Carrier 48TCA04---A12 appendix Economizer, Power Exhaust, Indoor Air Quality

Page 80

48TC

the T56 slider offset).

S Space Temperature reading is available.

S If it is unoccupied and the SPT > (unoccupied cool setpoint plus the T56 slider offset). The indoor fan will be turned on by the staging algorithm.

S If economizer is available and active and economizer open > 85% and SAT > (SAT low limit + 5_F) and SPT > effective setpoint + 0.5_F.

OR

Economizer is available, but not active

OR Economizer is not available

S OAT > DX Lockout temperature.

If all of the above conditions are met, the compressors will be energized as required, otherwise they will be de-energized.

There is a fixed 3-minute minimum on time and a 5-minute off time for each compressor output and a 3-minute minimum time delay between staging up or down.

Any time the compressors are running the RTU-MP will stage down the compressors if the SAT becomes less than the cooling low supply air setpoint.

After a compressor is staged off, it may be started again after a normal time-guard period and the supply air temperature has increased above the low supply air setpoint.

Economizer

The Economizer dampers are used to provide free cooling and Indoor Air Quality, if optional CO2 sensor is installed, when the outside conditions are suitable.

The following conditions must be true for economizer operation:

S Indoor Fan has been on for at least 30 seconds. S Enthalpy is Low if the Enthalpy input is enabled. S SAT reading is available.

S OAT reading is available. S SPT reading is available.

S OAT <= High OAT economizer lockout configuration (default = 75).

S OAT <= SPT

If any of the mentioned conditions are not true, the economizer will be set to its configured minimum position. The minimum damper position can be overridden by the IAQ routine described later in this section.

If the above conditions are true, the Economizer Control Master Loop will calculate a damper position value based on the following calculation:

Damper Position = minimum position + PID (SPT - econ setpoint). Econ setpoint is half way between the effective cool and heat setpoints. If the SAT drops below the cooling low supply air setpoint (+ 5_F), the economizer will ramp down to minimum position.

Power Exhaust

If RTU-MP is also controlling an exhaust fan, it can be enabled based on damper position or by occupancy. If

configured for continuous occupied operation, it will be energized whenever the controller is in the occupied mode and disabled when in the unoccupied mode. If configured for damper position control, it will be energized whenever the economizer exceeds the power exhaust setpoint and disabled when the economizer drops below the setpoint by a fixed hysteresis of 10%.

Heating

The heating outputs are controlled by the Heating Control PID Loop and Heating Stages Capacity algorithm. They will be used to calculate the desired number of stages needed to satisfy the space by comparing the SPT to the Occupied Heat Setpoint plus the T56 slider offset when occupied and the Unoccupied Heat Setpoint plus the T56 slider offset if unoccupied. The following conditions must be true in order for this algorithm to run:

S Indoor Fan has been ON for at least 30 seconds.

S Cool mode is not active and the time guard between modes equals zero.

S If occupied and SPT <(occupied heat setpoint plus T56 slider offset)

S SPT reading is available

S If it is unoccupied and the SPT < (unoccupied heat setpoint plus T56 slider offset). The indoor fan will be turned on by the staging algorithm.

S OAT < High OAT lockout temperature.

If all of the above conditions are met, the heating outputs will be energized as required, otherwise they will be de-energized. If the SAT begins to exceed the high supply air setpoint, a ramping function will cause the Heat Stages Capacity algorithm to decrease the number of stages until the SAT has dropped below the setpoint.

There is a fixed one minute minimum on time and a one minute off time for each heat output. Heat staging has a 3 minute stage up and 30 second stage down delay.

Indoor Air Quality

If the optional indoor air quality sensor is installed, the RTU-MP will maintain indoor air quality within the space at the user configured differential setpoint. The setpoint is the difference between the indoor air quality and an optional outdoor air quality sensor. If the outdoor air quality is not present then a fixed value of 400ppm is used. The following conditions must be true in order for this algorithm to run:

S The mode is occupied.

S Indoor Fan has been ON for at least 30 seconds. S Indoor Air Quality sensor has a valid reading

As air quality within the space changes, the minimum position of the economizer damper will be changed thus allowing more or less outdoor air into the space depending on the relationship of the indoor air quality to the differential setpoint. If all the above conditions are true, the IAQ algorithm will run and calculates an IAQ minimum position value using a PID loop. The IAQ minimum damper position is then compared against the user configured economizer minimum position and the greatest value becomes the final minimum damper position of the economizer output.

80

Image 80
Contents Table of Contents Safety ConsiderationsUnit Arrangement and Access Routine MaintenanceGeneral What to do if you smell gasSeasonal Maintenance Supply FAN Blower Section Supply Fan Belt-DriveCondenser Coil Condenser Coil Maintenance and Cleaning RecommendationCooling Periodic Clean Water Rinse Routine Cleaning of Coil SurfacesRemove Surface Loaded Fibers One-Row CoilRefrigerant System Pressure Access Ports Cleaning the Evaporator CoilEvaporator Coil Evaporator Coil Metering DevicesTo Use Cooling Charging Charts Puronr R-410A RefrigerantRefrigerant Charge No ChargeCooling Charging Charts Size Designation Nominal Tons ReferenceCooling Charging Charts C08229 C08437 C08438 C08439 Cooling Service Analysis Problem Cause RemedyCondenser-Fan Adjustment Troubleshooting Cooling SystemConvenience Outlets CompressorSmoke Detectors SystemController Unit Connect Primary TransformerSensor Smoke Detector LocationsCompleting Installation of Return Air Smoke Sensor Fiop Smoke Detector Wiring and ResponseSensor Alarm Test Sensor Alarm Test ProcedureController Alarm Test Sensor and Controller TestsController Alarm Test Procedure Dirty Controller Test ProcedureDirty Sensor Test Procedure To Configure the Dirty Sensor Test OperationDetector Cleaning Troubleshooting Protective Devices GAS Heating SystemCompressor Protection Relief DeviceFuel Types and Pressures Natural Gas Supply Line Pressure RangesNatural Gas Manifold Pressure Ranges Liquid Propane Supply Line Pressure RangesFlue Gas Passageways Combustion-Air BlowerCleaning and Adjustment Check Unit Operation and Make Necessary Adjust- mentsBurners and Igniters Main BurnersLimit Switch Burner IgnitionLED Indication Error Code Description Orifice ReplacementLED Error Code Description Red LED-Status IGC Connections Orifice SizesLP Orifice Altitude Compensation* A04-A07Cont. Altitude Compensation* A08-A12 Altitude Compensation* A04-A06 Low NOx Units Troubleshooting Heating SystemMinimum heating entering air temperature Heating Service Analysis Problem Cause RemedyIGC Board LED Alarm Codes IGCPremierlinkt Control PremierLink ControllerPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring Space Sensor Mode PremierLink Sensor UsageThermostat Mode 56 Internal ConnectionsLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection Color Code Recommendations RTU-MP Control SystemRecommended Cables RTU-MP Multi-Protocol Control Board RTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs OutputsSpace Temperature SPT Sensors RTU-MP T-55 Sensor ConnectionsIAQ Sensor SEN J4-2 COM J4-3 24 VAC Communication Wiring Protocols Connecting Discrete InputsPower Exhaust output RTU-MP Troubleshooting LEDs LEDs on the RTU-MP show the status of certain functionsTroubleshooting Alarms Alarms BACnet MS/TPRTU-MP Driver Basic Protocol Troubleshooting ModbusManufacture Date Code Name MeaningEconomizer Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring EconoMi$er EconoMi$er IV Input/Output LogicSupply Air Temperature SAT Sensor Outdoor Air Lockout SensorEconoMi$er IV Control Modes Outdoor Dry Bulb ChangeoverReturn Air Temperature or Enthalpy Sensor Mounting Location Outdoor Enthalpy ChangeoverMinimum Position Control Exhaust Setpoint AdjustmentIndoor Air Quality IAQ Sensor Input Damper Movement ThermostatsOccupancy Control Demand Control Ventilation DCVCO2 Sensor Configuration EconoMi$er IV Sensor UsageEconoMi$er IV Preparation Differential EnthalpyWiring Diagrams 48TC Typical Unit Wiring Diagram Power A06, 208/230-3-60 48TC Unit Wiring Diagram Control A06 PRE-START-UP START-UP, GeneralCooling Main BurnersHeating Ventilation Continuous FanField Service Test START-UP, Premierlink ControlsSTART-UP, RTU-MP Control Perform System Check-OutConfiguration Inputs InputSpace Sensor Type Input 1 FunctionOperating Sequences Base Unit Controls Cooling, Units Without EconomizerHeating, Units Without Economizer Cooling, Unit With EconoMi$erHeating With EconoMi$er PremierLink Control48TC Available Cooling Stages OAT ≤ SPT 48TC 48TC Loadshed Command Gas and Electric Heat Units RTU-MP Sequence of OperationLinkage Modes SchedulingAlways Occupied Default Occupancy Local ScheduleBACnet Schedule BAS On/OffIndoor Air Quality Power ExhaustEconomizer Torque Values Fastener Torque ValuesDemand Limit Appendix I. Model Number Significance Model Number NomenclatureSerial Number Format Position NumberAppendix II. Physical Data Physical Data Cooling TonsPhysical Data Cooling 48TC*A08 48TC*A09 48TC*A12Physical Data Heating LOW Appendix III. FAN Performance General Fan Performance NotesCFM RPM BHP Ton Horizontal SupplyTon Vertical Supply Medium Static Option High Static Option 48TC**05 Phase Ton Horizontal Supply 48TC**0548TC**05 Phase Ton Vertical Supply 14931506 148648TC**06 148248TC**06 Phase Ton Horizontal Supply 48TC**06 Phase Ton Vertical SupplyPhase Ton Horizontal Supply 48TC**071107 11241103 1143 1122 1162497 10991116 1093 1133579 12631247 1273Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboAppendix IV. Electrical Data IFMRange RLA LRA TypeAppendix IV. Electrical Data FLAIFM Range EFF atRLA LRA FullCombustion Power NOM IFM No P.EFAN Motor Exhaust Type DISC. SizeUnbalanced 3-Phase Supply Voltage NOMAppendix V. Wiring Diagram List Wiring DiagramsAppendix VI. Motormaster Sensor Locations 48TC*A04 Outdoor Circuiting48TC*A09/12 Outdoor Circuiting Catalog No 48TC---2SMUnit START-UP Checklist Preliminary Information

48TCA04---A12 specifications

The Carrier 48TCA04---A12 is a high-efficiency rooftop air conditioning unit designed for commercial and industrial applications. Known for its reliability and performance, this model features advanced technologies that cater to diverse climate control needs.

One of the standout features of the Carrier 48TCA04---A12 is its excellent energy efficiency, which adheres to the stringent standards set by the U.S. Environmental Protection Agency. The unit utilizes a highly efficient scroll compressor combined with state-of-the-art heat exchanger technology, allowing it to operate with minimal energy consumption while providing powerful cooling capabilities.

The unit comes equipped with a robust and durable design, built to withstand various environmental conditions. Its weather-resistant cabinet is constructed from high-quality materials, ensuring long-lasting performance even in harsh climates. Additionally, the unit features a galvanized steel structure with a powder-coated finish, further enhancing its resistance to corrosion and wear.

In terms of technologies, the Carrier 48TCA04---A12 incorporates advanced controls that promote optimal performance. The unit supports Carrier's smart connectivity options, facilitating remote monitoring and adjustments via smart devices. This feature ensures convenient energy management and allows maintenance teams to access performance data, leading to proactive service interventions.

Another important characteristic of this unit is its quiet operation. The design includes sound-reducing insulation and a well-engineered airflow system, minimizing noise levels to create a more comfortable indoor environment. This is particularly important for commercial spaces such as offices and retail environments, where a tranquil atmosphere is critical for customer satisfaction and productivity.

The Carrier 48TCA04---A12 also offers diverse application flexibility, making it suitable for various locations, from small retail stores to large warehouses. With several tonnage options available, users can select a model that perfectly aligns with their specific cooling needs. Additionally, the unit can be easily integrated with existing HVAC systems, providing a seamless solution for upgrading or retrofitting older installations.

To sum up, the Carrier 48TCA04---A12 rooftop air conditioning unit stands out due to its exceptional energy efficiency, durable construction, advanced technology, and quiet operation, making it a reliable choice for commercial and industrial cooling solutions. Its flexibility and smart technology integrations ensure that it meets a wide range of climate control requirements effectively.