Xantrex Technology PV-30208 Section Product Description Specifications, Equipment Symbol

Page 5

SECTION 1

PRODUCT DESCRIPTION

SPECIFICATIONS

The PV-30208 has been designed for photovoltaic power systems, which operate within the following specifications. Application of the PV-30208 in a manner inconsistent with these specifications may cause damage to the PV-30208 and other system components, and is a violation of the terms of the warranty.

Nominal AC Line Voltage

208 VAC, +10% -12%

 

 

Maximum AC Line Current

94 ARMS (at low line voltage)

 

 

Nominal Line Frequency

60 Hz, +0.5 Hz -0.7 Hz

 

 

Continuous AC Output Power

30.0 KW @ 208 VAC 3 Phase

 

 

PV MaximumVoltage

600 VDC

Peak Power Tracking Window

330*-600 VDC

 

 

PV Minimum Peak Power Tracking Voltage

330

 

 

PV Maximum Current

100 ADC

 

 

PV Maximum Array Short Circuit Current

138 ADC

 

 

PV Configuration

Monopolar negative grounded, or bi-polar

neutral ground

 

Operating Temperature

**-20 to 50° C

 

 

Storage Temperature

-40 to 50° C

 

 

Maximum Ambient Temperature Rating

50° C

 

 

Relative Humidity

To 95%, Non-condensing

 

 

Elevation

Derated above 6,600 feet

 

 

Dimensions (in inches)

54.5 X 35.6 X 19

 

 

Weight

Approx. 260 lbs.

 

 

Enclosure Type

NEMA 3R

 

 

UL Listing File

File-E199356

 

 

*Dependent on actual AC line voltage. Refer to Section 4 for detail on the minimum power tracking voltage.

**If ambient temperature is between -20 to 0° C, the unit must be powered up in standby for at least one hour prior to going on-line.

EQUIPMENT SYMBOL

Chassis ground – Customer supplied system ground connection point. This symbol may be found near a stud within the main enclosure. It is provided as a location to bond the electrical system equipment ground.

DOCUMENT: 151315PV-30208 Photovoltaic Inverter1-3

Operation and Maintenance Manual

Copyright 2003, Xantrex Technology Inc.

Image 5
Contents Copyright 2003, Xantrex Technology Inc South Vasco RoadTable of Contents Main Enclosure Section Product Description IntroductionMajor Components Interconnection Standards Compliance Section Product DescriptionMatrix Bus Board Solar Control Unit SCUEquipment Symbol Section Product Description SpecificationsPV Ground Fault Detection Section Safety Safety FeaturesEnclosure Front Access Panel Anti Island Protection Section Safety Isolation ProcedureUtility Side Isolation Transformer Requirements Torque and Wire Gauge SpecificationsInstallation Instructions Section Installation and Initial TURN-ONInstallation Floor MountedSection Installation and Initial TURN-ON Array Grounding Ground Fault DetectionPhase-Sequencing Section Installation and Initial TURN-ON PV-30208 Inverter Wiring Diagram Optional BoxFrame Optional PV Conductor PV Array Ground Jumper Initial Power Visual Inspection, PV Array WiringVisual Inspection, Isolation Transformer WYE/WYE Visual Inspection, PV-30208System Verification Fine TuningOperating States Section Operation Description of System OperationOverview Section Operation Operation Features Block Diagram Of Monopolar ConfigurationSection Operation Current Imbalance Detection Peak Power TrackingDC Overvoltage Detection Automatic Wake Up PV Voltage OptimizationSection Operation Operator Interface Example of Normal System Operation System Fault System Sleep Test System Stop System ShutdownSection Operation System Operating Parameters User Factory Password Parameter Description Section Operation Fault Conditions Section Troubleshooting GeneralIPM Device Fault 0x0001 Through Fault DescriptionsAC Line Voltage Low Fault Section TroubleshootingAC Line Voltage High Fault AC Line Under Frequency FaultGround Current Fault AC Line Over Frequency FaultDC Bus Over Voltage Fault CT Offset FaultStop Switch Fault Current Imbalance FaultSection Preventative Maintenance Periodic Maintenance TURN-ON Procedure Section Preventative MaintenanceOptional Accessories Section Drawings and Parts List Drawings ListWarranty and Certifications Page Page Page Page Page Enclosure, Upper Page Xantrex PV Series Limited Warranty and Registration