TROUBLESHOOTING – SERVICE TIPS
13. TROUBLESHOOTING – SERVICE TIPS
Problem | Possible Cause | Suggested Remedy | |
|
|
| |
| Defective Thermocouple | Replace | |
|
|
| |
| Heavy Draft Blowing across Pilot | Redirect Air Movement or Eliminate | |
|
|
| |
| Plugged Pilot Orifice | Replace Orifice | |
|
|
| |
Pilot Outage |
| Check Manual Pilot Valve | |
| No Gas | Check Main Gas | |
| Check Manual Meter Valve | ||
|
| ||
|
| Consult Gas Company | |
|
|
| |
| Defective Thermopilot Valve | Replace | |
|
|
| |
| Defective Ignition Control | Replace | |
|
|
| |
| No Power | Check Power Source with Meter | |
| Check Fuses | ||
|
| ||
|
|
| |
| Defective Gas Valve | Replace | |
|
|
| |
| Defective Thermocouple | Replace | |
|
|
| |
| Low Water Level in Boiler | Check for Leaks | |
Main Gas Valve Will Not Open | or System Causing Low Water | Check Feeder (if Supplied) | |
(Standard |
|
| |
Defective Thermopilot Valve | Replace | ||
|
|
| |
| Defective Ignition Control | Replace | |
|
|
| |
| High Gas Pressure Switch Open | Check Switch Setting | |
| (if Provided) | Check Manifold Gas Pressure | |
|
|
| |
| Low Gas Pressure Switch Open | Check Switch Setting | |
| (if Provided) | Check Manifold Gas Pressure | |
|
|
| |
| No Power | Check Power Source with Meter | |
| Check Fuses | ||
|
| ||
|
|
| |
| Defective Gas Valve | Replace | |
|
|
| |
| Relay Locked Out on Safety | Check for Pilot Outage | |
|
|
| |
| Pilot Out | Relight Pilot | |
| (May have defective pilot valve or relay) | ||
|
| ||
|
|
| |
Main Gas Valve Will Not Open | Defective Relay | Replace | |
(Electronic Standing Pilot System) | Low Water in Boiler | Check for Leaks | |
| or System Causing Low Water | Check Feeder (if Supplied) | |
|
|
| |
| Defective Thermopilot Valve(s) | Replace | |
|
|
| |
| Defective Thermocouple(s) | Replace | |
|
|
| |
| High Gas Pressure Switch Open | Check Switch Setting | |
| (if Provided) | Check Manifold Gas Pressure | |
|
|
| |
| Low Gas Pressure Switch Open | Check Switch Setting | |
| (if Provided) | Check Inlet Gas Pressure | |
|
|
| |
| Air Adjustment Screws Turned in Too Far | Adjust Screws Out | |
|
|
| |
| Low Gas Pressure in Manifold | Adjust Main Gas Pressure Regulator | |
| (Insufficient Air Injection) | or Check Line Pressure | |
|
|
| |
| Burner Ports Partially Closed (Rust, Dirt, Lint, etc.) | Replace Burners or Clean Ports | |
|
|
| |
Burner(s) Burning with Yellow Flame |
| Check Size of Combustion Air Openings to | |
| Insufficient Air for Combustion | Room, if Undersized, Correct as Required | |
|
| Check for Negative Pressure in Boiler Room | |
|
|
| |
| Oversized Burner Orifice | Install Correct Orifice | |
|
|
| |
| High Gas Pressure in Manifold | Adjust Main Gas Pressure Regulator | |
|
|
| |
| Insufficient Draft – Chimney Too Low | Increase Height or Add Induced Draft Fan | |
|
|
| |
| Insufficient Draft – Chimney Too Small | Replace Chimney or Add Induced Draft Fan | |
|
|
| |
Gas Spillage from | Insufficient Draft – Blockage in Chimney or Vent | Repair Chimney or Vent | |
|
| ||
Insufficient Draft – Downdraft Caused by |
| ||
Draft Hood Relief Opening |
| ||
Chimney Location with Respect to | Install Chimney Cap | ||
| |||
| Other Buildings, Roofs, etc. |
| |
|
|
| |
| Negative Pressure in Boiler Room | Remove Exhaust Fan | |
| (Due to Exhaust Fan or Duct System) | or Isolate Fan From Boiler Room | |
|
|
| |
| Insufficient Combustion Air Openings | Provide Correctly Sized Combustion and | |
|
| Ventilation Air Openings |
46