Xantrex Technology PV-30208 Fault Descriptions, IPM Device Fault 0x0001 Through

Page 26

SECTION 5

TROUBLESHOOTING

FAULT DESCRIPTIONS AND TROUBLESHOOTING

FAULT DESCRIPTIONS

Fault Description

Fault Code (LCD)

 

 

IPM Device Fault A+

0x0001

 

 

IPM Device Fault A-

0x0002

 

 

IPM Device Fault B+

0x0004

 

 

IPM Device Fault B-

0x0008

 

 

IPM Device Fault C+

0x0010

 

 

IPM Device Fault C-

0x0020

 

 

AC Line Under Voltage

0x0100

 

 

AC Line Over Voltage

0x0200

 

 

AC Line Under Frequency

0x0400

 

 

AC Line Over Frequency

0x0800

 

 

Ground Current Fault

0x8000

 

 

DC Bus Over Voltage

0x4000

 

 

CT Offset Fault

80000

 

 

Current Imbalance

100000

 

 

(1) IPM Device Fault (0x0001 Through 0x0020)

Both over current and over temperature condition can cause IPM device faults. The fault code for both conditions is the same for each device, while there is a unique fault code for each device.

Possible causes for over current condition:

Short circuit in output AC line.

Low supply voltage to IPM control circuit.

Shorted isolation transformer.

Possible causes for over temperature condition:

External cooling fan inoperable.

Airflow on heatsink impeded due to accumulation of debris.

Operation above rated ambient temperature for an extended period of time.

Auxiliary contact block on contactor K1 inoperable. This is only possible if the fan does not operate

DOCUMENT: 151315PV-30208 Photovoltaic Inverter5-2

Operation and Maintenance Manual

Copyright 2003, Xantrex Technology Inc.

Image 26
Contents South Vasco Road Copyright 2003, Xantrex Technology IncTable of Contents Main Enclosure Section Product Description IntroductionMajor Components Matrix Bus Board Section Product DescriptionInterconnection Standards Compliance Solar Control Unit SCUSection Product Description Specifications Equipment SymbolPV Ground Fault Detection Section Safety Safety FeaturesEnclosure Front Access Panel Section Safety Isolation Procedure Anti Island ProtectionTorque and Wire Gauge Specifications Utility Side Isolation Transformer RequirementsInstallation Section Installation and Initial TURN-ONInstallation Instructions Floor MountedSection Installation and Initial TURN-ON Array Grounding Ground Fault DetectionPhase-Sequencing Section Installation and Initial TURN-ON PV-30208 Inverter Wiring Diagram Optional BoxFrame Optional PV Conductor PV Array Ground Jumper Visual Inspection, Isolation Transformer WYE/WYE Visual Inspection, PV Array WiringInitial Power Visual Inspection, PV-30208Fine Tuning System VerificationOperating States Section Operation Description of System OperationOverview Section Operation Operation Features Block Diagram Of Monopolar ConfigurationSection Operation DC Overvoltage Detection Peak Power TrackingCurrent Imbalance Detection Automatic Wake Up PV Voltage OptimizationSection Operation Operator Interface System Fault System Sleep Test System Stop System Shutdown Example of Normal System OperationSection Operation System Operating Parameters User Factory Password Parameter Description Section Operation Section Troubleshooting General Fault ConditionsFault Descriptions IPM Device Fault 0x0001 ThroughAC Line Voltage High Fault Section TroubleshootingAC Line Voltage Low Fault AC Line Under Frequency FaultDC Bus Over Voltage Fault AC Line Over Frequency FaultGround Current Fault CT Offset FaultCurrent Imbalance Fault Stop Switch FaultSection Preventative Maintenance Periodic Maintenance Section Preventative Maintenance TURN-ON ProcedureOptional Accessories Section Drawings and Parts List Drawings ListWarranty and Certifications Page Page Page Page Page Enclosure, Upper Page Xantrex PV Series Limited Warranty and Registration