Carrier 48TCA04---A12 RTU-MP Control System, Recommended Cables, Color Code Recommendations

Page 42

48TC

At any baud (9600, 19200, 38400 baud), the number of controllers is limited to 239 devices maximum. Bus length may not exceed 4000 ft, with no more than 60 total devices on any 1000-ft section. Optically isolated RS-485 repeaters are required every 1000 ft.

NOTE: Carrier device default is 9600 band.

COMMUNICATION BUS WIRE SPECIFICATIONS — The CCN Communication Bus wiring is field-supplied and field-installed. It consists of shielded 3-conductor cable with drain (ground) wire. The cable selected must be identical to the CCN Communication Bus wire used for the entire network.

See Table 19 for recommended cable.

Table 19 – Recommended Cables

MANUFACTURER

CABLE PART NO.

Alpha

2413 or 5463

American

A22503

Belden

8772

Columbia

02525

NOTE: Conductors and drain wire must be at least 20 AWG, stranded, and tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of -20 C to 60 C is required. Do not run communication wire in the same conduit as or next to any AC voltage wiring.

The communication bus shields must be tied together at each system element. If the communication bus is entirely within one building, the resulting continuous shield must be connected to ground at only one single point. If the communication bus cable exits from one building and enters another building, the shields must be connected to the grounds at a lightning suppressor in each building (one point only).

Connecting CCN bus:

NOTE: When connecting the communication bus cable, a color code system for the entire network is recommended to simplify installation and checkout. See Table 20 for the recommended color code.

Table 20 – Color Code Recommendations

SIGNAL TYPE

CCN BUS WIRE

CCN PLUG PIN

COLOR

NUMBER

 

 

 

 

+

Red

1

 

 

 

Ground

White

2

---

Black

3

 

 

 

Connect the CCN (+) lead (typically RED) to the unit￿s TB1-12 terminal. Connect the CCN (ground) lead (typically WHT) to the unit’s TB1-14 terminal. Connect the CCN (-) lead (typically BLK) to the unit’s TB1-16 terminal. See Fig. 58.

CCN Bus

 

 

 

 

TB1

PL

+ (RED)

12

 

J2-1

 

TB1

GND (WHT) 14 J2-2

TB1

– (BLK) 16 J2-3

C08276

Fig. 58 - PremierLink CCN Bus Connections

RTU-MP CONTROL SYSTEM

The RTU-MP controller, see Fig. 59, provides expanded stand-alone operation of the HVAC system plus connection and control through communication with several Building Automation Systems (BAS) through popular third-party network systems. The available network systems are BACnet MP/TP, Modbus and Johnson J2. Communication with LonWorks is also possible by adding an accessory interface card to the RTU-MP. Selection of the communication protocol and baud rate are made at on-board DIP switches.

Carrier’s diagnostic display tools BACviewer6 Handheld and Virtual BACview (loaded on a portable PC) must be used with the RTU-MP controller. Connection to the RTU-MP board is at the J12 access port, see Fig. 59.

The RTU-MP control is factory-mounted in the 48TC unit’s main control box, to the left of the LCTB. See Fig.

60.Factory wiring is completed through harnesses connected to the LCTB. Field connections for RTU-MP sensors will be made at the Phoenix connectors on the RTU-MP board. The factory-installed RTU-MP control includes the supply-air temperature (SAT) sensor. The outdoor air temperature (OAT) sensor is included in the FIOP/accessory EconoMi$er 2 package.

Refer to Table 21, RTU-MP Controller Inputs and Outputs for locations of all connections to the RTU-MP board.

42

Image 42
Contents Table of Contents Safety ConsiderationsGeneral Unit Arrangement and AccessRoutine Maintenance What to do if you smell gasSeasonal Maintenance Supply FAN Blower Section Supply Fan Belt-DriveCondenser Coil Maintenance and Cleaning Recommendation CoolingCondenser Coil Remove Surface Loaded Fibers Periodic Clean Water RinseRoutine Cleaning of Coil Surfaces One-Row CoilEvaporator Coil Refrigerant System Pressure Access PortsCleaning the Evaporator Coil Evaporator Coil Metering DevicesRefrigerant Charge To Use Cooling Charging ChartsPuronr R-410A Refrigerant No ChargeCooling Charging Charts Size Designation Nominal Tons ReferenceCooling Charging Charts C08229 C08437 C08438 C08439 Cooling Service Analysis Problem Cause RemedyConvenience Outlets Condenser-Fan AdjustmentTroubleshooting Cooling System CompressorController Smoke DetectorsSystem Unit Connect Primary TransformerSensor Smoke Detector LocationsCompleting Installation of Return Air Smoke Sensor Fiop Smoke Detector Wiring and ResponseController Alarm Test Sensor Alarm TestSensor Alarm Test Procedure Sensor and Controller TestsDirty Sensor Test Procedure Controller Alarm Test ProcedureDirty Controller Test Procedure To Configure the Dirty Sensor Test OperationDetector Cleaning Troubleshooting Compressor Protection Protective DevicesGAS Heating System Relief DeviceNatural Gas Manifold Pressure Ranges Fuel Types and PressuresNatural Gas Supply Line Pressure Ranges Liquid Propane Supply Line Pressure RangesFlue Gas Passageways Combustion-Air BlowerBurners and Igniters Cleaning and AdjustmentCheck Unit Operation and Make Necessary Adjust- ments Main BurnersLimit Switch Burner IgnitionOrifice Replacement LED Error Code DescriptionLED Indication Error Code Description Red LED-Status IGC Connections Orifice SizesAltitude Compensation* A04-A07 Cont. Altitude Compensation* A08-A12LP Orifice Troubleshooting Heating System Minimum heating entering air temperatureAltitude Compensation* A04-A06 Low NOx Units Heating Service Analysis Problem Cause RemedyIGC Board LED Alarm Codes IGCPremierlinkt Control PremierLink ControllerPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring Space Sensor Mode PremierLink Sensor UsageThermostat Mode 56 Internal ConnectionsLctb Indoor CO2 Sensor 33ZCSENCO2 Connections PremierLink Filter Switch Connection RTU-MP Control System Recommended CablesColor Code Recommendations RTU-MP Multi-Protocol Control Board RTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs OutputsSpace Temperature SPT Sensors RTU-MP T-55 Sensor ConnectionsIAQ Sensor SEN J4-2 COM J4-3 24 VAC Connecting Discrete Inputs Power Exhaust outputCommunication Wiring Protocols RTU-MP Troubleshooting LEDs LEDs on the RTU-MP show the status of certain functionsTroubleshooting Alarms Alarms BACnet MS/TPRTU-MP Driver Manufacture Date Basic Protocol TroubleshootingModbus Code Name MeaningEconomizer Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring EconoMi$er EconoMi$er IV Input/Output LogicEconoMi$er IV Control Modes Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor Outdoor Dry Bulb ChangeoverReturn Air Temperature or Enthalpy Sensor Mounting Location Outdoor Enthalpy ChangeoverExhaust Setpoint Adjustment Indoor Air Quality IAQ Sensor InputMinimum Position Control Occupancy Control Damper MovementThermostats Demand Control Ventilation DCVEconoMi$er IV Preparation CO2 Sensor ConfigurationEconoMi$er IV Sensor Usage Differential EnthalpyWiring Diagrams 48TC Typical Unit Wiring Diagram Power A06, 208/230-3-60 48TC Unit Wiring Diagram Control A06 PRE-START-UP START-UP, GeneralHeating CoolingMain Burners Ventilation Continuous FanSTART-UP, RTU-MP Control Field Service TestSTART-UP, Premierlink Controls Perform System Check-OutConfiguration Space Sensor Type InputsInput Input 1 FunctionHeating, Units Without Economizer Operating SequencesBase Unit Controls Cooling, Units Without Economizer Cooling, Unit With EconoMi$erHeating With EconoMi$er PremierLink Control48TC Available Cooling Stages OAT ≤ SPT 48TC 48TC Linkage Modes Loadshed Command Gas and Electric Heat UnitsRTU-MP Sequence of Operation SchedulingBACnet Schedule Always Occupied Default OccupancyLocal Schedule BAS On/OffPower Exhaust EconomizerIndoor Air Quality Fastener Torque Values Demand LimitTorque Values Serial Number Format Appendix I. Model Number SignificanceModel Number Nomenclature Position NumberAppendix II. Physical Data Physical Data Cooling TonsPhysical Data Cooling 48TC*A08 48TC*A09 48TC*A12Physical Data Heating LOW Appendix III. FAN Performance General Fan Performance NotesTon Horizontal Supply Ton Vertical SupplyCFM RPM BHP Medium Static Option High Static Option 48TC**05 Phase Ton Horizontal Supply 48TC**051506 48TC**05 Phase Ton Vertical Supply1493 148648TC**06 148248TC**06 Phase Ton Horizontal Supply 48TC**06 Phase Ton Vertical SupplyPhase Ton Horizontal Supply 48TC**071103 1143 11071124 1122 11621116 4971099 1093 11331247 5791263 1273Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboRange RLA LRA Appendix IV. Electrical DataIFM TypeAppendix IV. Electrical Data FLARLA LRA IFM RangeEFF at FullFAN Motor Exhaust Combustion PowerNOM IFM No P.E Type DISC. SizeUnbalanced 3-Phase Supply Voltage NOMAppendix V. Wiring Diagram List Wiring DiagramsAppendix VI. Motormaster Sensor Locations 48TC*A04 Outdoor Circuiting48TC*A09/12 Outdoor Circuiting Catalog No 48TC---2SMUnit START-UP Checklist Preliminary Information

48TCA04---A12 specifications

The Carrier 48TCA04---A12 is a high-efficiency rooftop air conditioning unit designed for commercial and industrial applications. Known for its reliability and performance, this model features advanced technologies that cater to diverse climate control needs.

One of the standout features of the Carrier 48TCA04---A12 is its excellent energy efficiency, which adheres to the stringent standards set by the U.S. Environmental Protection Agency. The unit utilizes a highly efficient scroll compressor combined with state-of-the-art heat exchanger technology, allowing it to operate with minimal energy consumption while providing powerful cooling capabilities.

The unit comes equipped with a robust and durable design, built to withstand various environmental conditions. Its weather-resistant cabinet is constructed from high-quality materials, ensuring long-lasting performance even in harsh climates. Additionally, the unit features a galvanized steel structure with a powder-coated finish, further enhancing its resistance to corrosion and wear.

In terms of technologies, the Carrier 48TCA04---A12 incorporates advanced controls that promote optimal performance. The unit supports Carrier's smart connectivity options, facilitating remote monitoring and adjustments via smart devices. This feature ensures convenient energy management and allows maintenance teams to access performance data, leading to proactive service interventions.

Another important characteristic of this unit is its quiet operation. The design includes sound-reducing insulation and a well-engineered airflow system, minimizing noise levels to create a more comfortable indoor environment. This is particularly important for commercial spaces such as offices and retail environments, where a tranquil atmosphere is critical for customer satisfaction and productivity.

The Carrier 48TCA04---A12 also offers diverse application flexibility, making it suitable for various locations, from small retail stores to large warehouses. With several tonnage options available, users can select a model that perfectly aligns with their specific cooling needs. Additionally, the unit can be easily integrated with existing HVAC systems, providing a seamless solution for upgrading or retrofitting older installations.

To sum up, the Carrier 48TCA04---A12 rooftop air conditioning unit stands out due to its exceptional energy efficiency, durable construction, advanced technology, and quiet operation, making it a reliable choice for commercial and industrial cooling solutions. Its flexibility and smart technology integrations ensure that it meets a wide range of climate control requirements effectively.