Carrier 48TCA04---A12 Remove Surface Loaded Fibers, Periodic Clean Water Rinse, One-Row Coil

Page 6

48TC

life of the coil and extend the life of the unit. The following maintenance and cleaning procedures are recommended as part of the routine maintenance activities to extend the life of the coil.

Remove Surface Loaded Fibers

Surface loaded fibers or dirt should be removed with a vacuum cleaner. If a vacuum cleaner is not available, a soft non-metallic bristle brush may be used. In either case, the tool should be applied in the direction of the fins. Coil surfaces can be easily damaged (fin edges can be easily bent over and damage to the coating of a protected coil) if the tool is applied across the fins.

NOTE: Use of a water stream, such as a garden hose, against a surface loaded coil will drive the fibers and dirt into the coil. This will make cleaning efforts more difficult. Surface loaded fibers must be completely removed prior to using low velocity clean water rinse.

Periodic Clean Water Rinse

A periodic clean water rinse is very beneficial for coils that are applied in coastal or industrial environments. However, it is very important that the water rinse is made with a very low velocity water stream to avoid damaging the fin edges. Monthly cleaning as described below is recommended.

Routine Cleaning of Coil Surfaces

Periodic cleaning with TotalineR environmentally sound coil cleaner is essential to extend the life of coils. This cleaner is available from Carrier Replacement Components Division as part number P902-0301 for a one gallon container, and part number P902-0305 for a 5 gallon container. It is recommended that all coils, including standard aluminum, pre-coated, copper/copper or E-coated coils be cleaned with the Totaline environmentally sound coil cleaner as described below. Coil cleaning should be part of the unit’s regularly scheduled maintenance procedures to ensure long life of the coil. Failure to clean the coils may result in reduced durability in the environment.

Avoid use of:

S coil brighteners

S acid cleaning prior to painting S high pressure washers

S poor quality water for cleaning

Totaline environmentally sound coil cleaner is nonflammable, hypo allergenic, non bacterial, and a USDA accepted biodegradable agent that will not harm the coil or surrounding components such as electrical wiring, painted metal surfaces, or insulation. Use of non-recommended coil cleaners is strongly discouraged since coil and unit durability could be affected.

One-Row Coil

Wash coil with commercial coil cleaner. It is not necessary to remove top panel.

Two-Row Coils

Clean coil as follows:

1.Turn off unit power, tag disconnect.

2.Remove top panel screws on condenser end of unit.

3.Remove condenser coil corner post. See Fig. 8. To hold top panel open, place coil corner post between top panel and center post. See Fig. 9.

C08205

Fig. 8 - Cleaning Condenser Coil

C08206

Fig. 9 - Propping Up Top Panel

4.Remove screws securing coil to compressor plate and compressor access panel.

5.Remove fastener holding coil sections together at re- turn end of condenser coil. Carefully separate the out- er coil section 3 to 4 in. from the inner coil section. See Fig. 10.

C08207

Fig. 10 - Separating Coil Sections

6

Image 6
Contents Table of Contents Safety ConsiderationsGeneral Unit Arrangement and AccessRoutine Maintenance What to do if you smell gasSeasonal Maintenance Supply FAN Blower Section Supply Fan Belt-DriveCondenser Coil Maintenance and Cleaning Recommendation CoolingCondenser Coil Remove Surface Loaded Fibers Periodic Clean Water RinseRoutine Cleaning of Coil Surfaces One-Row CoilEvaporator Coil Refrigerant System Pressure Access PortsCleaning the Evaporator Coil Evaporator Coil Metering DevicesRefrigerant Charge To Use Cooling Charging ChartsPuronr R-410A Refrigerant No ChargeCooling Charging Charts Size Designation Nominal Tons ReferenceCooling Charging Charts C08229 C08437 C08438 C08439 Cooling Service Analysis Problem Cause RemedyConvenience Outlets Condenser-Fan AdjustmentTroubleshooting Cooling System CompressorController Smoke DetectorsSystem Unit Connect Primary TransformerSensor Smoke Detector LocationsCompleting Installation of Return Air Smoke Sensor Fiop Smoke Detector Wiring and ResponseController Alarm Test Sensor Alarm TestSensor Alarm Test Procedure Sensor and Controller TestsDirty Sensor Test Procedure Controller Alarm Test ProcedureDirty Controller Test Procedure To Configure the Dirty Sensor Test OperationDetector Cleaning Troubleshooting Compressor Protection Protective DevicesGAS Heating System Relief DeviceNatural Gas Manifold Pressure Ranges Fuel Types and PressuresNatural Gas Supply Line Pressure Ranges Liquid Propane Supply Line Pressure RangesFlue Gas Passageways Combustion-Air BlowerBurners and Igniters Cleaning and AdjustmentCheck Unit Operation and Make Necessary Adjust- ments Main BurnersLimit Switch Burner IgnitionOrifice Replacement LED Error Code DescriptionLED Indication Error Code Description Red LED-Status IGC Connections Orifice SizesAltitude Compensation* A04-A07 Cont. Altitude Compensation* A08-A12LP Orifice Troubleshooting Heating System Minimum heating entering air temperatureAltitude Compensation* A04-A06 Low NOx Units Heating Service Analysis Problem Cause RemedyIGC Board LED Alarm Codes IGCPremierlinkt Control PremierLink ControllerPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring Space Sensor Mode PremierLink Sensor UsageThermostat Mode 56 Internal ConnectionsLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection RTU-MP Control System Recommended CablesColor Code Recommendations RTU-MP Multi-Protocol Control Board RTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs OutputsSpace Temperature SPT Sensors RTU-MP T-55 Sensor ConnectionsIAQ Sensor SEN J4-2 COM J4-3 24 VAC Connecting Discrete Inputs Power Exhaust outputCommunication Wiring Protocols RTU-MP Troubleshooting LEDs LEDs on the RTU-MP show the status of certain functionsTroubleshooting Alarms Alarms BACnet MS/TPRTU-MP Driver Manufacture Date Basic Protocol TroubleshootingModbus Code Name MeaningEconomizer Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring EconoMi$er EconoMi$er IV Input/Output LogicEconoMi$er IV Control Modes Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor Outdoor Dry Bulb ChangeoverReturn Air Temperature or Enthalpy Sensor Mounting Location Outdoor Enthalpy ChangeoverExhaust Setpoint Adjustment Indoor Air Quality IAQ Sensor InputMinimum Position Control Occupancy Control Damper MovementThermostats Demand Control Ventilation DCVEconoMi$er IV Preparation CO2 Sensor ConfigurationEconoMi$er IV Sensor Usage Differential EnthalpyWiring Diagrams 48TC Typical Unit Wiring Diagram Power A06, 208/230-3-60 48TC Unit Wiring Diagram Control A06 PRE-START-UP START-UP, GeneralHeating CoolingMain Burners Ventilation Continuous FanSTART-UP, RTU-MP Control Field Service TestSTART-UP, Premierlink Controls Perform System Check-OutConfiguration Space Sensor Type InputsInput Input 1 FunctionHeating, Units Without Economizer Operating SequencesBase Unit Controls Cooling, Units Without Economizer Cooling, Unit With EconoMi$erHeating With EconoMi$er PremierLink Control48TC Available Cooling Stages OAT ≤ SPT 48TC 48TC Linkage Modes Loadshed Command Gas and Electric Heat UnitsRTU-MP Sequence of Operation SchedulingBACnet Schedule Always Occupied Default OccupancyLocal Schedule BAS On/OffPower Exhaust EconomizerIndoor Air Quality Fastener Torque Values Demand LimitTorque Values Serial Number Format Appendix I. Model Number SignificanceModel Number Nomenclature Position NumberAppendix II. Physical Data Physical Data Cooling TonsPhysical Data Cooling 48TC*A08 48TC*A09 48TC*A12Physical Data Heating LOW Appendix III. FAN Performance General Fan Performance NotesTon Horizontal Supply Ton Vertical SupplyCFM RPM BHP Medium Static Option High Static Option 48TC**05 Phase Ton Horizontal Supply 48TC**051506 48TC**05 Phase Ton Vertical Supply1493 148648TC**06 148248TC**06 Phase Ton Horizontal Supply 48TC**06 Phase Ton Vertical SupplyPhase Ton Horizontal Supply 48TC**071103 1143 11071124 1122 11621116 4971099 1093 11331247 5791263 1273Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboRange RLA LRA Appendix IV. Electrical DataIFM TypeAppendix IV. Electrical Data FLARLA LRA IFM RangeEFF at FullFAN Motor Exhaust Combustion PowerNOM IFM No P.E Type DISC. SizeUnbalanced 3-Phase Supply Voltage NOMAppendix V. Wiring Diagram List Wiring DiagramsAppendix VI. Motormaster Sensor Locations 48TC*A04 Outdoor Circuiting48TC*A09/12 Outdoor Circuiting Catalog No 48TC---2SMUnit START-UP Checklist Preliminary Information

48TCA04---A12 specifications

The Carrier 48TCA04---A12 is a high-efficiency rooftop air conditioning unit designed for commercial and industrial applications. Known for its reliability and performance, this model features advanced technologies that cater to diverse climate control needs.

One of the standout features of the Carrier 48TCA04---A12 is its excellent energy efficiency, which adheres to the stringent standards set by the U.S. Environmental Protection Agency. The unit utilizes a highly efficient scroll compressor combined with state-of-the-art heat exchanger technology, allowing it to operate with minimal energy consumption while providing powerful cooling capabilities.

The unit comes equipped with a robust and durable design, built to withstand various environmental conditions. Its weather-resistant cabinet is constructed from high-quality materials, ensuring long-lasting performance even in harsh climates. Additionally, the unit features a galvanized steel structure with a powder-coated finish, further enhancing its resistance to corrosion and wear.

In terms of technologies, the Carrier 48TCA04---A12 incorporates advanced controls that promote optimal performance. The unit supports Carrier's smart connectivity options, facilitating remote monitoring and adjustments via smart devices. This feature ensures convenient energy management and allows maintenance teams to access performance data, leading to proactive service interventions.

Another important characteristic of this unit is its quiet operation. The design includes sound-reducing insulation and a well-engineered airflow system, minimizing noise levels to create a more comfortable indoor environment. This is particularly important for commercial spaces such as offices and retail environments, where a tranquil atmosphere is critical for customer satisfaction and productivity.

The Carrier 48TCA04---A12 also offers diverse application flexibility, making it suitable for various locations, from small retail stores to large warehouses. With several tonnage options available, users can select a model that perfectly aligns with their specific cooling needs. Additionally, the unit can be easily integrated with existing HVAC systems, providing a seamless solution for upgrading or retrofitting older installations.

To sum up, the Carrier 48TCA04---A12 rooftop air conditioning unit stands out due to its exceptional energy efficiency, durable construction, advanced technology, and quiet operation, making it a reliable choice for commercial and industrial cooling solutions. Its flexibility and smart technology integrations ensure that it meets a wide range of climate control requirements effectively.