STARTING THE BOILER
10. STARTING THE BOILER
A.CHECK THE PIPING
1.Water and Steam Piping
a.The Boiler must have been hydrostatically tested.
b.Check the attached piping for joint tightness.
c.Continue monitoring as you proceed through start up.
2.Gas Piping
a.Make sure the gas system piping and the connections to the boiler Gas Control Train(s) have been leak tested.
b.After the boiler is in operation, check the tightness of all joints in the boiler gas piping with a soap suds solution.
c.Purge the gas piping of all air up to the boiler Gas Control Train.
B.FILL THE BOILER
1.Fill the boiler to the normal water line.
a.Gravity Systems and Pumped Return with Condensate Units Fill to
b.Pumped Return with Boiler Feed
C.STUDY LIGHTING INSTRUCTIONS
1.Before starting the boiler, study the Lighting Instructions supplied with the boiler.
D.RUN PILOT CHECK-OUT
1.Shut off all electrical power to the boiler.
2.Close Main and Pilot gas
3.Set the Operating and Limit Pressure Controls to minimum setting so they will not call for heat.
4.Perform Pilot Check:
a.Turn main electric disconnect switch to the ON position.
b.Turn up the settings on the Operating and Limit Pressure Controls so they will call for heat.
c.Check for a continuous spark at the electronic
d.Electronic
e.Electronic standing pilot
f.Turn down the Operating Pressure Control to stop the call for heat.
g.Wait 60 seconds to allow the control to reset before proceeding with the next step.
5.Light Manual Pilots
a.Follow the procedure in the Lighting Instructions to manually light any standing pilots.
6.Electronic
a.Turn up the Operating Pressure Control for a call for heat.
b.The electronic
c.Turn down the Operating Pressure Control to stop the call for heat.
d.The
7.Check Main Burner Ignition
a.With the Operating Pressure Control turned down, open the main gas
b.Turn up the Operating Pressure Control for a call for heat.
c.The electronic
d.The main gas valves will then open and the main burners should ignite.
e.Turn down the Operating Pressure Control to stop the call for heat.
f.The electronic
E.CHECK MAIN BURNER SYSTEM
1.Remove the pressure test plug at the Main gas shut- off valve. Attach a
2.Restart the boiler by turning up the Operating Pressure Control for a call for heat.
3.Leak test all gas train joints with a soap suds solution.
4.Check the gas pressure at the entrance to the Gas Control train.
a.The pressure reading under flow should be between 5 and 14 inches water column (1.7 and
3.5kPa).
b.If the pressure to the Gas Control Train exceeds 14 inches (3.5 kPa) under any conditions, the system must be provided with a lockup type gas pressure regulator to provide 14 inches (3.5 kPa) maximum.
5.Check the Manifold gas pressure.
a.Remove the 1/8" pipe plug from the manifold gas pressure tapping.
b.Attach a
c.Adjust the Main Gas Pressure Regulator to obtain
3.5inches water column (.9 kPa) on Natural Gas 10 inches water column (2.5 kPa) on Propane (LP) Gas.
d.NOTE: If the pressure is adjusted to set the nameplate input to the boiler, do not set it more than 0.3 inches (75 Pa) plus or minus from the specified settings. If more adjustment to the rate is needed, it must be done by changing the burner gas orifices.
40