SECTION 5
TROUBLESHOOTING
This fault is
(5) AC Line Over Frequency Fault (0x0800)
The AC frequency exceeded the
Possible causes:
•The utility frequency exceeded the allowable limit (60.5 Hz by default). Verify the utility frequency is stable and within allowable operating limits.
•There is a problem with one or more of the AC sense wires (see system schematic in Section 7).
This fault is
(6) Ground Current Fault (0x8000)
The earth safety ground current has exceeded the
Possible causes:
•The negative wire from the PV array has been passed through CT1. Verify PV ground jumper is installed between TBDC- and TB NEUT.
•Inspect the PV array for actual ground faults.
•The PV array has been grounded in more than one location. If the PV array is grounded through CT1, it must not be grounded at any other location.
•CT1 defective: Contact your Xantrex Technology distributor for assistance or service.
(7) DC Bus Over Voltage Fault (0x4000)
The DC bus voltage has exceeded the maximum limit.
This is also the PV input voltage sense point. Check the PV input voltage at the PV disconnect switch. If the voltage is below 600 VDC and agrees with the voltage displayed on the LCD, cycle the on/off switch and restart the
Possible causes:
•The PV array open circuit voltage exceeded 600 VDC.
•There is a problem with the PV voltage sense wiring (see system schematic in Section 7).
(8) CT Offset Fault (0x80000)
Upon system startup, the
•Observe individual phase currents with the operator interface program. Generally, a CT offset fault with show high currents on one phase while the system is in Standby, with zero actual current being
DOCUMENT: 151315PV-30208 Photovoltaic Inverter5-4
Operation and Maintenance Manual
Copyright 2003, Xantrex Technology Inc.