Carrier 48TCA04---A12 appendix Indoor Air Quality IAQ Sensor Input, Exhaust Setpoint Adjustment

Page 60

48TC

N1

 

 

EXH

TR

TR1

 

N

 

Set

 

 

 

2V

10V

 

 

 

 

 

 

P1

 

EXH

 

24

24 Vac

 

 

 

Vac

COM

 

P

 

 

 

 

Min

HOT

_

T1

 

 

Pos

+

 

 

 

T

Open

 

 

 

DCV

1

2

 

 

Max

 

 

 

 

 

2V

10V

 

 

AQ1

DCV

 

 

5

 

 

 

 

 

 

 

AQ

 

DCV

 

4

SO+

 

Set

3

SO

2V

10V

 

 

 

 

 

 

SR+

Free

 

EF

EF1

 

Cool

 

 

 

SR

B

C

 

 

 

A

D

 

 

C06038

Fig. 81 - EconoMi$er IV Control

Differential Enthalpy Control

For differential enthalpy control, the EconoMi$er IV controller uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return air duct. The EconoMi$er IV controller compares the outdoor air enthalpy to the return air enthalpy to determine EconoMi$er IV use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er IV opens to bring in outdoor air for free cooling.

Replace the standard outside air dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. (See Fig. 70.) Mount the return air enthalpy sensor in the return air duct. (See Fig. 79.) Wiring is provided in the EconoMi$er IV wiring harness. (See Fig. 70.) The outdoor enthalpy changeover setpoint is set with the outdoor enthalpy setpoint potentiometer on the EconoMi$er IV controller. When using this mode of changeover control, turn the enthalpy setpoint potentiometer fully clockwise to the D setting.

Indoor Air Quality (IAQ) Sensor Input

The IAQ input can be used for demand control ventilation control based on the level of CO2 measured in the space or return air duct.

Mount the accessory IAQ sensor according to manufacturer specifications. The IAQ sensor should be wired to the AQ and AQ1 terminals of the controller. Adjust the DCV potentiometers to correspond to the DCV voltage output of the indoor air quality sensor at the user-determined setpoint. (See Fig. 82.)

CO2 SENSOR MAX RANGE SETTING

 

6000

 

 

 

 

 

 

(ppm)

5000

 

 

 

 

 

 

 

 

 

 

 

 

 

CONFIGURATION

4000

 

 

 

 

 

800 ppm

 

 

 

 

 

 

3000

 

 

 

 

 

900 ppm

 

 

 

 

 

1000 ppm

 

 

 

 

 

 

2000

 

 

 

 

 

1100 ppm

 

 

 

 

 

 

 

 

 

 

 

 

 

RANGE

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

2

3

4

5

6

7

8

 

DAMPER VOLTAGE FOR MAX VENTILATION RATE

C06039

Fig. 82 - CO2 Sensor Maximum Range Settings

If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$er IV control board will be damaged.

When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC (volatile organic compounds) ventilation requirements. The maximum demand ventilation position is used for fully occupied ventilation.

When demand ventilation control is not being used, the minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation position should be turned fully clockwise.

Exhaust Setpoint Adjustment

The exhaust setpoint will determine when the exhaust fan runs based on damper position (if accessory power exhaust is installed). The setpoint is modified with the Exhaust Fan Setpoint (EXH SET) potentiometer. (See Fig. 76.) The setpoint represents the damper position above which the exhaust fans will be turned on. When there is a call for exhaust, the EconoMi$er IV controller provides a 45 ± 15 second delay before exhaust fan activation to allow the dampers to open. This delay allows the damper to reach the appropriate position to avoid unnecessary fan overload.

Minimum Position Control

There is a minimum damper position potentiometer on the EconoMi$er IV controller. (See Fig. 76.) The minimum damper position maintains the minimum airflow into the building during the occupied period.

When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements. The maximum demand ventilation position is used for fully occupied ventilation.

When demand ventilation control is not being used, the minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation position should be turned fully clockwise.

Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10_F temperature difference between the outdoor and return-air temperatures.

60

Image 60
Contents Table of Contents Safety ConsiderationsUnit Arrangement and Access Routine MaintenanceGeneral What to do if you smell gasSeasonal Maintenance Supply FAN Blower Section Supply Fan Belt-DriveCondenser Coil Maintenance and Cleaning Recommendation CoolingCondenser Coil Periodic Clean Water Rinse Routine Cleaning of Coil SurfacesRemove Surface Loaded Fibers One-Row CoilRefrigerant System Pressure Access Ports Cleaning the Evaporator CoilEvaporator Coil Evaporator Coil Metering DevicesTo Use Cooling Charging Charts Puronr R-410A RefrigerantRefrigerant Charge No ChargeCooling Charging Charts Size Designation Nominal Tons ReferenceCooling Charging Charts C08229 C08437 C08438 C08439 Cooling Service Analysis Problem Cause RemedyCondenser-Fan Adjustment Troubleshooting Cooling SystemConvenience Outlets CompressorSmoke Detectors SystemController Unit Connect Primary TransformerSensor Smoke Detector LocationsCompleting Installation of Return Air Smoke Sensor Fiop Smoke Detector Wiring and ResponseSensor Alarm Test Sensor Alarm Test ProcedureController Alarm Test Sensor and Controller TestsController Alarm Test Procedure Dirty Controller Test ProcedureDirty Sensor Test Procedure To Configure the Dirty Sensor Test OperationDetector Cleaning Troubleshooting Protective Devices GAS Heating SystemCompressor Protection Relief DeviceFuel Types and Pressures Natural Gas Supply Line Pressure RangesNatural Gas Manifold Pressure Ranges Liquid Propane Supply Line Pressure RangesFlue Gas Passageways Combustion-Air BlowerCleaning and Adjustment Check Unit Operation and Make Necessary Adjust- mentsBurners and Igniters Main BurnersLimit Switch Burner IgnitionOrifice Replacement LED Error Code DescriptionLED Indication Error Code Description Red LED-Status IGC Connections Orifice SizesAltitude Compensation* A04-A07 Cont. Altitude Compensation* A08-A12LP Orifice Troubleshooting Heating System Minimum heating entering air temperatureAltitude Compensation* A04-A06 Low NOx Units Heating Service Analysis Problem Cause RemedyIGC Board LED Alarm Codes IGCPremierlinkt Control PremierLink ControllerPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring Space Sensor Mode PremierLink Sensor UsageThermostat Mode 56 Internal ConnectionsLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection RTU-MP Control System Recommended CablesColor Code Recommendations RTU-MP Multi-Protocol Control Board RTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs OutputsSpace Temperature SPT Sensors RTU-MP T-55 Sensor ConnectionsIAQ Sensor SEN J4-2 COM J4-3 24 VAC Connecting Discrete Inputs Power Exhaust outputCommunication Wiring Protocols RTU-MP Troubleshooting LEDs LEDs on the RTU-MP show the status of certain functionsTroubleshooting Alarms Alarms BACnet MS/TPRTU-MP Driver Basic Protocol Troubleshooting ModbusManufacture Date Code Name MeaningEconomizer Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring EconoMi$er EconoMi$er IV Input/Output LogicSupply Air Temperature SAT Sensor Outdoor Air Lockout SensorEconoMi$er IV Control Modes Outdoor Dry Bulb ChangeoverReturn Air Temperature or Enthalpy Sensor Mounting Location Outdoor Enthalpy ChangeoverExhaust Setpoint Adjustment Indoor Air Quality IAQ Sensor InputMinimum Position Control Damper Movement ThermostatsOccupancy Control Demand Control Ventilation DCVCO2 Sensor Configuration EconoMi$er IV Sensor UsageEconoMi$er IV Preparation Differential EnthalpyWiring Diagrams 48TC Typical Unit Wiring Diagram Power A06, 208/230-3-60 48TC Unit Wiring Diagram Control A06 PRE-START-UP START-UP, GeneralCooling Main BurnersHeating Ventilation Continuous FanField Service Test START-UP, Premierlink ControlsSTART-UP, RTU-MP Control Perform System Check-OutConfiguration Inputs InputSpace Sensor Type Input 1 FunctionOperating Sequences Base Unit Controls Cooling, Units Without EconomizerHeating, Units Without Economizer Cooling, Unit With EconoMi$erHeating With EconoMi$er PremierLink Control48TC Available Cooling Stages OAT ≤ SPT 48TC 48TC Loadshed Command Gas and Electric Heat Units RTU-MP Sequence of OperationLinkage Modes SchedulingAlways Occupied Default Occupancy Local ScheduleBACnet Schedule BAS On/OffPower Exhaust EconomizerIndoor Air Quality Fastener Torque Values Demand LimitTorque Values Appendix I. Model Number Significance Model Number NomenclatureSerial Number Format Position NumberAppendix II. Physical Data Physical Data Cooling TonsPhysical Data Cooling 48TC*A08 48TC*A09 48TC*A12Physical Data Heating LOW Appendix III. FAN Performance General Fan Performance NotesTon Horizontal Supply Ton Vertical SupplyCFM RPM BHP Medium Static Option High Static Option 48TC**05 Phase Ton Horizontal Supply 48TC**0548TC**05 Phase Ton Vertical Supply 14931506 148648TC**06 148248TC**06 Phase Ton Horizontal Supply 48TC**06 Phase Ton Vertical SupplyPhase Ton Horizontal Supply 48TC**071107 11241103 1143 1122 1162497 10991116 1093 1133579 12631247 1273Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboAppendix IV. Electrical Data IFMRange RLA LRA TypeAppendix IV. Electrical Data FLAIFM Range EFF atRLA LRA FullCombustion Power NOM IFM No P.EFAN Motor Exhaust Type DISC. SizeUnbalanced 3-Phase Supply Voltage NOMAppendix V. Wiring Diagram List Wiring DiagramsAppendix VI. Motormaster Sensor Locations 48TC*A04 Outdoor Circuiting48TC*A09/12 Outdoor Circuiting Catalog No 48TC---2SMUnit START-UP Checklist Preliminary Information

48TCA04---A12 specifications

The Carrier 48TCA04---A12 is a high-efficiency rooftop air conditioning unit designed for commercial and industrial applications. Known for its reliability and performance, this model features advanced technologies that cater to diverse climate control needs.

One of the standout features of the Carrier 48TCA04---A12 is its excellent energy efficiency, which adheres to the stringent standards set by the U.S. Environmental Protection Agency. The unit utilizes a highly efficient scroll compressor combined with state-of-the-art heat exchanger technology, allowing it to operate with minimal energy consumption while providing powerful cooling capabilities.

The unit comes equipped with a robust and durable design, built to withstand various environmental conditions. Its weather-resistant cabinet is constructed from high-quality materials, ensuring long-lasting performance even in harsh climates. Additionally, the unit features a galvanized steel structure with a powder-coated finish, further enhancing its resistance to corrosion and wear.

In terms of technologies, the Carrier 48TCA04---A12 incorporates advanced controls that promote optimal performance. The unit supports Carrier's smart connectivity options, facilitating remote monitoring and adjustments via smart devices. This feature ensures convenient energy management and allows maintenance teams to access performance data, leading to proactive service interventions.

Another important characteristic of this unit is its quiet operation. The design includes sound-reducing insulation and a well-engineered airflow system, minimizing noise levels to create a more comfortable indoor environment. This is particularly important for commercial spaces such as offices and retail environments, where a tranquil atmosphere is critical for customer satisfaction and productivity.

The Carrier 48TCA04---A12 also offers diverse application flexibility, making it suitable for various locations, from small retail stores to large warehouses. With several tonnage options available, users can select a model that perfectly aligns with their specific cooling needs. Additionally, the unit can be easily integrated with existing HVAC systems, providing a seamless solution for upgrading or retrofitting older installations.

To sum up, the Carrier 48TCA04---A12 rooftop air conditioning unit stands out due to its exceptional energy efficiency, durable construction, advanced technology, and quiet operation, making it a reliable choice for commercial and industrial cooling solutions. Its flexibility and smart technology integrations ensure that it meets a wide range of climate control requirements effectively.