Carrier 48TCA04---A12 Controller Alarm Test Procedure, Dirty Controller Test, Dirty Sensor Test

Page 19

!CAUTION

OPERATIONAL TEST HAZARD

Failure to follow this caution may result in personnel and authority concern.

This test places the duct detector into the alarm state. Disconnect all auxiliary equipment from the controller before performing the test. If the duct detector is connected to a fire alarm system, notify the proper authorities before performing the test.

Controller Alarm Test Procedure

1.Press the controller’s test/reset switch for seven seconds.

2.Verify that the controller’s Alarm LED turns on.

3.Reset the sensor by pressing the test/reset switch for two seconds.

4.Verify that the controller’s Alarm LED turns off.

Dirty Controller Test

The dirty controller test checks the controller’s ability to initiate a dirty sensor test and indicate its results.

!CAUTION

OPERATIONAL TEST HAZARD

Failure to follow this caution may result in personnel and authority concern.

Pressing the controller’s test/reset switch for longer than seven seconds will put the duct detector into the alarm state and activate all automatic alarm responses.

Dirty Controller Test Procedure

1.Press the controller’s test/reset switch for two seconds.

2.Verify that the controller’s Trouble LED flashes.

Dirty Sensor Test

The dirty sensor test provides an indication of the sensor’s ability to compensate for gradual environmental changes. A sensor that can no longer compensate for environmental changes is considered 100% dirty and requires cleaning or replacing. You must use a field provided SD-MAG test magnet to initiate a sensor dirty test. The sensor’s Dirty LED indicates the results of the dirty test as shown in Table 2.

!CAUTION

OPERATIONAL TEST HAZARD

Failure to follow this caution may result in personnel and authority concern.

Holding the test magnet against the sensor housing for more than seven seconds will put the duct detector into the alarm state and activate all automatic alarm responses.

 

Table 2 – Dirty LED Test

 

 

FLASHES

DESCRIPTION

 

 

1

0---25% dirty. (Typical of a newly installed detector)

 

 

2

25---50% dirty

 

 

3

51---75% dirty

 

 

4

76---99% dirty

 

 

Dirty Sensor Test Procedure

1.Hold the test magnet where indicated on the side of the sensor housing for two seconds.

2.Verify that the sensor’s Dirty LED flashes.

!CAUTION

OPERATIONAL TEST HAZARD

Failure to follow this caution may result in personnel and authority concern.

Changing the dirty sensor test operation will put the detector into the alarm state and activate all automatic alarm responses. Before changing dirty sensor test operation, disconnect all auxiliary equipment from the controller and notify the proper authorities if connected to a fire alarm system.

Changing the Dirt Sensor Test

By default, sensor dirty test results are indicated by:

S The sensor’s Dirty LED flashing.

S The controller’s Trouble LED flashing.

S The controller’s supervision relay contacts toggle.

The operation of a sensor’s dirty test can be changed so that the controller’s supervision relay is not used to indicate test results. When two detectors are connected to a controller, sensor dirty test operation on both sensors must be configured to operate in the same manner.

To Configure the Dirty Sensor Test Operation

1.Hold the test magnet where indicated on the side of the sensor housing until the sensor’s Alarm LED turns on and its Dirty LED flashes twice (approximately 60 seconds).

2.Reset the sensor by removing the test magnet then holding it against the sensor housing again until the sensor’s Alarm LED turns off (approximately 2 seconds).

Remote Station Test

The remote station alarm test checks a test/reset station’s ability to initiate and indicate an alarm state.

!CAUTION

OPERATIONAL TEST HAZARD

Failure to follow this caution may result in personnel and authority concern.

This test places the duct detector into the alarm state. Unless part of the test, disconnect all auxiliary equipment from the controller before performing the test. If the duct detector is connected to a fire alarm system, notify the proper authorities before performing the test.

48TC

19

Image 19
Contents Safety Considerations Table of ContentsWhat to do if you smell gas Unit Arrangement and AccessRoutine Maintenance GeneralSeasonal Maintenance Supply Fan Belt-Drive Supply FAN Blower SectionCooling Condenser Coil Maintenance and Cleaning RecommendationCondenser Coil One-Row Coil Periodic Clean Water RinseRoutine Cleaning of Coil Surfaces Remove Surface Loaded FibersEvaporator Coil Metering Devices Refrigerant System Pressure Access PortsCleaning the Evaporator Coil Evaporator CoilNo Charge To Use Cooling Charging ChartsPuronr R-410A Refrigerant Refrigerant ChargeSize Designation Nominal Tons Reference Cooling Charging ChartsCooling Charging Charts C08229 C08437 C08438 C08439 Problem Cause Remedy Cooling Service AnalysisCompressor Condenser-Fan AdjustmentTroubleshooting Cooling System Convenience OutletsUnit Connect Primary Transformer Smoke DetectorsSystem ControllerSmoke Detector Locations SensorFiop Smoke Detector Wiring and Response Completing Installation of Return Air Smoke SensorSensor and Controller Tests Sensor Alarm TestSensor Alarm Test Procedure Controller Alarm TestTo Configure the Dirty Sensor Test Operation Controller Alarm Test ProcedureDirty Controller Test Procedure Dirty Sensor Test ProcedureDetector Cleaning Troubleshooting Relief Device Protective DevicesGAS Heating System Compressor ProtectionLiquid Propane Supply Line Pressure Ranges Fuel Types and PressuresNatural Gas Supply Line Pressure Ranges Natural Gas Manifold Pressure RangesCombustion-Air Blower Flue Gas PassagewaysMain Burners Cleaning and AdjustmentCheck Unit Operation and Make Necessary Adjust- ments Burners and IgnitersBurner Ignition Limit SwitchLED Error Code Description Orifice ReplacementLED Indication Error Code Description Red LED-Status Orifice Sizes IGC ConnectionsCont. Altitude Compensation* A08-A12 Altitude Compensation* A04-A07LP Orifice Minimum heating entering air temperature Troubleshooting Heating SystemAltitude Compensation* A04-A06 Low NOx Units Problem Cause Remedy Heating Service AnalysisIGC IGC Board LED Alarm CodesPremierLink Controller Premierlinkt ControlPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring PremierLink Sensor Usage Space Sensor Mode56 Internal Connections Thermostat ModeLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection Recommended Cables RTU-MP Control SystemColor Code Recommendations RTU-MP Multi-Protocol Control Board RTU-MP System Control Wiring Diagram Outputs RTU-MP Controller Inputs and OutputsRTU-MP T-55 Sensor Connections Space Temperature SPT SensorsIAQ Sensor SEN J4-2 COM J4-3 24 VAC Power Exhaust output Connecting Discrete InputsCommunication Wiring Protocols RTU-MP Troubleshooting LEDs on the RTU-MP show the status of certain functions LEDsTroubleshooting Alarms BACnet MS/TP AlarmsRTU-MP Driver Code Name Meaning Basic Protocol TroubleshootingModbus Manufacture DateEconoMi$er IV Component Locations Economizer SystemsEconoMi$er IV Wiring EconoMi$er IV Input/Output Logic EconoMi$erOutdoor Dry Bulb Changeover Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor EconoMi$er IV Control ModesOutdoor Enthalpy Changeover Return Air Temperature or Enthalpy Sensor Mounting LocationIndoor Air Quality IAQ Sensor Input Exhaust Setpoint AdjustmentMinimum Position Control Demand Control Ventilation DCV Damper MovementThermostats Occupancy ControlDifferential Enthalpy CO2 Sensor ConfigurationEconoMi$er IV Sensor Usage EconoMi$er IV PreparationWiring Diagrams 48TC Typical Unit Wiring Diagram Power A06, 208/230-3-60 48TC Unit Wiring Diagram Control A06 START-UP, General PRE-START-UPVentilation Continuous Fan CoolingMain Burners HeatingPerform System Check-Out Field Service TestSTART-UP, Premierlink Controls START-UP, RTU-MP ControlConfiguration Input 1 Function InputsInput Space Sensor TypeCooling, Unit With EconoMi$er Operating SequencesBase Unit Controls Cooling, Units Without Economizer Heating, Units Without EconomizerPremierLink Control Heating With EconoMi$er48TC Available Cooling Stages OAT ≤ SPT 48TC 48TC Scheduling Loadshed Command Gas and Electric Heat UnitsRTU-MP Sequence of Operation Linkage ModesBAS On/Off Always Occupied Default OccupancyLocal Schedule BACnet ScheduleEconomizer Power ExhaustIndoor Air Quality Demand Limit Fastener Torque ValuesTorque Values Position Number Appendix I. Model Number SignificanceModel Number Nomenclature Serial Number FormatPhysical Data Cooling Tons Appendix II. Physical Data48TC*A08 48TC*A09 48TC*A12 Physical Data CoolingPhysical Data Heating LOW General Fan Performance Notes Appendix III. FAN PerformanceTon Vertical Supply Ton Horizontal SupplyCFM RPM BHP Medium Static Option High Static Option 48TC**05 48TC**05 Phase Ton Horizontal Supply1486 48TC**05 Phase Ton Vertical Supply1493 15061482 48TC**0648TC**06 Phase Ton Vertical Supply 48TC**06 Phase Ton Horizontal Supply48TC**07 Phase Ton Horizontal Supply1122 1162 11071124 1103 11431093 1133 4971099 11161273 5791263 1247Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentType Appendix IV. Electrical DataIFM Range RLA LRAFLA Appendix IV. Electrical DataFull IFM RangeEFF at RLA LRAType DISC. Size Combustion PowerNOM IFM No P.E FAN Motor ExhaustNOM Unbalanced 3-Phase Supply VoltageWiring Diagrams Appendix V. Wiring Diagram List48TC*A04 Outdoor Circuiting Appendix VI. Motormaster Sensor LocationsCatalog No 48TC---2SM 48TC*A09/12 Outdoor CircuitingPreliminary Information Unit START-UP Checklist

48TCA04---A12 specifications

The Carrier 48TCA04---A12 is a high-efficiency rooftop air conditioning unit designed for commercial and industrial applications. Known for its reliability and performance, this model features advanced technologies that cater to diverse climate control needs.

One of the standout features of the Carrier 48TCA04---A12 is its excellent energy efficiency, which adheres to the stringent standards set by the U.S. Environmental Protection Agency. The unit utilizes a highly efficient scroll compressor combined with state-of-the-art heat exchanger technology, allowing it to operate with minimal energy consumption while providing powerful cooling capabilities.

The unit comes equipped with a robust and durable design, built to withstand various environmental conditions. Its weather-resistant cabinet is constructed from high-quality materials, ensuring long-lasting performance even in harsh climates. Additionally, the unit features a galvanized steel structure with a powder-coated finish, further enhancing its resistance to corrosion and wear.

In terms of technologies, the Carrier 48TCA04---A12 incorporates advanced controls that promote optimal performance. The unit supports Carrier's smart connectivity options, facilitating remote monitoring and adjustments via smart devices. This feature ensures convenient energy management and allows maintenance teams to access performance data, leading to proactive service interventions.

Another important characteristic of this unit is its quiet operation. The design includes sound-reducing insulation and a well-engineered airflow system, minimizing noise levels to create a more comfortable indoor environment. This is particularly important for commercial spaces such as offices and retail environments, where a tranquil atmosphere is critical for customer satisfaction and productivity.

The Carrier 48TCA04---A12 also offers diverse application flexibility, making it suitable for various locations, from small retail stores to large warehouses. With several tonnage options available, users can select a model that perfectly aligns with their specific cooling needs. Additionally, the unit can be easily integrated with existing HVAC systems, providing a seamless solution for upgrading or retrofitting older installations.

To sum up, the Carrier 48TCA04---A12 rooftop air conditioning unit stands out due to its exceptional energy efficiency, durable construction, advanced technology, and quiet operation, making it a reliable choice for commercial and industrial cooling solutions. Its flexibility and smart technology integrations ensure that it meets a wide range of climate control requirements effectively.