SECTION 3
INSTALLATION AND INITIAL
•Carefully measure VDC at the PV disconnect switch. The value should be the same as at the PV array string disconnect device. It should also be positive.
•Close the PV disconnect switch (if present).
•Carefully measure VDC across TBDC+ and TBDC- (PV
•Open the PV disconnect switch. The matrix capacitor bank voltage should slowly degrade to near zero over a
•Open all PV string disconnect switches.
System Verification
•Ensure the on/off switch is disabled.
•Upon applying 208 VAC power to the
•Remedy any faults reported. If the fault indicator does not change, the fault condition is still present (see Section 5). Cycling the on/off switch will reset the
•Close all PV array string disconnect switches (if present).
•Close the main PV disconnect switch (if present).
•Turn the on/off switch to the on position.
•If the PV voltage is above the PV Start Voltage setpoint, and the PV Start Time is exceeded, the PV- 30208 should transition to “Power Tracking” (see Section 4, Operation).
•Depending upon solar conditions, the
•The
Fine Tuning
•All
•It is recommended that the
NOTE
Some field adjustable parameters are password protected and may only be changed by trained service technicians. In particular are parameters relating to utility protection setpoints. These have been set in the factory to the limits mandated by UL1741. Any changes to these setpoints should be agreed upon by the local utility and the equipment owner.
DOCUMENT: 151315PV-30208 Photovoltaic Inverter3-8
Operation and Maintenance Manual
Copyright 2003, Xantrex Technology Inc.