SECTION 4
OPERATION
Current Imbalance Detection
In the event of phase-to-phase current imbalance of greater than 20% between phases, the inverter will execute an orderly shutdown, and annunciate a fault at the operator interface. See Section 5, Trouble- shooting, for further information on this fault condition.
DC Overvoltage Detection
In the event of DC voltage greater than 600Vdc, the PV-30208 will execute an orderly shutdown and annunciate a fault to the operator interface. If DC voltage remains greater than 600Vdc, the PV-30208 may be irreparably damaged. See Section 5, Troubleshooting for further information on this fault con- dition.
Peak Power Tracking
The PV-30208 control software employs an active PV peak power tracker, designed to maintain maxi- mum power output from the PV array at all times of operation. The peak power voltage point varies primarily depending upon the temperature of the PV cells. The PV-30208 constantly seeks the opti- mum voltage and current operating points of the PV array to maintain maximum PV power output.
Automatic Wake Up PV Voltage Optimization
Every day the PV-30208 wakes up and starts producing power, the control software determines if it is necessary to make adjustments to the start voltage setpoint. If the PV-30208 wakes up and determines that there is insufficient PV array power to support inverter operation, the start voltage setpoint is shifted slightly higher. This assumes that once the voltage on the array has risen, there will be greater PV power as the PV array is exposed to higher irradiance. Conversely, if the PV-30208 wakes up and determines that there is more power than is necessary to support inverter operation, the PV start voltage setpoint is lowered. The PV start voltage setpoint will usually be optimized over the period of one week. This value may be manually adjusted via the graphical user interface program to expedite the optimization process. There is also a user settable timer that determines the time required for the PV start voltage to exceed the start voltage setpoint. This timer may also be manually adjusted via the graphical user interface to help compensate for poorly placed PV arrays. The default wake-up time delay is factory set at five minutes.
Automatic Sleep Test
Toward the end of every solar day, the PV-30208 automatically determines when to stop producing power dependent upon the output power of the inverter. As the net output power of the PV-30208 nears zero, a timer is started to allow the inverter to ride through any brief irradiance reductions. The default sleep time delay is factory set at five minutes.
DOCUMENT: 151315 | PV-30208 Photovoltaic Inverter | 4-4 |
| Operation and Maintenance Manual | |
Copyright 2003, Xantrex Technology