Carrier 48TCA04---A12 appendix Alarms, BACnet MS/TP

Page 52

48TC

Alarms

Alarms can be checked through the network and/or the local access. All the alarms are listed in Table 23 with name, object name, action taken by control, reset method, and probable cause. There are help screens for each alarm on the local access display and listed in Form 48-50H-T-2T, Appendix A: Help Screens. Some alarms are explained in detail below.

Safety Chain Alarm

This alarm occurs immediately if the supply-fan internal overload trips or if an electric-heat limit switch trips. The Unit Status will be Shutdown and the System Mode will be Disable. When this happens LCTB (R terminal) will not have 24 VAC, but the RTU-MP board will still be powered. All unit operations stop immediately and will not restart until the alarm automatically clears. There are no configurations for this alarm; it is all based on internal wiring. This alarm will never occur if Fire Shutdown Alarm is active.

Fire Shutdown Alarm

This alarm occurs immediately when the smoke detector senses smoke. The Unit Status will be Shutdown and the System Mode will be Disable. All unit operations stop immediately and will not restart until the alarm automatically clears. If there is not a smoke detector installed or the smoke detector did not trip, check input configurations.

Space Temp Sensor Failure

This alarm occurs if the space sensor wired to the RTU-MP is disconnected or shorted for more then 10 seconds. When this occurs the Unit Status will be Shutdown and the System Mode will be Run. Sensor, sensor connections, wiring, board connection, and configurations should be checked for faults or errors. Alarm will reset automatically when cause is fixed.

SAT Sensor Alarm

This alarm occurs immediately when the supply air temperature sensor wired to the RTU-MP is disconnected or shorted. When this occurs the Unit Status will be Shutdown and the System Mode will be Run. Sensor, sensor connections, wiring, board connection, and configurations should be checked for faults or errors. Alarm will reset automatically when cause is fixed.

Switch Configuration Alarm

This occurs if more than one binary input (inputs 3, 5, 8, and 9) is configured for the same function. When this happens the two inputs (or more) configured wrong will be disabled as an inputs. This alarm will automatically be cleared when configuration is corrected.

An example of this would be: Input 3 = Compressor Safety, input 5 = Fan Status, input 8 = Fan Status, and input 9 = Humidistat; the alarm would be active, unit would run, compressor safety and humidistat would function normally, and Fan Status (inputs 5 & 8) will be interpreted as “No Function.”

Misconfigured Analog Input

This occurs if more than one analog input (inputs 1 & 2) is configured for the same sensor. When this happens the two inputs will be disabled as inputs. This alarm will automatically be cleared when configuration is corrected.

An example of this would be: Input 1 = IAQ Sensor, input 2 = IAQ Sensor; the alarm would be active, unit would run, but the IAQ Sensor (inputs 1 & 2) will be interpreted as “No Function.”

Third Party Networking

Third party communication and networking troubleshooting should be done by or with assistance from the front end 3rd party technician. A Module Status Report (Modstat) can be run from the BACview6, see Table 24 to perform. This lists information about the board status and networking state. For basic troubleshooting, see Table 25. Refer to the RTU-MP 3rd Party Integration Guide for additional information.

BACnet MS/TP

1.Verify that the BAS and controller are both set to speak the BACnet MS/TP protocol. The protocol of the controller is set via SW3 (switches 3, 4, 5, and 6). The protocol can also be verified by getting a Modstat of the controller through the BACview. Hit the “FN” key and the ’.’ key at the same time to pull up a Modstat. Scroll to the bottom of the page and there is a section entitled “Network Communications.” The active protocol and baud rate will be shown in this section.

2.Verify that the BAS and controller are set for the same baud rate. The baud rate of the controller is set via SW3 (switches 1 and 2). The baud rate can also be verified via the BACview by obtaining a Modstat. (See Fig. 67.)

3.Verify that the BAS is configured to speak 2-wire EIA-485 to the controller. The BAS may have to con- figure jumper or DIP switches on their end.

4.Verify that the BAS and the controller have the same communication settings (8 data bits, No Parity, and 1 stop bit).

5.Verify that the controller has a unique MAC address on the MS/TP bus. The controller’s MS/TP MAC ad- dress is set by its rotary address switches.

6.Verify proper wiring between the BAS and the con- troller.

7.Verify that the BAS is reading or writing to the proper BACnet objects in the controller. Download the latest points list for the controller to verify.

8.Verify that the BAS is sending his requests to the proper MS/TP MAC address of our controller.

9.Present the BAS company with a copy of our control- ler’s BACnet PICS so that they know which BACnet commands are supported. See below.

10.In certain situations, it may be necessary to tweak the MS/TP Protocol timing settings through the BAC- view6. There are two settings that may be tweaked:

52

Image 52
Contents Table of Contents Safety ConsiderationsUnit Arrangement and Access Routine MaintenanceGeneral What to do if you smell gasSeasonal Maintenance Supply FAN Blower Section Supply Fan Belt-DriveCooling Condenser Coil Maintenance and Cleaning RecommendationCondenser Coil Periodic Clean Water Rinse Routine Cleaning of Coil SurfacesRemove Surface Loaded Fibers One-Row CoilRefrigerant System Pressure Access Ports Cleaning the Evaporator CoilEvaporator Coil Evaporator Coil Metering DevicesTo Use Cooling Charging Charts Puronr R-410A RefrigerantRefrigerant Charge No ChargeCooling Charging Charts Size Designation Nominal Tons ReferenceCooling Charging Charts C08229 C08437 C08438 C08439 Cooling Service Analysis Problem Cause RemedyCondenser-Fan Adjustment Troubleshooting Cooling SystemConvenience Outlets CompressorSmoke Detectors SystemController Unit Connect Primary TransformerSensor Smoke Detector LocationsCompleting Installation of Return Air Smoke Sensor Fiop Smoke Detector Wiring and ResponseSensor Alarm Test Sensor Alarm Test ProcedureController Alarm Test Sensor and Controller TestsController Alarm Test Procedure Dirty Controller Test ProcedureDirty Sensor Test Procedure To Configure the Dirty Sensor Test OperationDetector Cleaning Troubleshooting Protective Devices GAS Heating SystemCompressor Protection Relief DeviceFuel Types and Pressures Natural Gas Supply Line Pressure RangesNatural Gas Manifold Pressure Ranges Liquid Propane Supply Line Pressure RangesFlue Gas Passageways Combustion-Air BlowerCleaning and Adjustment Check Unit Operation and Make Necessary Adjust- mentsBurners and Igniters Main BurnersLimit Switch Burner IgnitionLED Error Code Description Orifice ReplacementLED Indication Error Code Description Red LED-Status IGC Connections Orifice SizesCont. Altitude Compensation* A08-A12 Altitude Compensation* A04-A07LP Orifice Minimum heating entering air temperature Troubleshooting Heating SystemAltitude Compensation* A04-A06 Low NOx Units Heating Service Analysis Problem Cause RemedyIGC Board LED Alarm Codes IGCPremierlinkt Control PremierLink ControllerPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring Space Sensor Mode PremierLink Sensor UsageThermostat Mode 56 Internal ConnectionsLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection Recommended Cables RTU-MP Control SystemColor Code Recommendations RTU-MP Multi-Protocol Control Board RTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs OutputsSpace Temperature SPT Sensors RTU-MP T-55 Sensor ConnectionsIAQ Sensor SEN J4-2 COM J4-3 24 VAC Power Exhaust output Connecting Discrete InputsCommunication Wiring Protocols RTU-MP Troubleshooting LEDs LEDs on the RTU-MP show the status of certain functionsTroubleshooting Alarms Alarms BACnet MS/TPRTU-MP Driver Basic Protocol Troubleshooting ModbusManufacture Date Code Name MeaningEconomizer Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring EconoMi$er EconoMi$er IV Input/Output LogicSupply Air Temperature SAT Sensor Outdoor Air Lockout SensorEconoMi$er IV Control Modes Outdoor Dry Bulb ChangeoverReturn Air Temperature or Enthalpy Sensor Mounting Location Outdoor Enthalpy ChangeoverIndoor Air Quality IAQ Sensor Input Exhaust Setpoint AdjustmentMinimum Position Control Damper Movement ThermostatsOccupancy Control Demand Control Ventilation DCVCO2 Sensor Configuration EconoMi$er IV Sensor UsageEconoMi$er IV Preparation Differential EnthalpyWiring Diagrams 48TC Typical Unit Wiring Diagram Power A06, 208/230-3-60 48TC Unit Wiring Diagram Control A06 PRE-START-UP START-UP, GeneralCooling Main BurnersHeating Ventilation Continuous FanField Service Test START-UP, Premierlink ControlsSTART-UP, RTU-MP Control Perform System Check-OutConfiguration Inputs InputSpace Sensor Type Input 1 FunctionOperating Sequences Base Unit Controls Cooling, Units Without EconomizerHeating, Units Without Economizer Cooling, Unit With EconoMi$erHeating With EconoMi$er PremierLink Control48TC Available Cooling Stages OAT ≤ SPT 48TC 48TC Loadshed Command Gas and Electric Heat Units RTU-MP Sequence of OperationLinkage Modes SchedulingAlways Occupied Default Occupancy Local ScheduleBACnet Schedule BAS On/OffEconomizer Power ExhaustIndoor Air Quality Demand Limit Fastener Torque ValuesTorque Values Appendix I. Model Number Significance Model Number NomenclatureSerial Number Format Position NumberAppendix II. Physical Data Physical Data Cooling TonsPhysical Data Cooling 48TC*A08 48TC*A09 48TC*A12Physical Data Heating LOW Appendix III. FAN Performance General Fan Performance NotesTon Vertical Supply Ton Horizontal SupplyCFM RPM BHP Medium Static Option High Static Option 48TC**05 Phase Ton Horizontal Supply 48TC**0548TC**05 Phase Ton Vertical Supply 14931506 148648TC**06 148248TC**06 Phase Ton Horizontal Supply 48TC**06 Phase Ton Vertical SupplyPhase Ton Horizontal Supply 48TC**071107 11241103 1143 1122 1162497 10991116 1093 1133579 12631247 1273Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboAppendix IV. Electrical Data IFMRange RLA LRA TypeAppendix IV. Electrical Data FLAIFM Range EFF atRLA LRA FullCombustion Power NOM IFM No P.EFAN Motor Exhaust Type DISC. SizeUnbalanced 3-Phase Supply Voltage NOMAppendix V. Wiring Diagram List Wiring DiagramsAppendix VI. Motormaster Sensor Locations 48TC*A04 Outdoor Circuiting48TC*A09/12 Outdoor Circuiting Catalog No 48TC---2SMUnit START-UP Checklist Preliminary Information

48TCA04---A12 specifications

The Carrier 48TCA04---A12 is a high-efficiency rooftop air conditioning unit designed for commercial and industrial applications. Known for its reliability and performance, this model features advanced technologies that cater to diverse climate control needs.

One of the standout features of the Carrier 48TCA04---A12 is its excellent energy efficiency, which adheres to the stringent standards set by the U.S. Environmental Protection Agency. The unit utilizes a highly efficient scroll compressor combined with state-of-the-art heat exchanger technology, allowing it to operate with minimal energy consumption while providing powerful cooling capabilities.

The unit comes equipped with a robust and durable design, built to withstand various environmental conditions. Its weather-resistant cabinet is constructed from high-quality materials, ensuring long-lasting performance even in harsh climates. Additionally, the unit features a galvanized steel structure with a powder-coated finish, further enhancing its resistance to corrosion and wear.

In terms of technologies, the Carrier 48TCA04---A12 incorporates advanced controls that promote optimal performance. The unit supports Carrier's smart connectivity options, facilitating remote monitoring and adjustments via smart devices. This feature ensures convenient energy management and allows maintenance teams to access performance data, leading to proactive service interventions.

Another important characteristic of this unit is its quiet operation. The design includes sound-reducing insulation and a well-engineered airflow system, minimizing noise levels to create a more comfortable indoor environment. This is particularly important for commercial spaces such as offices and retail environments, where a tranquil atmosphere is critical for customer satisfaction and productivity.

The Carrier 48TCA04---A12 also offers diverse application flexibility, making it suitable for various locations, from small retail stores to large warehouses. With several tonnage options available, users can select a model that perfectly aligns with their specific cooling needs. Additionally, the unit can be easily integrated with existing HVAC systems, providing a seamless solution for upgrading or retrofitting older installations.

To sum up, the Carrier 48TCA04---A12 rooftop air conditioning unit stands out due to its exceptional energy efficiency, durable construction, advanced technology, and quiet operation, making it a reliable choice for commercial and industrial cooling solutions. Its flexibility and smart technology integrations ensure that it meets a wide range of climate control requirements effectively.