Keating Of Chicago Gas Custom Pasta System Preventive Maintenance, Limited Calibration, Hourly

Page 13
PREVENTIVE

(at 1-800-KEATING) before calling a local service company

PREVENTIVE

MAINTENANCE

Preventive maintenance should be done in daily, weekly, monthly and yearly intervals as necessary. Following preventive maintenance procedures will help keep your Pasta System working efficiently. Proper care and servicing will lead to years of quality performance.

￿NOTE: The most important part of any maintenance program is daily cleaning. Ninety percent of any maintenance problem is directly or indirectly related to cleanliness.

￿NOTE: Water level problems caused by the sensors not being cleaned adequately will not be covered under warranty.

PREVENTIVE MAINTENANCE CHART

TIME FRAME

OPERATOR/OWNER

SECTION

Hourly

• Clean sensor tube with a brush

 

 

 

 

Daily

• Check lights and controls.

III

 

• Check water level.

 

 

• Clean all baskets.

 

 

 

 

Weekly

Boil-out Pasta Cooker

III

 

(2-3 times/week)

 

 

• Drain and clean Pasta Cooker

 

 

 

 

Monthly

• Verify thermostat settings

IV & V

 

(primary and secondary)

 

 

 

 

Yearly

QUALIFIED SERVICE

IV & V

 

PERSONNEL ONLY

 

 

• Disassemble Pasta Cooker to

 

 

clean burners, orifices and

 

 

runner pilot tube.

 

 

• Check and replace radiants.

 

 

• Align burners

 

 

 

 

* High production facilities should be checked more often.

NOTE: Use of sodium chloride (salt) during the cooking process will have a detrimental effect on the cooker vessel and will void the warranty.

LIMITED CALIBRATION

Calibration is not covered under warranty

A. Calibration

￿NOTE: This procedure can only be used with the primary (left side) thermostat. When calibrating the secondary (right side) thermostat.

You will need:

One standard flat blade screwdriver.

One accurate thermometer suitable for boiling water.

￿NOTE: For best results, water should be clean.

1.Set thermostat to 212°F(190°C).

2.Allow Pasta System to cycle three times.

3.Place an accurate thermometer in the water.

Figure 4-1: Thermometer in water

￿NOTE: Locate thermometer in same position for every calibration. Position near primary thermostat (center) bulb is recommended.

4.If calibration of thermostat is found to be less than 15°F(-9.44°C) off, simply loosen three dial plate retaining screws, rotate dial plate to match thermometer reading and tighten screws. If the thermostat is more than 15°F(-9.44°C) off then a qualified service company must be contacted to have the Pasta System properly calibrated.

Figure 4-2

Thermostat calibration

B.The Water Auto-Fill and Low Water Safety Shut- Off Systems

The water supply connection, located at the bottom rear of the Pasta System and marked water, is a standard 3/8” female pipe connection. The water pressure should be between 20-60 psi. If the pressure exceeds 60 psi, a pressure regulator must be used. The water temperature must not exceed 150°F(65.6°C). Hot or warm water is not needed due to the instant recovery of the Pasta System.

PREVENTIVE MAINTENANCE CHARTCAUTION

Connections suitable for hot water must be used. All connections must be tested for leaks before using the Pasta System.

￿NOTE: For Pasta Systems with casters, flexible hose must be used to avoid leaking when the Pasta System is moved for cleaning.

Control of the water level is fully automatic with the

10

Image 13
Contents 1-800-KEATING KEEP THIS MANUAL FOR TRAINING NEW PERSONNELGas Pasta 0107 9/07 POST THIS LABEL IN A PROMINENT LOCATION ON YOUR UNIT SECTION II INSTALLATION TABLE OF CONTENTSSECTION IV MAINTENANCE SECTION V SERVICE DIAGNOSISSTANDARD FEATURES I INTRODUCTIONSTANDARD ACCESSORIES SAFETY PRECAUTIONSCLEARANCES INSTALLATION II INSTALLATIONPOSITIONING CLEARANCES DAMAGE DURING SHIPMENTRESTRAINING DEVICES SPECIFICATIONSGAS CONNECTION HAVE YOUR PLUMBER OR GAS COMPANY CHECK FOR LEAKSELECTRICAL CONNECTION GAS LEAK TESTINGCHECK GAS SUPPLY PRESSURE SPECIAL NOTICESCALIBRATION III OPERATINGWATER AND DRAIN CONNECTIONS FILLINGCOOKING INDICATING LIGHTSSHUTDOWN DRAININGELECTRONIC TIMERS CLEANINGDisconnect electric power source before cleaning A. Timer OperationELECTRONIC TIMER OPERATING INSTRUCTIONS PART # IV MAINTENANCEWARRANTY REPAIRS B. How to program the “Keating” Electronic TimerPREVENTIVE MAINTENANCE CHART PREVENTIVE MAINTENANCEB. The Water Auto-Fill and Low Water Safety Shut- Off Systems LIMITED CALIBRATIONUsing a worn brush could damage the sensors SOLUTION PROBLEMPROBABLE CAUSE SOLUTION SOLUTIONS Follow Sequentially REPLACEMENT OF A AND B BOARDS CUSTOM PASTA SYSTEM CONTROL PANEL WITH DIGITAL TIMERS V SERVICE DIAGNOSISMANUAL FILL CUSTOM PASTA SYSTEM CONTROL PANEL WITH DIGITAL TIMERS MODELS GAS PASTA SYSTEM ASSEMBLYPART# DESCRIPTION PASTA SYSTEM WIRING DIAGRAM GAS PASTA SYSTEM WITH BASKET-LIFT WIRING DIAGRAM The Customer must provide proof of purchase from Keating WARRANTYKEATING If you have a service related question call 1-800-KEATING SERVICE INFORMATIONHave your serial and model number available when ordering parts “Serving Those Who Serve The Very Best”