Carrier 48TCA04---A12 appendix Evaporator Coil, Refrigerant System Pressure Access Ports

Page 7

6.Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.

7.Secure inner and outer coil rows together with a field-supplied fastener.

8.Reposition the outer coil section and remove the coil corner post from between the top panel and center post. Reinstall the coil corner post and replace all screws.

Totaline Environmentally Sound Coil Cleaner Application Equipment

S2-1/2 gallon garden sprayer

S Water rinse with low velocity spray nozzle

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in accelerated corrosion of unit parts.

Harsh chemicals, household bleach or acid or basic cleaners should not be used to clean outdoor or indoor coils of any kind. These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion at the fin/tube interface where dissimilar materials are in contact. If there is dirt below the surface of the coil, use the Totaline environmentally sound coil cleaner.

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in reduced unit performance or unit shutdown.

High velocity water from a pressure washer, garden hose, or compressed air should never be used to clean a coil. The force of the water or air jet will bend the fin edges and increase airside pressure drop.

Totaline Environmentally Sound Coil Cleaner Application Instructions

1.Proper eye protection such as safety glasses is recom- mended during mixing and application.

2.Remove all surface loaded fibers and dirt with a vacu- um cleaner as described above.

3.Thoroughly wet finned surfaces with clean water and a low velocity garden hose, being careful not to bend fins.

4.Mix Totaline environmentally sound coil cleaner in a 2-1/2 gallon garden sprayer according to the instruc- tions included with the cleaner. The optimum solution temperature is 100_F.

NOTE: Do NOT USE water in excess of 130_F, as the enzymatic activity will be destroyed.

5.Thoroughly apply Totaline environmentally sound coil cleaner solution to all coil surfaces including finned area, tube sheets and coil headers.

6.Hold garden sprayer nozzle close to finned areas and apply cleaner with a vertical, up-and-down motion.

Avoid spraying in horizontal pattern to minimize po- tential for fin damage.

7.Ensure cleaner thoroughly penetrates deep into finned areas.

8.Interior and exterior finned areas must be thoroughly cleaned.

9.Finned surfaces should remain wet with cleaning solution for 10 minutes.

10.Ensure surfaces are not allowed to dry before rinsing. Reapplying cleaner as needed to ensure 10-minute saturation is achieved.

11.Thoroughly rinse all surfaces with low velocity clean water using downward rinsing motion of water spray nozzle. Protect fins from damage from the spray nozzle.

Evaporator Coil

Cleaning the Evaporator Coil

1.Turn unit power off. Install lockout tag. Remove evaporator coil access panel.

2.If economizer or two-position damper is installed, re- move economizer by disconnecting Molex plug and removing mounting screws.

3.Slide filters out of unit.

4.Clean coil using a commercial coil cleaner or dish- washer detergent in a pressurized spray canister. Wash both sides of coil and flush with clean water. For best results, back-flush toward return-air section to re- move foreign material. Flush condensate pan after completion.

5.Reinstall economizer and filters.

6.Reconnect wiring.

7.Replace access panels.

Evaporator Coil Metering Devices

The metering devices are multiple fixed-bore devices (Acutrolt) swedged into the horizontal outlet tubes from the liquid header, located at the entrance to each evaporator coil circuit path. These are non-adjustable. Service requires replacing the entire liquid header assembly.

To check for possible blockage of one or more of these metering devices, disconnect the supply fan contactor (IFC) coil, then start the compressor and observe the frosting pattern on the face of the evaporator coil. A frost pattern should develop uniformly across the face of the coil starting at each horizontal header tube. Failure to develop frost at an outlet tube can indicate a plugged or a missing orifice.

Refrigerant System Pressure Access Ports

There are two access ports in the system - on the suction tube near the compressor and on the discharge tube near the compressor. These are brass fittings with black plastic caps. The hose connection fittings are standard 1/4 SAE male flare couplings.

The brass fittings are two-piece High Flow valves, with a receptacle base brazed to the tubing and an integral spring-closed check valve core screwed into the base.

48TC

7

Image 7
Contents Safety Considerations Table of ContentsWhat to do if you smell gas Unit Arrangement and AccessRoutine Maintenance GeneralSeasonal Maintenance Supply Fan Belt-Drive Supply FAN Blower SectionCooling Condenser Coil Maintenance and Cleaning RecommendationCondenser Coil One-Row Coil Periodic Clean Water RinseRoutine Cleaning of Coil Surfaces Remove Surface Loaded FibersEvaporator Coil Metering Devices Refrigerant System Pressure Access PortsCleaning the Evaporator Coil Evaporator CoilNo Charge To Use Cooling Charging ChartsPuronr R-410A Refrigerant Refrigerant ChargeSize Designation Nominal Tons Reference Cooling Charging ChartsCooling Charging Charts C08229 C08437 C08438 C08439 Problem Cause Remedy Cooling Service AnalysisCompressor Condenser-Fan AdjustmentTroubleshooting Cooling System Convenience OutletsUnit Connect Primary Transformer Smoke DetectorsSystem ControllerSmoke Detector Locations SensorFiop Smoke Detector Wiring and Response Completing Installation of Return Air Smoke SensorSensor and Controller Tests Sensor Alarm TestSensor Alarm Test Procedure Controller Alarm TestTo Configure the Dirty Sensor Test Operation Controller Alarm Test ProcedureDirty Controller Test Procedure Dirty Sensor Test ProcedureDetector Cleaning Troubleshooting Relief Device Protective DevicesGAS Heating System Compressor ProtectionLiquid Propane Supply Line Pressure Ranges Fuel Types and PressuresNatural Gas Supply Line Pressure Ranges Natural Gas Manifold Pressure RangesCombustion-Air Blower Flue Gas PassagewaysMain Burners Cleaning and AdjustmentCheck Unit Operation and Make Necessary Adjust- ments Burners and IgnitersBurner Ignition Limit SwitchLED Error Code Description Orifice ReplacementLED Indication Error Code Description Red LED-Status Orifice Sizes IGC ConnectionsCont. Altitude Compensation* A08-A12 Altitude Compensation* A04-A07LP Orifice Minimum heating entering air temperature Troubleshooting Heating SystemAltitude Compensation* A04-A06 Low NOx Units Problem Cause Remedy Heating Service AnalysisIGC IGC Board LED Alarm CodesPremierLink Controller Premierlinkt ControlPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring PremierLink Sensor Usage Space Sensor Mode56 Internal Connections Thermostat ModeLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection Recommended Cables RTU-MP Control SystemColor Code Recommendations RTU-MP Multi-Protocol Control Board RTU-MP System Control Wiring Diagram Outputs RTU-MP Controller Inputs and OutputsRTU-MP T-55 Sensor Connections Space Temperature SPT SensorsIAQ Sensor SEN J4-2 COM J4-3 24 VAC Power Exhaust output Connecting Discrete InputsCommunication Wiring Protocols RTU-MP Troubleshooting LEDs on the RTU-MP show the status of certain functions LEDsTroubleshooting Alarms BACnet MS/TP AlarmsRTU-MP Driver Code Name Meaning Basic Protocol TroubleshootingModbus Manufacture DateEconoMi$er IV Component Locations Economizer SystemsEconoMi$er IV Wiring EconoMi$er IV Input/Output Logic EconoMi$erOutdoor Dry Bulb Changeover Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor EconoMi$er IV Control ModesOutdoor Enthalpy Changeover Return Air Temperature or Enthalpy Sensor Mounting LocationIndoor Air Quality IAQ Sensor Input Exhaust Setpoint AdjustmentMinimum Position Control Demand Control Ventilation DCV Damper MovementThermostats Occupancy ControlDifferential Enthalpy CO2 Sensor ConfigurationEconoMi$er IV Sensor Usage EconoMi$er IV PreparationWiring Diagrams 48TC Typical Unit Wiring Diagram Power A06, 208/230-3-60 48TC Unit Wiring Diagram Control A06 START-UP, General PRE-START-UPVentilation Continuous Fan CoolingMain Burners HeatingPerform System Check-Out Field Service TestSTART-UP, Premierlink Controls START-UP, RTU-MP ControlConfiguration Input 1 Function InputsInput Space Sensor TypeCooling, Unit With EconoMi$er Operating SequencesBase Unit Controls Cooling, Units Without Economizer Heating, Units Without EconomizerPremierLink Control Heating With EconoMi$er48TC Available Cooling Stages OAT ≤ SPT 48TC 48TC Scheduling Loadshed Command Gas and Electric Heat UnitsRTU-MP Sequence of Operation Linkage ModesBAS On/Off Always Occupied Default OccupancyLocal Schedule BACnet ScheduleEconomizer Power ExhaustIndoor Air Quality Demand Limit Fastener Torque ValuesTorque Values Position Number Appendix I. Model Number SignificanceModel Number Nomenclature Serial Number FormatPhysical Data Cooling Tons Appendix II. Physical Data48TC*A08 48TC*A09 48TC*A12 Physical Data CoolingPhysical Data Heating LOW General Fan Performance Notes Appendix III. FAN PerformanceTon Vertical Supply Ton Horizontal SupplyCFM RPM BHP Medium Static Option High Static Option 48TC**05 48TC**05 Phase Ton Horizontal Supply1486 48TC**05 Phase Ton Vertical Supply1493 15061482 48TC**0648TC**06 Phase Ton Vertical Supply 48TC**06 Phase Ton Horizontal Supply48TC**07 Phase Ton Horizontal Supply1122 1162 11071124 1103 11431093 1133 4971099 11161273 5791263 1247Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentType Appendix IV. Electrical DataIFM Range RLA LRAFLA Appendix IV. Electrical DataFull IFM RangeEFF at RLA LRAType DISC. Size Combustion PowerNOM IFM No P.E FAN Motor ExhaustNOM Unbalanced 3-Phase Supply VoltageWiring Diagrams Appendix V. Wiring Diagram List48TC*A04 Outdoor Circuiting Appendix VI. Motormaster Sensor LocationsCatalog No 48TC---2SM 48TC*A09/12 Outdoor CircuitingPreliminary Information Unit START-UP Checklist

48TCA04---A12 specifications

The Carrier 48TCA04---A12 is a high-efficiency rooftop air conditioning unit designed for commercial and industrial applications. Known for its reliability and performance, this model features advanced technologies that cater to diverse climate control needs.

One of the standout features of the Carrier 48TCA04---A12 is its excellent energy efficiency, which adheres to the stringent standards set by the U.S. Environmental Protection Agency. The unit utilizes a highly efficient scroll compressor combined with state-of-the-art heat exchanger technology, allowing it to operate with minimal energy consumption while providing powerful cooling capabilities.

The unit comes equipped with a robust and durable design, built to withstand various environmental conditions. Its weather-resistant cabinet is constructed from high-quality materials, ensuring long-lasting performance even in harsh climates. Additionally, the unit features a galvanized steel structure with a powder-coated finish, further enhancing its resistance to corrosion and wear.

In terms of technologies, the Carrier 48TCA04---A12 incorporates advanced controls that promote optimal performance. The unit supports Carrier's smart connectivity options, facilitating remote monitoring and adjustments via smart devices. This feature ensures convenient energy management and allows maintenance teams to access performance data, leading to proactive service interventions.

Another important characteristic of this unit is its quiet operation. The design includes sound-reducing insulation and a well-engineered airflow system, minimizing noise levels to create a more comfortable indoor environment. This is particularly important for commercial spaces such as offices and retail environments, where a tranquil atmosphere is critical for customer satisfaction and productivity.

The Carrier 48TCA04---A12 also offers diverse application flexibility, making it suitable for various locations, from small retail stores to large warehouses. With several tonnage options available, users can select a model that perfectly aligns with their specific cooling needs. Additionally, the unit can be easily integrated with existing HVAC systems, providing a seamless solution for upgrading or retrofitting older installations.

To sum up, the Carrier 48TCA04---A12 rooftop air conditioning unit stands out due to its exceptional energy efficiency, durable construction, advanced technology, and quiet operation, making it a reliable choice for commercial and industrial cooling solutions. Its flexibility and smart technology integrations ensure that it meets a wide range of climate control requirements effectively.