manifold Pressure Ranges Fuel Types and PressuresNatural Gas Supply Line Pressure Ranges Liquid Propane Supply Line Pressure RangesFlue Gas Passageways Combustion-Air BlowerBurners and Igniters Cleaning and AdjustmentCheck Unit Operation and Make Necessary Adjust- ments Main BurnersLimit Switch Burner IgnitionLED Error Code Description Orifice ReplacementLED Indication Error Code Description Red LED-Status IGC Connections Orifice SizesCont. Altitude Compensation* A08-A12 Altitude Compensation* A04-A07LP Orifice Minimum heating entering air temperature Troubleshooting Heating SystemAltitude Compensation* A04-A06 Low NOx Units Heating Service Analysis Problem Cause RemedyIGC Board LED Alarm Codes IGCPremierlinkt Control PremierLink ControllerPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring Space Sensor Mode PremierLink Sensor UsageThermostat Mode 56 Internal ConnectionsLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection Recommended Cables RTU-MP Control SystemColor Code Recommendations RTU-MP Multi-Protocol Control Board RTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs OutputsSpace Temperature SPT Sensors RTU-MP T-55 Sensor ConnectionsIAQ Sensor SEN J4-2 COM J4-3 24 VAC Power Exhaust output Connecting Discrete InputsCommunication Wiring Protocols RTU-MP Troubleshooting LEDs LEDs on the RTU-MP show the status of certain functionsTroubleshooting Alarms Alarms BACnet MS/TPRTU-MP Driver Manufacture Date Basic Protocol TroubleshootingModbus Code Name MeaningEconomizer Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring EconoMi$er EconoMi$er IV Input/Output LogicEconoMi$er IV Control Modes Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor Outdoor Dry Bulb ChangeoverReturn Air Temperature or Enthalpy Sensor Mounting Location Outdoor Enthalpy ChangeoverIndoor Air Quality IAQ Sensor Input Exhaust Setpoint AdjustmentMinimum Position Control Occupancy Control Damper MovementThermostats Demand Control Ventilation DCVEconoMi$er IV Preparation CO2 Sensor ConfigurationEconoMi$er IV Sensor Usage Differential EnthalpyWiring Diagrams 48TC Typical Unit Wiring Diagram Power A06, 208/230-3-60 48TC Unit Wiring Diagram Control A06 PRE-START-UP START-UP, GeneralHeating CoolingMain Burners Ventilation Continuous FanSTART-UP, RTU-MP Control Field Service TestSTART-UP, Premierlink Controls Perform System Check-OutConfiguration Space Sensor Type InputsInput Input 1 FunctionHeating, Units Without Economizer Operating SequencesBase Unit Controls Cooling, Units Without Economizer Cooling, Unit With EconoMi$erHeating With EconoMi$er PremierLink Control48TC Available Cooling Stages OAT ≤ SPT 48TC 48TC Linkage Modes Loadshed Command Gas and Electric Heat UnitsRTU-MP Sequence of Operation SchedulingBACnet Schedule Always Occupied Default OccupancyLocal Schedule BAS On/OffEconomizer Power ExhaustIndoor Air Quality Demand Limit Fastener Torque ValuesTorque Values Serial Number Format Appendix I. Model Number SignificanceModel Number Nomenclature Position NumberAppendix II. Physical Data Physical Data Cooling TonsPhysical Data Cooling 48TC*A08 48TC*A09 48TC*A12Physical Data Heating LOW Appendix III. FAN Performance General Fan Performance NotesTon Vertical Supply Ton Horizontal SupplyCFM RPM BHP Medium Static Option High Static Option 48TC**05 Phase Ton Horizontal Supply 48TC**051506 48TC**05 Phase Ton Vertical Supply1493 148648TC**06 148248TC**06 Phase Ton Horizontal Supply 48TC**06 Phase Ton Vertical SupplyPhase Ton Horizontal Supply 48TC**071103 1143 11071124 1122 11621116 4971099 1093 11331247 5791263 1273Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboRange RLA LRA Appendix IV. Electrical DataIFM TypeAppendix IV. Electrical Data FLARLA LRA IFM RangeEFF at FullFAN Motor Exhaust Combustion PowerNOM IFM No P.E Type DISC. SizeUnbalanced 3-Phase Supply Voltage NOMAppendix V. Wiring Diagram List Wiring DiagramsAppendix VI. Motormaster Sensor Locations 48TC*A04 Outdoor Circuiting48TC*A09/12 Outdoor Circuiting Catalog No 48TC---2SMUnit START-UP Checklist Preliminary Information

48TCA04---A12 specifications

The Carrier 48TCA04---A12 is a high-efficiency rooftop air conditioning unit designed for commercial and industrial applications. Known for its reliability and performance, this model features advanced technologies that cater to diverse climate control needs.

One of the standout features of the Carrier 48TCA04---A12 is its excellent energy efficiency, which adheres to the stringent standards set by the U.S. Environmental Protection Agency. The unit utilizes a highly efficient scroll compressor combined with state-of-the-art heat exchanger technology, allowing it to operate with minimal energy consumption while providing powerful cooling capabilities.

The unit comes equipped with a robust and durable design, built to withstand various environmental conditions. Its weather-resistant cabinet is constructed from high-quality materials, ensuring long-lasting performance even in harsh climates. Additionally, the unit features a galvanized steel structure with a powder-coated finish, further enhancing its resistance to corrosion and wear.

In terms of technologies, the Carrier 48TCA04---A12 incorporates advanced controls that promote optimal performance. The unit supports Carrier's smart connectivity options, facilitating remote monitoring and adjustments via smart devices. This feature ensures convenient energy management and allows maintenance teams to access performance data, leading to proactive service interventions.

Another important characteristic of this unit is its quiet operation. The design includes sound-reducing insulation and a well-engineered airflow system, minimizing noise levels to create a more comfortable indoor environment. This is particularly important for commercial spaces such as offices and retail environments, where a tranquil atmosphere is critical for customer satisfaction and productivity.

The Carrier 48TCA04---A12 also offers diverse application flexibility, making it suitable for various locations, from small retail stores to large warehouses. With several tonnage options available, users can select a model that perfectly aligns with their specific cooling needs. Additionally, the unit can be easily integrated with existing HVAC systems, providing a seamless solution for upgrading or retrofitting older installations.

To sum up, the Carrier 48TCA04---A12 rooftop air conditioning unit stands out due to its exceptional energy efficiency, durable construction, advanced technology, and quiet operation, making it a reliable choice for commercial and industrial cooling solutions. Its flexibility and smart technology integrations ensure that it meets a wide range of climate control requirements effectively.