Desa SBVBP installation manual Installing GAS Piping to Stove Location, Installation Items Needed

Page 13

CAST IRON STOVE AND B-VENT BURNER SYSTEM INSTALLATION

Installing Gas Piping to Stove Location

13

CAST IRON STOVE AND B-VENT BURNER SYSTEM INSTALLATION

Continued

INSTALLING GAS PIPING TO STOVE LOCATION

WARNING: A qualified installer or service person must connect burner system to gas supply. Follow all local codes.

CAUTION: For propane/LP units, never connect burner system directly to the propane/LP supply. This burner system requires an external regulator (not supplied). Install the external regulator between the burner system and propane/LP supply.

Installation Items Needed

Before installing stove and burner system, make sure you have the items listed below.

• external regulator (supplied by installer)

• piping (check local codes)

• sealant (resistant to propane/LP gas)

• equipment shutoff valve *

• test gauge connection *

sediment trap

tee joint

pipe wrench

• approved flexible gas line with gas connector (if allowed by lo-

 

cal codes) (not provided)

Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from burner system (see Figure 28).

Check your building codes for any special requirements for locating equipment shutoff valve to stoves.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged burner system valves.

WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

External

Regulator

Propane/LP

Supply Tank

Vent Pointing

Down

Figure 27 - External Regulator with Vent Pointing Down (Propane/LP Only)

*A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the CSA design-certified equipment shutoff valve from your dealer.

For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 27. Pointing the vent down protects it from freezing rain or sleet.

Approved Flexible

Gas Line

3" Minimum

CSA Design-Certified Equipment Shutoff Valve with 1/8" NPT Tap*

Natural - From Gas Meter (5" W.C. to 10.5" W.C. Pressure )

LP - From External Regulator (11" W.C. to 14" W.C. Pressure)

CAUTION: Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in cer- tain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to burner system. If pipe is too small, undue loss of volume will occur.

Cap Pipe Nipple Tee Joint

Sediment Trap/Drip Leg

*The CSA design-certified equipment shutoff valve may be sup- plied with the appliance or you can purchase it from your dealer.

Figure 28 - Gas Connection

For morevisit www..com

112127-01B

Image 13
Contents For Your Safety What to do if YOU Smell GAS For Your SafetyVH series Stove Series StoveSafety Information Table of ContentsProduct Identification PRE-INSTALLATION Preparation Product FeaturesLocal Codes Stove Body Assembly Cast Iron Stove and B-VENT Burner System AssemblyRemoving Screen Optional Removing Front Surround PanelAmity Models Oxford or Victor Hearth ModelsInstalling Optional Blower Accessory Installing B-VENT Burner System Into Stove BodySecurely in place before venting pipes are installed Installing Rear CoverInstallation Precautions Venting InstallationVertical Checking Vent CapacityChimneys High Altitude InstallationRelining Systems Cast Iron Stove and B-VENT Burner System Installation Troubleshooting Venting ProblemsFlue GAS Spillage Causes of Spillage and Corrective ActionInstallation Items Needed Installing GAS Piping to Stove LocationPressure Testing Gas Supply Piping System Connecting STOVE/BURNER System to GAS SupplyChecking GAS Connections Test Pressures In Excess Of 1/2 Psig 3.5 kPaInstalling Optional Wall Mounted Thermostat GWMT1 Installing Optional Wall Mount Switch GWMS2Pressure Testing Burner System Gas Connections Will occurInstalling Battery in Receiver Installing Remote ReceiverREMOVING/REPLACING Glass Door Installing 9-Volt Battery in Hand-Held Remote Control UnitRemove glass door. See Removing/Replacing Glass Door, Installing LOGS, Lava ROCK, and Glowing EmbersOperating Stove with B-VENT Burner System For Your Safety Read Before LightingLighting Instructions To Turn OFF GAS To ApplianceOptional Remote Thermostat Series Operation Operating Stove with Vent Burner SystemON/OFF Series Models Ghrcb and Cghrcb Pilot Assembly Operating Optional Blower AccessoryInspecting Burners Operating Optional GWMT1 Wall Mounted ThermostatGlass Door Cleaning MaintenancePilot and Burners LogsObserved Problem Possible Cause TroubleshootingObserved Problem Possible Cause Remedy Above Gas leak. See Warning statementTechnical Service Replacement PartsWiring Diagram Service HintsSbvbnd Sbvbpd SpecificationsModels Sbvbnd and Sbvbpd Illustrated Parts BreakdownKEY Part Number Description QTY Parts ListStove Body Indicates Color Suffix Designation Oxford AmityVictor Hearth Stove Body Description QTY Indicates Color Suffix DesignationReceiver and HAND-HELD Remote Control KIT Ghrcb and Cghrcb AccessoriesTHERMOSTATICALLY- Controlled Blower KIT CDA3620TB Stove Hearth Base GC10SPAOwners Registration Form Postage Required 112127-01B Warranty Information